22
Parameter setting
Actuator KNX S1R-BA4-UP 24 V
• Version: 27.05.2020 • Technical changes and errors excepted.
Runtime zero position and step setting of slats:
(only for shutters)
Through the runtime in which the drive continues moving in the zero position (i.e. after
reaching the top end position), different curtain lengths or assembly positions of the
end position switch may be balanced. The shading of a facade is completely retracted
by adjusting the zero position runtimes, and thus provides a better overall image.
Step time x step number determines the turning time of the slats.
If the short time command for shutters (step command) is used only for slat
adjustment, but not for positioning the curtain, the following parameter is set to "Yes".
The parameter appears only for shutters.
Break time:
The required break times during a change of direction of the drive should be adjusted
according to the specifications of the motor manufacturer.
Reference movement:
With the regular movement to the two end positions, the runtime and zero position are
adjusted again. This is especially important for the automatic runtime determination.
Therefore, it can be set here after how many movements before a positioning
movement a reference movement will be performed. The reference movement is
always in the direction of the secure position (retracting when shading, closing
windows).
for movement with change of direction
in 10 ms
(only for manual input)
0 ... 600
for slat movement from all other
positions in 10 ms
(only for manual input)
0 ... 600
Runtime zero position in 0.1 sec
0 … 255
Step time in 10 ms
1 … 100; 20
Step number slats
1 … 255; 5
Allow step commands only for slat
adjustment
no • yes
Break time for a change of direction
in 0.1 sec
5 … 100; 10
Perform a reference movement
no • yes
Perform a reference movement
yes
for more than
movements before an auto positioning
movement
1 ... 255; 10