34
Installation
, connection and commissioning
Output
Function
DA1
Pulse output for the total standard volume "VbT"
11
(CP.O1= 0.1 Imp/m
3
)
DA2
Pulse output for the total standard volume "VmT" (CP.O2= 0.1 Imp/m
3
)
The cp value of an output states how many pulses were emitted per cubic meter. A cp value
of 0.1/m3 (0.1 pulses per m3) means that e.g. a pulse is emitted per 10m3.
To change the cp values for output 1 or output 2, move the cursor to the "Serv." tab and via
the following path to "CP.O1" (output 1) or "CP.O2" (output 2):
Serv.
Outputs
Output 1
CP.O1
or
Serv.
Outputs
Output 2
CP.O2
Press the key combination ENTER
+
One digit of the cp value flashes.
Move the cursor with the arrow buttons
or
to the digits and change these with the
arrow buttons
or
.
Press the key combination ENTER
+
to confirm the set value. It is possible to abort
the entry by pressing the key combination ESC
+
.
Except for the settings described here, many additional functions, such as time
synchronous pulses, can be set for the outputs.
The complete description can be found in the application manual EK205, which
you can download from www.elster-instromet.com.
5.3.1.11 Setting summer time switching
Move the cursor to the "Serv." tab and via the following path to the value "MdTim"
(summer time mode):
Serv.
Date and time
MdTim
Press the key combination ENTER
+
The value set flashes.
Change the value using the arrow buttons
or
:
Mod.Z
Meaning
off
No switching to CEST*
auto
Automatic switching to CEST*
manual
Every year, the start and end of CEST* is set by the control room.
*CEST = Central European Summer Time
Press the ENTER
+
button to confirm the set value. It is possible to abort the entry
by pressing the key combination ESC
+
.
5.3.1.12 Delete measurement archives
It is not mandatory to delete the archives on commissioning.
11
VbT must not be used for billing purposes.
Содержание EK205
Страница 1: ...Operating manual Volume conversion device EK205 ...
Страница 6: ......
Страница 64: ...64 Appendix 9 2 Conformity declarations19 19 IECEx is not available for all device types ...
Страница 65: ...Appendix 65 9 3 Design test certifications 9 3 1 ATEX EC Type Examination Certificat ...
Страница 66: ...66 Appendix ...
Страница 67: ...Appendix 67 ...
Страница 68: ...68 Appendix 9 3 2 IECEx Certificate of Conformity20 20 Not available for all device types ...
Страница 69: ...Appendix 69 ...
Страница 70: ...70 Appendix ...
Страница 71: ...Appendix 71 ...