background image

Technical Manual   Cold Storage Controller EVP 3150-1 and EVP 3150-2

Page  11

  Intelligent Defrost (adaptive defrost) for Walk-In Coolers

Main Characteristics

This defrost control method, developed in co-

operation with the ‘

GÜNTNER

’ company, fits 

especially for 

cold stores

 and freezers which 

are closed (like walk-ins).

It is 

less efficient

 in applications where 

the  limitation  sensor  is  located  in  the 

airflow (e.g. open chest freezers).

This  technique 

reduces  significantly  the 

amount  of  energy 

the  refrigeration  plant 

needs.

Especially while 

difficult situations

 (like high 

air-humidity, in cool-down chambers, while long 

opening times of the door of the cold storage 

room,  uneven  feeding  of  the  cold  storage 

room, etc.) the adaptive method protects the 

evaporator from glaciation safely.

Dynamic ‘room-feeding’ situations engage 

the  controller  to  adapt  itself  to  the  new 

situation,  without  expensive  adjustment 

by technical personnel.
Specialized sensors or additional probes 

are not required.

Parameterization is very easy:

  set parameter "

d02

" to value "

AdA

"    

  (adaptive)

  set parameter "

d05

" (Defrost Page)    

  to a value which is 2 or 3 times the  

 

  normal defrost interval.

  Within this period the algorithm  

 

  decides  independly about the point    

  in time to defrost. After the end of this    

  period defrost starts in all cases.

  parameter "

d04

" (Defrost Page)  

 

  shows the time up to the next defrost.

●  parameters "

d34

  and  

  "

d31

" define the range the heater will    

  be pulsed within.

 Process Sequence

1

.  If [se hysteresis > 2,5°C] the    

 

controller uses the fan to reduce icing. 

2

.  In the time period set by „

d05

“ the controller  

 

decides itself if and at which moment a   

 

defrost cycle is necessary. If icing is    

 

detected, the controller prepares defrost  

 

and begins either immediately or at the 

 

next allowed defrost time.

3.

   Cooling stops, the fan goes on turning a  

 

certain time

4.

   The fan stops and the defrost heater starts

5.

  If several evaporators are installed,  

 

 

each one has its own defrost sensor and  

 

heater relay, so it is individually heated.

6.

  After achieving a defined evaporator    

 

temperature, the heater will be cut on/   

 

off in calculated periods. The period lenghts  

 

depend on evaporator temperature.

7.

  Defrost heater cut off, limit temp. is reached.

8.

  Cooling and fan remain still off (drain time).

9.

  After the end of „

d35

“ cooling starts, but the  

 

fan remains still off. 

10.

 After end of „

r22

“ the fan starts and normal  

 

refrigeration goes on.

Refrigeration

Even during normal operation the fan stays on after 

cut-off of cooling to reduce icing.

Recognition of icing

The more ice on the fins the more increases the 

difference of temperature between the roomsensor 

and evaporator sensor. The controller uses the value 

of these sensors, their difference, the historic curves 

of these values as well as curves and duration of 

the  past  defrostings  to  calculate  the  necessity  of 

defrosting.

Use of latent energy by airflow

We recommend to use "

d03

" (defrost forerun,  defrost 

page) to switch on the fan several minutes ahead 

the defrost cycle, while cooling stops and the heater 

is not yet on. 

Additionally, the fan is switched on automatically at a 

certain difference between the sensors. By this, the 

„cooling-energy“ is brought out of the evaporator and 

stored in the chamber. This helps also to reduce the 

amount of heat energy necessary to defrost.

Defrost start

If all six parameters release times are set to Off, the 

controller decides itself when it starts defrost.

 

Further time influence

   If you want to prevent that defrost starts at  

  certain day-times use all the defrost release  

  times and set them to points in time where  

  defrost is allowed. If no icing is detected,   

  these times will be ignored. 

  On the other hand, once icing detected, the  

  controller will wait for the next defrost release  

  time before starting a defrost cycle.

 

External command

  Assign one of the digital inputs to "

deF

". By  

  applying voltage to that input it is possible to  

  start defrosting at every moment.

Defrost heating

When „

d34

“ is achieved, the heater will be cut off. 

The  heat  energy  of  the  resistances  will  dissipate 

slowly and melt the ice. The length of the cut-off is 

calculated by the controller and as soon as some 

criteria are fulfilled, it will switch on the heater again. 

The heater will be pulsed until the temperature of 

the evaporator sensor reaches the defrost limitation 

temperature "

d31

". 

