background image

Technical Manual   Cold Storage Controller EVP 3150-1 and EVP 3150-2

Page 16

 Installation / Start-Up

Upon  applying  voltage  to  the  controller,  after  a  few  seconds  the  display 

shows the parameter which is selected as permanent display or an actual 

error code.

 

Start-up sequence

•  Assign inputs/outputs to functions (see example on page 3)

•  Select type of used temperature sensors ("

P35

", Mode Page),  

 

  use TF 501 types for EEx-valves.

•   Correct the displayed temperature values if necessary 

  ("

P31

"-"

P34

", Mode Page).

•  Set date and time ("

P81

"-"

P87

", Mode Page)

•  Set defrost mode ("

d02

", Defrost Page)

•  Set fan mode  "

d01

" and "

P02

"

•  Set cooling mode "

P03

" (Mode Page) 

•  See page 9 for parameterization of the pressure transmitter inputs  

These are the most important steps for the basic configuration of the controller. 

Upon that, adapt the other parameters like temperature setpoint, hysteresis, 

delay times.... Refer to the previous chapters in this manual. 

Start-up in a data network

•  Set the address of the controller  ("

P90

", Mode Page)

•   Upload parameters from PC to controller

The EVP offers several status messages, which enables you to check the 

states of inputs and outputs:

•   "

L50

", value of the analogue output

•   "

L60

", state of the digital inputs DI1 and DI2

•   "

L61

", state of the relays

Sensor positions for EEx-Valve Control, 

Pressure Transmitter / Temperature Sensor Method

The pressure transmitter must be mounted at the suction pipe, at a position 

where no pressure decrease can affect the measuring. The best place is 

close to the evaporator. If there are several evaporators, select a position 

from where the distance to all evaporators is as short as possible.

Selection of Pressure Transmitter

To detect a pressure transmitter malfunction, the signal voltage input is 

scalable. So you can use e.g. transmitters with an 2...10V output which 

makes it easier to recognize a malfunction.

Number  of  controllers  working  with  the  same  pressure 

transmitter

The input resistance of the pressure transmitter input is 80 kOhm. Several 

inputs can be connected in parallel, but the resulting resistance must not 

fall below the minimum specifications of the used pressure transmitter. 

In practise, up to 10 controllers mostly work trouble-free.

Sensor positions for EEx-Valve control, 

Temperature Sensors Method

*

 = alternative positions for Outlet-Sensor

Please care for a good isolation 

by foamed material, so that none 

of the sensors get contact with 

the airflow.

Pipe mounting

Most expedient is it to use 

cable fixers

, some thermal conduction silico-

ne cares for a good thermal flow.

Metallic fixers with high mass are not qualified. 

 Sensor Positions

Sensor positions are not critical in stan-

dard applications. The 

control sensor

 

or 

alarm sensor

 has to be fixed behind 

the evaporator (air-inlet) or at a repre-

sentative place in the chamber, but not 

in the air outlet. 
The second sensor (

defrost term-inati-

on sensor, evaporator sensor

) should 

be  assembled  in  the  contact  pipe  or 

within the fins of the evaporator. A good 

thermal exchange to the fins is important. 

It should be placed at the position where 

the ice remains the longest time while 

a defrost cycle.

Sensors  for  intelligent  (adaptive) 

defrost

To detect icing the EVP doesn't need 

additional sensors. The control sensor 

and the defrost (evap.) sensor are suf-

ficient. Please note that the emergency 

defrost mode is not able to prevent ice-

clusters or slow glacieration in case of a 

incorrect sensor position. If ice-clusters 

appear,  the  defrost  sensor  must  be 

placed at this position.

After  start-up,  Please  check  the  position  of  the 

evaporator sensors accurately!!

This manual, which is part of the product, has been set up with care and our best knowledge, but mistakes are still possible. Technical details 

can be changed without notice, especially the software. Please note that the described functions are only valid for units containing the software 

with the version-number shown on page 1 of this manual. Units with an other version number may work a little bit different. 

evap sensor

control sensor

airflow

fins

contact-

pipe

*

*

*

pipe

distributor

EEx-valve

outlet

sensor

inlet

sensor

foam Isolation

sensor

thermal

conduction 

silicone

liquid

gaseous

refrigerant in evaporator pipe

For more infor-

mation about 

Electronic Ex-

pansion Valves 

see page 9 !

set up:  26.6.17, tkd/jr 

checked:  26.6.17, ek/jk  approved: 26.6.17, mv/sha  

transl.(E): ......................  transl()................  corr. 

Содержание EVP 3150-1

Страница 1: ...ming Enter access code if necessary Change value If you hold the key the values change faster and faster P Confirm programming P 2 sec Page name will be displayed again If an older version must be replaced please note the modified terminals Technical Manual 5311092 00 26E Cold Storage Controller from SoftVers 1 61 Types EVP 3150 1 EVP 3150 2 ELEKTRONISCHE REGELUNGEN GMBH Please note safety instruc...

Страница 2: ...personal injury or damage to property caused by inadequate handling or non observance of the safety instructions The guarantee will lapse in such cases This manual contains additional safety instructions in the functional description Please note them If you notice any damage the product may not be connected to mains voltage Danger of Life A riskless operation is impossible if The device has visibl...

Страница 3: ...01 is the 1st parameter on the page and determines the function of relay 1 displaying the function of relay 1 P any new assignment of relay 1 P C00 Code expected only if no key key is hit for about 3 minutes enter access code C88 confirm P any select function ALA ALA alarm relay confirm P h01 parameter will be displayed again select new in output h02 determines the function of relay 2 displaying t...

Страница 4: ...s 02 0 48 0 h min 24 0 h d11 Defrost release time 1 in 10 minutes steps 00 0 23 5 off 05 0 d12 Defrost release time 2 in 10 minutes steps 00 0 23 5 off off d13 Defrost release time 3 in 10 minutes steps 00 0 23 5 off off d14 Defrost release time 4 in 10 minutes steps 00 0 23 5 off off d15 Defrost release time 5 in 10 minutes steps 00 0 23 5 off off d16 Defrost release time 6 in 10 minutes steps 00...

Страница 5: ...ve Control 1 999 sec 240 sec P65 Superheat maximum value 2 0 100 0K 8 0K P66 Limitation of EEx valve signal 0 100 100 P67 Actuating Variable Delay EEx valve step size 1 100 100 P68 Actuating Variable Delay EEx valve output delay 0 240 sec 0 P79 X Software version P81 Standard of summer winter switch oFF on EU since 96 on P82 P83 Year Month P84 P85 Day Hour P86 P87 Minute Second P90 Address of the ...

Страница 6: ...y digital input or via interface LED on defrost increase values decrease values this setpoint is active Connection EVP 3150 1 Older product production discontinued DI 1 relay K2 10 29 analog out EVP 3150 1 24V supply L DI 2 mains 2 1 N 3 L 4 N 7 6 5 8 9 relay K1 24 21 20 22 23 NDO DO RS 485 26 25 28 27 sensor 3 sensor 4 sensor 1 sensor 2 0 10V IN 15 SSR K4 230V AC 11 12 14 13 relay K3 18 L 230V AC...

Страница 7: ...eshold for the low temperature limitation function Low temperature alarm can be disabled by P41 Mode Page Supplementary alarm delay during defrost Afteradefrostcyclethetemperaturemaytakelonger to stabilize and the normal alarm delay turns out to be too short For this reason the value of parameter d33 defrost page will be added on to the normal alarm delay after defrosting cooling relay normal cool...

Страница 8: ...ller OFF If a digital input is assigned to the functions oFL or oFH and is activated by the matching signal then all control functions will be disabled All alarm functions are locked and the display shows oFF Safety Chain Monitoring When using the controller for single compressor appli ca tions one of the digital inputs can be used to monitor the safety chain chA Normally the digital input is conn...

Страница 9: ...he superheat value is determined by P60 only Function is disabled P65 Superheat maximum value exceeds P60 Function enabled P65 is below or equal to P60 Temperature control with Electronic Expansion Valves Sensor Positions Pressure Transmitter Temperatur Sensor method 2 Temperature Sensors method Parameterization Thefollowingrecommendationsrefertothepressure transmitter DG 1 9 2 10V L05 Display of ...

Страница 10: ...tion where by experience iceremainsthelongesttime Ifthetemperaturerises at that position the ice in the evaporator is probably melted completely Adefrost cycle is completed as soon as the defrost sensor has reached the defrost limitation tempera ture d31 Defrost Page If 2 defrost sensors are assigned both sensors must achieve the limitation temperature to termi nate defrost Defrost termination by ...

Страница 11: ...influence If you want to prevent that defrost starts at certain day times use all the defrost release times and set them to points in time where defrost is allowed If no icing is detected these times will be ignored On the other hand once icing detected the controller will wait for the next defrost release time before starting a defrost cycle External command Assign one of the digital inputs to de...

Страница 12: ...al input OK DI1 is configured at h61 to the value AnA r63 is set to 50 If the analogue output works as voltage output it delivers 5V DC If it works as current output it delivers 12 mA Electronic Expansion Valves with analogue input The analogue output is able to control expansion valves with analog input Therefore h52 must be set to EEP Also in this case h51 serves as a switch for a voltage or cur...

Страница 13: ...o 0 2 fan interval mode defrost by fan A relay is reserved for fan control P02 is set to Int d01 is set to on 3 fan interval mode defrost by electric heater hot gaz A relay is reserved for fan control P02 is set to Int d01 is set to oFF The fan runs while cooling is on will be disabled during defrost periods and comes on after defrost with a time delay set by parameter r22 4 fan in permanent mode ...

Страница 14: ...fthe ambient air market temperature The information about current market temperature and humidity the controller gets from a superior system VPR 5240 can also be disabled ther to calculate the absolute humidty Ifoneoftherelaysisassignedto FrA thiswillcontrol theframeheaterenergywithacertainfrequencyand pulse width For day and night operation you can choose different values to save energy The corre...

Страница 15: ...ry for selecting the right controller when a data package is transmitted on the network bus If the controller is used outside a network these parameters are of no importance Remote control at Frontend Systems EVP controllers can be operated remotely via interface when they are connected to Frontend Systems such as SMZ or VPR Inthiscase theFrontendSystemshowstheEVP s display contents and the keys o...

Страница 16: ...the minimum specifications of the used pressure transmitter In practise up to 10 controllers mostly work trouble free Sensor positions for EEx Valve control Temperature Sensors Method alternative positions for Outlet Sensor Please care for a good isolation by foamed material so that none of the sensors get contact with the airflow Pipe mounting Most expedient is it to use cable fixers some thermal...

Отзывы: