Technical Manual   Cold Storage Controller EVP 3150-1 and EVP 3150-2

Page 12

 Analogue Output

The analogue output can be used for regulation 

purposes or to provide a remote display with an 

actual value image. The signal is available as a 

DC-Voltage or a DC-Current-Signal, fixed by "

h51

(Assignment Page). 

Parameter "

L50

" (Actual Values Page) shows the 

current output signal as a %-part of the selected 

range,  "

h52

"  (Assignment  Page)  determines  the 

behaviour of the output:

Test functions

"h52" = "0"

  

output signal is 0V resp. 

   

4 mA (fixed)

"h52" = "100 

output  signal is 10V resp.  

   

20mA (fixed)

Transmission of actual values to remote displays 

or similar

This function allows the analogue outputs to deliver 

a mirror of measured actual value. 

Normally  a  control  probe  will  be  used.  If  multiple 

probes are configured, the warmest actual value will 

be used. If a virtual probe is configured, this probe is 

used in the same way as a real probe.

"h52" = "dIS" 

The output provides an image  

   

of the value of cooling sensor 1. 

   

U-output: 

-50°C = 0V,  

   

   

+100°C = 10V

   

I-output: 

-50°C = 4mA,  

   

   

+100°C = 20mA

Control with the analog output signal (PID-control)

"h52" = "P" 

PID-controller, whose output  

   

signal represents an addition of  

   

the components P, I, D and T1.

"h52" = "Pr" 

PID-controller like above, but  

   

with inverted output (rising  

   

temperature = falling signal). 

To adapt the controller to the process use the fol-

lowing parameters:
"

r51

" = 

PID proportional band,    

   

located symmetrically    

   

around setpoint 1

"

r52

" = 

PID-integral time (I-part)

"

r53

" =

 

PID-derivative time (D-part)

"

r54

" =

 

PID-actuator response    

   

time (T1-part)

How to influence the analog output manually
For certain applications it may be useful to affect 

the output signal manually. Any digital input can be 

assigned to a function "

AnA

". Once activated, the 

analogue output delivers a predefined voltage- or 

current signal, e.g. to drive a valve to a specific 

position.

"

h61

" or "

h62

" set to "

AnA

" (Assignment Page) 

  = configure digital input 1 or 2 

"

r63

" (Setpoint Page) 

  = amount of the output in % of the selected  

    range, if the digital input is activated.

Example

:

Digital input OK/DI1 is configured at "

h61

" to the 

value "

AnA

", "

r63

" is set to "50".

If  the  analogue  output  works  as  voltage  output, 

it delivers 5V DC. If it works as current output, it 

delivers 12 mA. 

   

Electronic Expansion Valves  

   

with analogue input

The  analogue  output  is  able  to  control 

expansion  valves  with  analog  input. 

Therefore,  "

h52

"  must  be  set  to  "

EEP

".  

Also in this case, "

h51

" serves as a switch 

for a voltage- or current output.

PI-control, D and T1-parts de-activated

PID-control, T1-part de-activated

Control Characteristic

 Actuating Variable Delay for PID

For using control processes with large reaction 

times the controller offers an 'Actuating Variable 

Delay'.

1. Analogue Output

If the controller sends a signal which initiates the 

analogue output to rise or to fall, then an adjustable 

delay time (

r56

, Setpoint Page) starts. Within this 

time period, the output signal is able to alter only 

by a specific %-part (step size, 

r57

). 

If "

r57

" is set to "100%" and "

r56

" to "0", then the 

function is disabled.

2. Relay Output

In  applications  with  motorized  actuators,  the 

Actuating Variable Delay takes effect by clocking 

the cooling resp. heating relays. If the controller 

sends a signal to initiate a relay permanently ON, 

an adjustable time period "

r58

" (Setpoint Page, 

Cooling/Heating Relay Time Period) starts. Within 

this period, the relay is engaged for the time set 

by "

r59

" (Setpoint page, Cooling/Heating Relay 

ON-Time). 

If "

r59

" is equal to "

r58

" or exceeds it, then the 

function is disabled, the relay switch as normal 

again.

Reaching the The OFF-value 

The  OFF-value  (0%)  will  be  initiated  immediately 

with:

-  defrost initiation

-  solenoid valve lock 

-  safety chain error

-   controller OFF

-  cooling OFF with an open door

Important !!

Please note the decreased lifetime of 

the relay contacts in cycling operati-

on. Please care for a suitable relief.

Cycle 40 sec.: 

load current 0,8A res. --> 5 years

load current 1,2A res. --> 2,5 year

load current 1,9A res. --> 15 months
(Theoretical values according to the

relays data sheet)

r58 (s)

r59 (s)

ON

OFF

relay off

relay on

t

t

PID

integral time

I-part

P-part

5V resp. 12mA

max.

min.

proportional band

output

setpoint deviation

t

t

PID

integral time

I-part

P-part

5V resp. 12mA

max.

min.

proportional band

output

setpoint deviation

PID attack time

Содержание EVP 3150-1

Страница 1: ...ming Enter access code if necessary Change value If you hold the key the values change faster and faster P Confirm programming P 2 sec Page name will be displayed again If an older version must be replaced please note the modified terminals Technical Manual 5311092 00 26E Cold Storage Controller from SoftVers 1 61 Types EVP 3150 1 EVP 3150 2 ELEKTRONISCHE REGELUNGEN GMBH Please note safety instruc...

Страница 2: ...personal injury or damage to property caused by inadequate handling or non observance of the safety instructions The guarantee will lapse in such cases This manual contains additional safety instructions in the functional description Please note them If you notice any damage the product may not be connected to mains voltage Danger of Life A riskless operation is impossible if The device has visibl...

