6.12. Humidity PI control
The chapter "Humidity PI control" only applies to the TH-L-Pr model.
If you activate humidity control, you can use the following settings to define control ty-
pe, setpoint values, and humidification and dehumidification.
General control
The sensor can be used to control one- or two-level dehumidification or combined hu-
midification/dehumidification.
Configure a block for the humidity control using the blocking object.
Specify when the current control variables are to be sent to the bus. Periodic sending
is safer, in case a message does not reach a recipient. You may also set up periodic
monitoring using an actuator with this setting.
The status object shows the current status of the output variable (0 = OFF,
>0 = ON) and can for example be used for visualisation.
Controller setpoint
Set, in which cases
setpoint values
received via object are to be retained. Please note
that the setting "After power supply restoration and programming" should not be used
Use humidity control
No • Yes
Type of control
• One-level dehumidification
• Two-level dehumidification
• Humidification and dehumidification
Behaviour of the blocking object with value
• 1 = Block | 0 = release
• 0 = block | 1 = release
Blocking object value
before first communication
0 • 1
Send control variable
• on change
• on change and periodically
Send cycle
(
is only sent if "periodically" is selected)
5 s • 10 s • ... • 5 min • … • 2 h
Send status object(s)
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Send cycle
(
is only sent if "periodically" is selected)
5 s • 10 s • ... • 5 min • … • 2 h