Thermo-Hygrometer

KNX TH-UP

Installation and Adjustment

Содержание KNX TH-UP basic

Страница 1: ...Thermo Hygrometer KNX TH UP Installation and Adjustment ...

Страница 2: ...l 19 Humidity measured value 26 Humidity threshold value 27 Humidity threshold value 1 2 28 Humidity PI control 30 Dew point temperature 34 Cooling medium temperature sensor 35 Absolute humidity 37 Comfort field 38 Logic 39 AND Logic 1 2 3 4 40 Linkage inputs of AND logic 41 OR Logic 1 2 3 4 42 Linkage inputs of OR logic 43 Display Settings 43 KNX TH UP from software version 0 2 0 ETS programme ve...

Страница 3: ...2 ...

Страница 4: ...oint Display 1 3 rows own values or values received from the bus Mixed values from own measured values and external values proportions can be set in percentage PI controller for heating one or two step and cooling one or two step depending on temperature PI controller for ventilation depending on humidity Dehumidify humidify one step or dehumidify one or two step 7 switching outputs with adjustabl...

Страница 5: ...orage 20 60 C Ambient air humidity max 95 R H avoid bedewing Operating voltage KNX bus voltage Bus current max 6 mA max 10 mA when programming LED is active Data output KNX bus terminal plug BCU type Own micro controller PEI type 0 Group addresses max 184 Allocations max 184 Communication objects 117 Measurement range temperature 40 100 C Resolution 0 1 C Accuracy 0 4 C at 25 C Measurement range h...

Страница 6: ... The sensor is exclusively intended for appropriate use With each inappropriate change or non observance of the instructions for use any warranty or guarantee claim will be void After unpacking the device check immediately for any mechanical damages In case of transport damage this must immediately notified to the supplier If damaged the sensor must not be put into operation If an operation withou...

Страница 7: ... element or draught from windows or doors will distort the values measured Infiltration from pipes that lead to the socket where the sensor is installed from other rooms may cause false measurement results too The sensor may be installed and operated in dry interior rooms only Avoid condensation Composition Casing 1 Notches 2 Air circulation holes 3 Programming LED recessed 4 Programming button re...

Страница 8: ... position the frame of the switching programme Connect the bus line black red plug to the terminals provided on the sensor board of KNX TH UP Pin the sensor with the notches on to the metal frame so that sensor and frame are fixed Notes on installation Sensor must not be exposed to water rain or dust This could result in the electronic being damaged A relative air humidity of 95 must not be exceed...

Страница 9: ...T 5 Maximum measured value for temperature Output 9 001 C R T 6 Reset min max measured value for temperature Input 1 017 C W 7 Temperature sensor malfunction Output 1 001 C R T 9 Temp threshold value 1 Absolute value Input Output 9 001 C R W T U 10 Temp threshold value 1 1 0 Input 1 006 C W 11 Temp threshold value 1 Switching output Output 1 001 C R T 12 Temp threshold value 1 Switching output blo...

Страница 10: ...rol Target value current Output 9 001 C R T 27 Temp control Blocking object Input 1 006 C R W 28 Temp control Target value day heating Input Output 9 001 C R W T U 29 Temp control Target value day heating 1 0 Input 1 002 C W 30 Temp control Target value day cooling Input Output 9 001 C R W T U 31 Temp control Target value day cooling 1 0 Input 1 002 C W 32 Temp control Act variable heating 1 stage...

Страница 11: ... closed 1 open Input 1 019 C W 48 External measured value for humidity Input 9 007 C W 49 Internal measured value for humidity Output 9 007 C R T 50 Total measured value for humidity Output 9 007 C R T 51 Request min max measured value for humidity Input 1 017 C W 52 Minimum measured value for humidity Output 9 007 C R T 53 Maximum measured value for humidity Output 9 007 C R T 54 Reset min max me...

Страница 12: ... control Act variable humidification Output 5 001 C R T 69 Dew point temperature Output 9 001 C R T 70 Cooling medium temp Threshold value Output 9 001 C R W T U 71 Cooling medium temp Actual value Input 9 001 C W 72 Cooling medium temp Offset change 1 0 Input 1 006 C W 73 Cooling medium temp Switching output Output 1 001 C R T 74 Cooling medium temp Switching output block Input 1 006 C W 75 Absol...

Страница 13: ...001 C R T 99 OR logic 1 8 bit output A Output 5 010 C R T 100 OR logic 1 8 bit output B Output 5 010 C R T 101 OR logic 2 1 bit Output 1 001 C R T 102 OR logic 2 8 bit output A Output 5 010 C R T 103 OR logic 2 8 bit output B Output 5 010 C R T 104 OR logic 3 1 bit Output 1 001 C R T 105 OR logic 3 8 bit output A Output 5 010 C R T 106 OR logic 3 8 bit output B Output 5 010 C R T 107 OR logic 4 1 ...

Страница 14: ...for Measured values 5 s 10 s 30 s 1 min 2 h Threshold values and switching outputs 5 s 10 s 30 s 1 min 2 h Target values and actuating variables 5 s 10 s 30 s 1 min 2 h Logic outputs 5 s 10 s 30 s 1 min 2 h Maximum telegram quota 1 2 3 5 10 20 Telegrams per second Use malfunction object No Yes ...

Страница 15: ...y send in case of change send in case of change and periodically From change of only if sending in case of change 2 5 10 25 50 Send periodically all only if sending periodically 5 s 10 s 30 s 1 min 2 h Use min and max temperature values Values are not maintained after reset No Yes If an external measured value is used Use external measured value for temperature Yes Ext temperature measured value p...

Страница 16: ...ll following settings refer to the total measured value From change of only if sending in case of change 2 5 10 25 50 Send periodically all only if sending periodically 5 s 10 s 30 s 1 min 2 h Use min and max temperature values Values are not maintained after reset No Yes Temperature threshold values Use temperature threshold value 1 2 3 4 No Yes ...

Страница 17: ...tion object Temperature threshold value standard per Communication object The value communicated last shall be maintained not after restoration of voltage after restoration of voltage and programming Do not use for first commissioning Start temperature threshold value in 0 1 C valid until 1 communication only if the value communicated last is not maintained or after restoration of voltage 300 800 ...

Страница 18: ...ng output sends on change on change to 1 on change to 0 on change and periodically on change to 1 and periodically on change to 0 and periodically Send temperature switching output in the cycle of only if sending periodically 5 s 10 s 30 s 1 min 2 h Blocking Use block of the temperature switching output No Yes Evaluation of the temperature blocking object if value 1 block if value 0 release if val...

Страница 19: ...tching output with release on change do not send telegram send status of the switching output on change to 1 do not send telegram if switching output 1 send 1 on change to 0 do not send telegram if switching output 0 send 0 on change and periodically send status of the switching output no selection on change to 1 and periodically if switching output 1 send 1 no selection on change to 0 and periodi...

Страница 20: ...ype of control One stage heating Two stage heating One stage cooling One stage heating one stage cooling Two stage heating one stage cooling Two stage heating two stage cooling Behaviour of the blocking object with value 1 block control 0 release control 0 block control 1 release control ...

Страница 21: ...ue setpoint per Parameter Target value in 0 1 C 300 800 If the target value is set per Communication object Target value setpoint per Communication object The value communicated last shall be maintained not after restoration of voltage after restoration of voltage and programming Do not use for first commissioning Start target value in 0 1 C valid until 1 communication only if the value communicat...

Страница 22: ... Fan convector Electrical heating Maximum actuating variable is reached at target actual difference of Attention Can only be adjusted if Setting of the controller by controller parameter 1 C 2 C 3 C 4 C 5 C Re setting time in mins Attention Can only be adjusted if Setting of the controller by controller parameter 1 255 If blocked the actuating variable shall will not be sent send a specific value ...

Страница 23: ...ol If the 2 stage is controlled with 2 point control Hysteresis in 0 1 C 0 100 Actuating variable is a 1 bit object 8 bit object Value in only if actuating variable is an 8 bit object 0 100 If blocked the actuating variable shall not be sent send a specific value Value in only if a specific value is sent 0 100 With release the actuating variable follows the control If the 2 stage is controlled wit...

Страница 24: ...is reached at target actual difference of Re setting time Cooling ceiling 5 C 240 min Cooling control 2 stage Appears only if two stage cooling control is used Target value difference between 1 and 2 stage in 0 1 C 0 100 Type of control of the 2 stage 2 point control PI control If the 2 stage is controlled with 2 point control Hysteresis in 0 1 C 0 100 Actuating variable is a 1 bit object 8 bit ob...

