20
Technical
data
3.7 Optical serial interface
Information
Value
Unit
Baud rate
9600
Bd
Format
1 start, 1 parity, 1 stop bit
3.8 Electrical serial interface
Information
Value
Adjustable types
RS232 or RS485
Cable length
max. 10 m
3.8.1 RS485 type
Parameter
Value
Operating types
RS485 2-wire (semi-duplex)
RS485 4-wire (full-duplex)
Scheduling
No load resistor usable in the connected bus
participants
Maximum data transmission rate 19,200 baud
Number of bus participants
Drive performance at the outlet: max. 16 unit loads
2
Received power at the input
3
:
- 6 unit loads (RS485, not electr. insulated)
- 3 unit loads (RS485, electr. separated)
Cable length
max. 10 m
3.9 Operating conditions
3.9.1 Environment
Information
Value
Unit
Temperature range
-25 – +55
°C
Relative humidity, maximum
93
%
Humidity conditions acc. EN12405-1
condensation
Point of use acc. EN12405-1
open
Mechanical ambient conditions acc. EN12405-1
M2
Electromagnetic ambient conditions acc. EN12405-1
E2
2
Unit load: Standard RS485 receiver with an input resistance = 12kOhm
3
Details on the connection of the RS485 interface, see application manual
Содержание EK205
Страница 1: ...Operating manual Volume conversion device EK205 ...
Страница 6: ......
Страница 64: ...64 Appendix 9 2 Conformity declarations19 19 IECEx is not available for all device types ...
Страница 65: ...Appendix 65 9 3 Design test certifications 9 3 1 ATEX EC Type Examination Certificat ...
Страница 66: ...66 Appendix ...
Страница 67: ...Appendix 67 ...
Страница 68: ...68 Appendix 9 3 2 IECEx Certificate of Conformity20 20 Not available for all device types ...
Страница 69: ...Appendix 69 ...
Страница 70: ...70 Appendix ...
Страница 71: ...Appendix 71 ...