This procedure fits in the same way for the case of 

several evaporators in the chamber.

By this way defrost period will take longer, but 

will be more efficient.

Several evaporators in one chamber

For  certain  plants  it  is  necessary  to  use  several 

evaporators in one chamber. The controller is able 

to control up to 3 evaporators in one chamber. Even 

in this case one unique room sensor is sufficient. 

E.g.  for  a  chamber  with  3  evaporators  you  need 

only 4 sensors:

●  one controlsensor

●  three defrost sensors (one for each evaporator)

If a defrost cycle is necessary, all evaporators will start 

defrost at the same time to avoid short circuit of air, 

when one is heating and the fan of another is turning. 

The one with the highest rate of icing determines the 

start of the defrost cycle. The EVP controller units are 

capable to 

determine just this evaporator 

and 

even to adapt it when conditions change.  

Thus always the evaporator with the most ice 

initiates defrost start, nevertheless the quantity of 

energy which is necessary to defrost will be calculated 

for each evaporator separately. 

To  finish  defrost  cycle  all  evaporators  must  have 

reached the defrost limitation temperature.

Emergency Operation Mode

In cases the controller recognizes that it would be 

incapable or to slow to control the process, or when 

it gets not enough information, e.g.:

●  charge of unusual very humid goods

●  freezer door was open a very long time

●  the evaporator is sprinkled with water

●  sensor broken or shortened

●  defrost terminated by the max. defrost time

the emergency operation starts.

To detect malfunction of the defrost control the unit 

uses the increasing of "

d05

".

If  a  defrost  cycle  is  terminated  by  this  time,  the 

controller starts several defrost events with the in-

terval corresponding to (¼) one quarter of the time 

programmed by "

d05

".

Therefore  be  careful  in  choosing  the  time  for 

this parameter.

After the end of the disturbance the controller works 

on normally.

Example

 

  Max time to defrost is set to 24 hours. If defrost  

  is not terminated by the evaporator sensor,  

  the controller will start defrost cycle every 

  24 / 4 = 6 hours until a cycle will be finished by  

  the evaporator sensor and not by timer.

  Independent from this procedure, a failure  

  message will be initiated.

End of defrost

When the defrost sensor has reached the defrost 

limitation temperature "

d31

", the heater stops and 

the controller waits until "

d35

" has expired, to allow 

the melted water drop to the drainage. 

While the following 'drain-on' time ("

r22

", Setpoint 

Page) cooling starts, but the fan still stay OFF to 

prevent that the fans blow warm and humid air or 

water drops into the chamber. 

Further information about possibilities to use 

latency heat you can find under "Evaporator 

Fan Control"

Содержание EVP 3150-1

Страница 1: ...ming Enter access code if necessary Change value If you hold the key the values change faster and faster P Confirm programming P 2 sec Page name will be displayed again If an older version must be replaced please note the modified terminals Technical Manual 5311092 00 26E Cold Storage Controller from SoftVers 1 61 Types EVP 3150 1 EVP 3150 2 ELEKTRONISCHE REGELUNGEN GMBH Please note safety instruc...

Страница 2: ...personal injury or damage to property caused by inadequate handling or non observance of the safety instructions The guarantee will lapse in such cases This manual contains additional safety instructions in the functional description Please note them If you notice any damage the product may not be connected to mains voltage Danger of Life A riskless operation is impossible if The device has visibl...

Страница 3: ...01 is the 1st parameter on the page and determines the function of relay 1 displaying the function of relay 1 P any new assignment of relay 1 P C00 Code expected only if no key key is hit for about 3 minutes enter access code C88 confirm P any select function ALA ALA alarm relay confirm P h01 parameter will be displayed again select new in output h02 determines the function of relay 2 displaying t...

Страница 4: ...s 02 0 48 0 h min 24 0 h d11 Defrost release time 1 in 10 minutes steps 00 0 23 5 off 05 0 d12 Defrost release time 2 in 10 minutes steps 00 0 23 5 off off d13 Defrost release time 3 in 10 minutes steps 00 0 23 5 off off d14 Defrost release time 4 in 10 minutes steps 00 0 23 5 off off d15 Defrost release time 5 in 10 minutes steps 00 0 23 5 off off d16 Defrost release time 6 in 10 minutes steps 00...

