INSTALLATION CHECK LIST
System Data
Minipack P
S S
ystem
Minipack
Power Supply System
, type
:
Artic
le No.:
Site,
name:
Serial No.:
Softw
are, version No
.:
Rectifiers,
ty
pe & number of:
AC I
nput Volt
age, m
easured:
Batte
ry Type:
Batte
ry Capacity:
Inst
allation carried o
ut by,
name:
Site Preparations
CARRY OUT
FOLLOWING
:
OK
1.
Organize the installation
site
o
Prepare a 2U hig
h spare location in existing 19”, 25
0 mm cabinet; C
heck min. clearance: front access, 60 cm
o
Ensure the installation site is suitably
ventilated a
nd
in a non-explosive atmosphere.
2.
Prepare the installation t
ools
o
Check that insulated tools suitable for telecom installations are used
3.
Prepare AC Supply: AC i
nput cable(s) and fuses
o
Check the AC supply is the correc
t t
ype, an
d that the ex
ternal AC f
uses and AC input cable(s) are s
uitably
rated
Mechanical Installation
Power is OFF!
CARRY OUT
FOLLOWING
:
OK
4.
Remove packaging and
check equipment
o
Check you have
received all the parts and correct documentation.
o
Inspect the equipm
ent for phys
ical damage (repo
rt an
y dam
ages)
o
Leave rectifier modules in their packaging or in t
he selves, if factory installed. (commissioning task)
5.
Remove the cabinet’s to
p cover and dummy front panels
o
Check that cable entry
from the to
p is possible
o
Connection terminals are accesse
s by opening the
dra
wer
shelf
6.
Position and fasten the subassembly
o
Subassemblies
in existing 19” or in ETSI cabinets, using
brackets, and 3ph AC Inpu
t Connection Kit, if required
7.
Mount the external batteries on the shelves
o
Start (if applicable) on the lower
shelf first, and continue up
wards
o
Do not term
inate
the batter
y cable
s yet
!
8.
Open the
Minipack
drawer shelf and
lift the plastic cover
o
Unlock the upper and lo
wer scre
ws and slide the drawer
shelf open, then lift the Melenex plastic cover
Electrical Installation
Power is OFF!
CARRY OUT
FOLLOWING
:
OK
9.
Make the system completely voltage free
o
Switch OFF
or re
move all load fuses (MCB1, MCBx), bat
tery fuses
(Fb1, Fbx) and
extern
al AC supply fuses
10.
AC Connections
(or connect to the 3ph AC Kit)
o
Check AC configuration
: Make available 3 single p
hase mains feed and earth (PE)
o
Connect the AC Earth wire
(PE)
to
the terminals AC Earth (PE)
o
Connect the AC input cable(s)
to the terminals. Ca
ble and terminal
block labeling are to correspond
11.
DC Connections
⎯
Load Circuits
o
Term
inate DC
Ea
rth (T
E):
Common DC
Output Ra
il is connected to TE at onl
y o
ne place
o
For each DC
load
, connect one of the cables to the common DC out
put terminal; the
other to the fuse
terminal
12.
DC Connections
⎯
Alarm & Signal Circuits
o
Refer to you
r s
yst
em’s connection dra
wings
and configuration, or t
o the Quick Start
Guide
o
Term
inate Alarm
Circuit cables
to the relay
output te
rminals
o
Term
inate Signal Circuit cables
to the digital input/output terminals
13.
DC Connections
⎯
Battery Cables
Careful! Use correct polarity.
For each batter
y shelf,
o
Mount 3 inter
cell links
to connect in series 4 battery blocks
o
Connect battery cables
to fuses and Common Batter
y, a
nd to the shelf’s outer termi
nals; (+) and (-)
o
Connect battery sym
metry cables
, if applicable, to the input terminals
o
Connect the temperatur
e sensor cable
, if applicable, to the D-Sub p
lug or input termi
nal, and fix the sensor (at th
e
end of the cable) to a suitable place in
the middle of the installed battery
bank
Approval
Responsible of
installat
ion,
sign.:
Date:
Approved by cu
stomer,
sign.:
EMC
regard
Electric
shock
Device
hazard
Electric
shock
www.elte
kvalere.com
Hea
dquarte
rs:
Eltek Va
lere
1303 E. A
rapaho R
d, R
ichards
on, TX.
75081,
USA
Phone: +1 (
469) 330-
9100
Fax: +1 (469) 3
30-9101
Eltek Va
lere
Gråteru
dv. 8, PB 2
340 Str
ømsø, 3
003 Dram
men, Norw
ay
Phone: +47
32 20 32
00 Fax: +47 3
2 20
32 10
Содержание Minipack
Страница 17: ...PULLOUT Check Lists Pullout Pull out the pages with the gray outer band and use them as check lists...
Страница 20: ......
Страница 22: ...PULLOUT...
Страница 24: ...PULLOUT Check Lists Pullout Pull out the pages with the gray outer band and use them as check lists...
Страница 35: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 27...
Страница 36: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 28...
Страница 39: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 31...