Страница 25: ...t before 1 communication 0 1 Target value setpoint per Parameter Communication object If the target value is set per Parameter Target value setpoint per Parameter Target value heating in 0 1 C if the heating control is used 300 800 Target value cooling in 0 1 C if the cooling control is used 300 800 If the target value is set per Communication object Target value setpoint per Communication object ...

Страница 26: ...f the value communicated last is not maintained or after restoration of voltage 300 800 Limitation of object value C min in 0 1 C 300 800 Limitation of object value C max in 0 1 C 300 800 Type of the target value change Absolute value Increment decrement Step size only with Increment decrement 0 1 C 0 2 C 0 3 C 0 4 C 0 5 C 1 C 2 C 3 C 4 C 5 C Frost heat protection Use frost heat protection No Yes ...

Страница 27: ...d in case of change send in case of change and periodically From change of only if sending in case of change 2 5 10 25 50 Send periodically all only if sending periodically 5 s 10 s 30 s 1 min 2 h Use min and max humidity values Values are not maintained after reset No Yes If an external measured value is used Use external measured value for humidity Yes Ext humidity measured value proprotion of t...

Страница 28: ... following settings refer to the total measured value for humidity From change of only if sending in case of change 2 5 10 25 50 Send periodically all only if sending periodically 5 s 10 s 30 s 1 min 2 h Use min and max humidity values Values are not maintained after reset No Yes Humidity threshold value Use humidity threshold value 1 2 No YesJa ...

Страница 29: ...et per Communication object Humidity threshold value setpoint per Communication object The value communicated last shall be maintained not after restoration of voltage after restoration of voltage and programming Do not use for first commissioning Start humidity threshold value in rh valid until 1 communication only if the value communicated last is not maintained or after restoration of voltage 0...

Страница 30: ...Blocking Use block of the humidity switching output No Yes Evaluation of the humidity blocking object if value 1 block if value 0 release if value 0 block if value 1 release Value of the humidity blocking object before 1 communication 0 1 Behaviour of humidity switching output with blocking do not send telegram send 0 send 1 The behaviour with release of the switching output depends on the value o...

Страница 31: ...end 0 no selection Humidity PI control Use humidity control No Yes If the control is used General humidity control Type of control One stage dehumidifcation Two stage dehumidifcation Humidification and dehumidification Behaviour of the blocking object with value 1 block control 0 release control 0 block control 1 release control Value of the blocking object before 1 communication 0 1 Controller ta...

Страница 32: ... the target value is set per communication object Target value setpoint per Communication object The value communicated last shall be maintained not after restoration of voltage after restoration of voltage and programming Do not use for first commissioning Start target value in valid until 1 communication only if the value communicated last is not maintained or after restoration of voltage 0 100 ...

Страница 33: ...With release the actuating variable follows the control Dehumidification 2 stage Appears only if two stage dehumidification is used Target value difference between 1 and 2 stage in 0 1 C 0 50 Maximum actuating variable is reached at target actual difference of 1 50 Re setting time in mins 1 255 If blocked the actuating variable shall not be sent send a specific value Value in only if a specific va...

Страница 34: ...ctuating variable is reached at target actual difference of 1 50 Re setting time in mins 1 255 If blocked the actuating variable shall nicht gesendet werden einen bestimmten Wert senden Value in only if a specific value is sent 0 100 With release the actuating variable follows the control ...

Страница 35: ...nt temperature do not send send periodically send in case of change send in case of change and periodically From change of only if sending in case of change 2 5 10 25 50 Send periodically all only if sending periodically 5 s 10 s 30 s 1 min 2 h Use monitoring of the cooling medium temperature No Yes ...

Страница 36: ...of voltage and programming Do not use for first commissioning Offset in C only if the offset set last is not maintained or after restoration of voltage 0 20 Step size for offset change per communication object 0 1 C 0 2 C 0 3 C 0 4 C 0 5 C 1 C 2 C 3 C 4 C 5 C Hysteresis of the threshold value in 0 50 Threshold value do not send send periodically send in case of change send in case of change and pe...

Страница 37: ... 1 block if value 0 release if value 0 block if value 1 release Value of the humidity blocking object before 1 communication 0 1 Behaviour of switching output with blocking do not send telegram send 0 send 1 The behaviour with release of the switching output depends on the value of the parameter Switching output sends see Switching output Value of parameter Switching output sends Setting options B...

Страница 38: ...ute humidity is used Unit object 65 g water kg air Unit object 66 g water m 3 air Transmission behaviour do not send send periodically send in case of change send in case of change and periodically From change of only if sending in case of change 2 5 10 25 50 Send periodically all only if sending periodically 5 s 10 s 30 s 1 min 2 h ...

Страница 39: ... 1 and periodically on change to 0 and periodically Send periodically all only if sending periodically 5 s 10 s 30 s 1 min 2 h maximum temperature in C Standard 26 C 25 40 minimum temperature in C Standard 20 C 10 21 maximum relative humidity in Standard 65 52 90 minimum relative humidity in Standard 30 10 43 maximum absolute humidity in 0 1 g kg Standard 11 5 g kg 50 200 ...

Страница 40: ...eresis of temperature 1 C Hysteresis of relative humidity 2 RH Hysteresis of absolute humidity 2 g kg Logic Communication objects logic inputs do nor release release AND logic Logic 1 2 3 4 not active active OR logic Logic 1 2 3 4 not active active ...

Страница 41: ...t value 1 0 If logic 0 object value 0 1 Communication object AND logic 1 2 sends on change of logic on change of logic to 1 on change of logic to 0 on change of logic and periodically on change of logic to 1 and periodically on change of logic to 0 and periodically Send periodically all only if sending periodically 5 s 10 s 30 s 1 min 2 h If the logic output sends two 8 bit objects Logic output se...

Страница 42: ... object logic input 3 Communication object logic input 3 inverted Communication object logic input 4 Communication object logic input 4 inverted Communication object logic input 5 Communication object logic input 5 invertiert Communication object logic input 6 Communication object logic input 6 inverted Communication object logic input 7 Communication object logic input 7 inverted Communication ob...

Страница 43: ...alue 1 0 If logic 0 object value 0 1 Communication object OR Logic 1 2 sends on change of logic on change of logic to 1 on change of logic to 0 on change of logic and periodically on change of logic to 1 and periodically on change of logic to 0 and periodically Send periodically all only if sending periodically 5 s 10 s 30 s 1 min 2 h If the logic output sends two 8 bit objects Logic output sends ...

Страница 44: ...c to 0 and periodically Send periodically all only if sending periodically 5 s 10 s 30 s 1 min 2 h Linkage inputs of OR logic The linkage inputs of the OR logic correspond with the parameters of the AND logic The OR logic is additionally provided with the following inputs AND Logic output 1 AND Logic output 1 inverted AND Logic output 2 AND Logic output 2 inverted AND Logic output 3 AND Logic outp...

Страница 45: ...ze 2 line big font size Content line 1 2 Display nothing Internal temperature External temperature Total temperature Internal relative air humidity External relative air humidity Total relative air humidity Absolute humidity g kg Absolute humidity g m3 Dew point temperature Time Value of the 8 bit object ...

Страница 46: ...elative air humidity Absolute humidity g kg Absolute humidity g m3 Dew point temperature Date Time Value of the 8 bit object Value of the 16 bit object Text message 1 Text message 2 Content line 2 Display nothing Internal temperature External temperature Total temperature Internal relative air humidity External relative air humidity Total relative air humidity Absolute humidity g kg Absolute humid...

Страница 47: ... parts per million s seconds ms milliseconds V volts mV millivolts A amperes mA milliamperes W watts mW milliwatts W m2 watts per sqaremeter W h watts per hour ltr litres ltr h litres per hour m metre mm millimetres Display duration of the message only if a textmessage is dislayed Until new message is available Maximum 1 minute Maximum 2 minutes Maximum 5 minutes Maximum 10 minutes Maximum 20 minu...

Страница 48: ...Elsner Elektronik GmbH Steuerungs und Automatisierungstechnik Herdweg 7 D 75391 Gechingen Germany Phone 49 0 70 56 93 97 0 Fax 49 0 70 56 93 97 20 info elsner elektronik de http www elsner elektronik de ...