Страница 5: ...ve Control 1 999 sec 240 sec P65 Superheat maximum value 2 0 100 0K 8 0K P66 Limitation of EEx valve signal 0 100 100 P67 Actuating Variable Delay EEx valve step size 1 100 100 P68 Actuating Variable Delay EEx valve output delay 0 240 sec 0 P79 X Software version P81 Standard of summer winter switch oFF on EU since 96 on P82 P83 Year Month P84 P85 Day Hour P86 P87 Minute Second P90 Address of the ...

Страница 6: ...y digital input or via interface LED on defrost increase values decrease values this setpoint is active Connection EVP 3150 1 Older product production discontinued DI 1 relay K2 10 29 analog out EVP 3150 1 24V supply L DI 2 mains 2 1 N 3 L 4 N 7 6 5 8 9 relay K1 24 21 20 22 23 NDO DO RS 485 26 25 28 27 sensor 3 sensor 4 sensor 1 sensor 2 0 10V IN 15 SSR K4 230V AC 11 12 14 13 relay K3 18 L 230V AC...

Страница 7: ...eshold for the low temperature limitation function Low temperature alarm can be disabled by P41 Mode Page Supplementary alarm delay during defrost Afteradefrostcyclethetemperaturemaytakelonger to stabilize and the normal alarm delay turns out to be too short For this reason the value of parameter d33 defrost page will be added on to the normal alarm delay after defrosting cooling relay normal cool...

Страница 8: ...ller OFF If a digital input is assigned to the functions oFL or oFH and is activated by the matching signal then all control functions will be disabled All alarm functions are locked and the display shows oFF Safety Chain Monitoring When using the controller for single compressor appli ca tions one of the digital inputs can be used to monitor the safety chain chA Normally the digital input is conn...

Страница 9: ...he superheat value is determined by P60 only Function is disabled P65 Superheat maximum value exceeds P60 Function enabled P65 is below or equal to P60 Temperature control with Electronic Expansion Valves Sensor Positions Pressure Transmitter Temperatur Sensor method 2 Temperature Sensors method Parameterization Thefollowingrecommendationsrefertothepressure transmitter DG 1 9 2 10V L05 Display of ...

Страница 10: ...tion where by experience iceremainsthelongesttime Ifthetemperaturerises at that position the ice in the evaporator is probably melted completely Adefrost cycle is completed as soon as the defrost sensor has reached the defrost limitation tempera ture d31 Defrost Page If 2 defrost sensors are assigned both sensors must achieve the limitation temperature to termi nate defrost Defrost termination by ...

Страница 11: ...influence If you want to prevent that defrost starts at certain day times use all the defrost release times and set them to points in time where defrost is allowed If no icing is detected these times will be ignored On the other hand once icing detected the controller will wait for the next defrost release time before starting a defrost cycle External command Assign one of the digital inputs to de...

Страница 12: ...al input OK DI1 is configured at h61 to the value AnA r63 is set to 50 If the analogue output works as voltage output it delivers 5V DC If it works as current output it delivers 12 mA Electronic Expansion Valves with analogue input The analogue output is able to control expansion valves with analog input Therefore h52 must be set to EEP Also in this case h51 serves as a switch for a voltage or cur...

Страница 13: ...o 0 2 fan interval mode defrost by fan A relay is reserved for fan control P02 is set to Int d01 is set to on 3 fan interval mode defrost by electric heater hot gaz A relay is reserved for fan control P02 is set to Int d01 is set to oFF The fan runs while cooling is on will be disabled during defrost periods and comes on after defrost with a time delay set by parameter r22 4 fan in permanent mode ...

Страница 14: ...fthe ambient air market temperature The information about current market temperature and humidity the controller gets from a superior system VPR 5240 can also be disabled ther to calculate the absolute humidty Ifoneoftherelaysisassignedto FrA thiswillcontrol theframeheaterenergywithacertainfrequencyand pulse width For day and night operation you can choose different values to save energy The corre...

Страница 15: ...ry for selecting the right controller when a data package is transmitted on the network bus If the controller is used outside a network these parameters are of no importance Remote control at Frontend Systems EVP controllers can be operated remotely via interface when they are connected to Frontend Systems such as SMZ or VPR Inthiscase theFrontendSystemshowstheEVP s display contents and the keys o...

Страница 16: ...the minimum specifications of the used pressure transmitter In practise up to 10 controllers mostly work trouble free Sensor positions for EEx Valve control Temperature Sensors Method alternative positions for Outlet Sensor Please care for a good isolation by foamed material so that none of the sensors get contact with the airflow Pipe mounting Most expedient is it to use cable fixers some thermal...

Отзывы: