Quick Start Guide
Minipack PS System
356808.103, 1v2-2008-10
14
CAN Bus Termination
Minipack
systems are shipped from factory
with the CAN bus already terminated with
120
Ω
resistors.
To ensure a correct bus communication and
avoid data reflection, you must
always
terminate the CAN bus with two 120
Ω
resistors, one at each end of the line (60
Ω
bus impedance). The figure shows a
Minipack
system with its controller
communicating with the rectifiers via the
CAN bus.
CAN Bus Addressing
All rectifiers,
Smartpack
controllers and other control units connected to the
Eltek Valere
’s CAN
bus must have a unique address or ID number. The control system’s master controller assigns
automatically the rectifiers’ addresses (
software assignment
). The controller registers the
rectifiers’ ID numbers – or CAN bus address (01, 02 ...) – together with their Serial Numbers.
The control system’s controllers and control units use DIP switches for configuring their unique
CAN bus ID number (
hardware assignment
).
You can address a maximum of 14 control units of each type –
Smartpack
controllers,
Smartnode
units, Battery Monitors, Load Monitors, etc. – to the control system’s CAN bus. See table below:
Number of nodes
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Smartpack
controllers
1 2
3 4 5 6 7 8 9 10 11 12 13 14
15 16
<-- ID #
Smartnodes
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
<-- ID #
Battery
Monitor
CAN
nodes
33 34
35 36 37 38 39 40 41 42 43 44 45 46
47 48
<-- ID #
Load Monitor CAN nodes
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
<-- ID #
65 66
67 68 69 70 71 72 73 74 75 76 77 78 79 80
<-- ID #
I/O Monitor CAN nodes
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
<-- ID #
Mains
Monitor
nodes 97 98 99 100 101 102 103 104 105 106 107 108 109 110
111 112
<-- ID #
ID numbers formatted in italics (column 15 and 16 and range 65-78) are not available due to
software constraints. For DIP switch configuration, refer to chapter “CAN Bus Nodes”, page 24.
The figure shows a
Minipack
DC power system expanded with 3 CAN nodes to implement
additional digital inputs, relay outputs or similar functionality.
Appendix
Communication
120
Ω
Minipack
DC Power System
End-of-Line
Resistor
End-of-Line
Resistor
120
Ω
CAN bus
(twisted-pair internal
CAT5 cable)
USB A-B cable
(standard)
1
02
n
01
Battery string #1
CAN bus
(twisted-pair CAT5 cable)
1
33
Battery
Monitor
ID Number
I/O Monitor
81
Minipack
Rectifiers
Alarm Outputs NC-C-NO
Config. Inputs
Temp, Fan Speed Mon & Ctrl
49
End-of-Line
Resistor
120
Ω
Fuses
Fuse Monitoring
Configurable Inputs
Current Monitoring
Sense Inputs
Shunts
Smartpack
controller,
Master
Alarm Outputs
NC-C-NO
Digital Inputs
USB A-B cable (standard)
CAN bus
CAN bus
Load Monitor
Minipack
DC Power System
120
Ω
02
n
01
Содержание Minipack
Страница 17: ...PULLOUT Check Lists Pullout Pull out the pages with the gray outer band and use them as check lists...
Страница 20: ......
Страница 22: ...PULLOUT...
Страница 24: ...PULLOUT Check Lists Pullout Pull out the pages with the gray outer band and use them as check lists...
Страница 35: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 27...
Страница 36: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 28...
Страница 39: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 31...