Страница 3: ...01 is the 1st parameter on the page and determines the function of relay 1 displaying the function of relay 1 P any new assignment of relay 1 P C00 Code expected only if no key key is hit for about 3 minutes enter access code C88 confirm P any select function ALA ALA alarm relay confirm P h01 parameter will be displayed again select new in output h02 determines the function of relay 2 displaying t...

Страница 4: ...s 02 0 48 0 h min 24 0 h d11 Defrost release time 1 in 10 minutes steps 00 0 23 5 off 05 0 d12 Defrost release time 2 in 10 minutes steps 00 0 23 5 off off d13 Defrost release time 3 in 10 minutes steps 00 0 23 5 off off d14 Defrost release time 4 in 10 minutes steps 00 0 23 5 off off d15 Defrost release time 5 in 10 minutes steps 00 0 23 5 off off d16 Defrost release time 6 in 10 minutes steps 00...

Страница 5: ...ve Control 1 999 sec 240 sec P65 Superheat maximum value 2 0 100 0K 8 0K P66 Limitation of EEx valve signal 0 100 100 P67 Actuating Variable Delay EEx valve step size 1 100 100 P68 Actuating Variable Delay EEx valve output delay 0 240 sec 0 P79 X Software version P81 Standard of summer winter switch oFF on EU since 96 on P82 P83 Year Month P84 P85 Day Hour P86 P87 Minute Second P90 Address of the ...

Страница 6: ...y digital input or via interface LED on defrost increase values decrease values this setpoint is active Connection EVP 3150 1 Older product production discontinued DI 1 relay K2 10 29 analog out EVP 3150 1 24V supply L DI 2 mains 2 1 N 3 L 4 N 7 6 5 8 9 relay K1 24 21 20 22 23 NDO DO RS 485 26 25 28 27 sensor 3 sensor 4 sensor 1 sensor 2 0 10V IN 15 SSR K4 230V AC 11 12 14 13 relay K3 18 L 230V AC...

Страница 7: ...eshold for the low temperature limitation function Low temperature alarm can be disabled by P41 Mode Page Supplementary alarm delay during defrost Afteradefrostcyclethetemperaturemaytakelonger to stabilize and the normal alarm delay turns out to be too short For this reason the value of parameter d33 defrost page will be added on to the normal alarm delay after defrosting cooling relay normal cool...

Страница 8: ...ller OFF If a digital input is assigned to the functions oFL or oFH and is activated by the matching signal then all control functions will be disabled All alarm functions are locked and the display shows oFF Safety Chain Monitoring When using the controller for single compressor appli ca tions one of the digital inputs can be used to monitor the safety chain chA Normally the digital input is conn...

Страница 9: ...he superheat value is determined by P60 only Function is disabled P65 Superheat maximum value exceeds P60 Function enabled P65 is below or equal to P60 Temperature control with Electronic Expansion Valves Sensor Positions Pressure Transmitter Temperatur Sensor method 2 Temperature Sensors method Parameterization Thefollowingrecommendationsrefertothepressure transmitter DG 1 9 2 10V L05 Display of ...

Страница 10: ...tion where by experience iceremainsthelongesttime Ifthetemperaturerises at that position the ice in the evaporator is probably melted completely Adefrost cycle is completed as soon as the defrost sensor has reached the defrost limitation tempera ture d31 Defrost Page If 2 defrost sensors are assigned both sensors must achieve the limitation temperature to termi nate defrost Defrost termination by ...

Страница 11: ...influence If you want to prevent that defrost starts at certain day times use all the defrost release times and set them to points in time where defrost is allowed If no icing is detected these times will be ignored On the other hand once icing detected the controller will wait for the next defrost release time before starting a defrost cycle External command Assign one of the digital inputs to de...

Страница 12: ...al input OK DI1 is configured at h61 to the value AnA r63 is set to 50 If the analogue output works as voltage output it delivers 5V DC If it works as current output it delivers 12 mA Electronic Expansion Valves with analogue input The analogue output is able to control expansion valves with analog input Therefore h52 must be set to EEP Also in this case h51 serves as a switch for a voltage or cur...

Страница 13: ...o 0 2 fan interval mode defrost by fan A relay is reserved for fan control P02 is set to Int d01 is set to on 3 fan interval mode defrost by electric heater hot gaz A relay is reserved for fan control P02 is set to Int d01 is set to oFF The fan runs while cooling is on will be disabled during defrost periods and comes on after defrost with a time delay set by parameter r22 4 fan in permanent mode ...

Страница 14: ...fthe ambient air market temperature The information about current market temperature and humidity the controller gets from a superior system VPR 5240 can also be disabled ther to calculate the absolute humidty Ifoneoftherelaysisassignedto FrA thiswillcontrol theframeheaterenergywithacertainfrequencyand pulse width For day and night operation you can choose different values to save energy The corre...

Страница 15: ...ry for selecting the right controller when a data package is transmitted on the network bus If the controller is used outside a network these parameters are of no importance Remote control at Frontend Systems EVP controllers can be operated remotely via interface when they are connected to Frontend Systems such as SMZ or VPR Inthiscase theFrontendSystemshowstheEVP s display contents and the keys o...

Страница 16: ...the minimum specifications of the used pressure transmitter In practise up to 10 controllers mostly work trouble free Sensor positions for EEx Valve control Temperature Sensors Method alternative positions for Outlet Sensor Please care for a good isolation by foamed material so that none of the sensors get contact with the airflow Pipe mounting Most expedient is it to use cable fixers some thermal...

Отзывы: