Technical Manual   Cold Storage Controller EVP 3150-1 and EVP 3150-2

Page 8

 Second setpoint

 (night operation)

A second setpoint can be defined by "

r03

" (Setpoint 

Page). This can be used for night operation or other 

energy savings. Switching between these setpoints 

can be made by internal clock or by digital input. The 

current used setpoint is marked by a lighted decimal 

point in the parameter display. On the 'Actual Values 

Page', parameter "

L43

" shows the current state.

Internal switching

The parameters „

P21

“ and „

P22

“ determine  

the 2nd setpoint period. If the internal timer is not 

used, set both times to "

oFF

". 

  External switching

  The digital inputs can be configured for 

  external switching, selectable as "

dnL

  (active low) or "

dnh

" (active high). After the  

  input has been activated, the 2nd setpoint is  

  active all time and the internal timer is disabled. 

  If you want to use external switching only, 

  please set „

P21

“ and „

P22

“ to "

oFF

".

 Second Set of Setpoints

The  controller  offers  two  complete  setpoint  sets 

including day/night setpoints and alarm limits.

Example Application:  By  an  external  switch  it  is 

possible to change a cold room from refrigeration 

to freezing for temporary storage of other products, 

without changing any parameters at the controller. 

Even here the currently used setpoint is marked by 

a lighted decimal point in the parameter display.

Toggling between the setpoint layers
1. internal:  by parameter „

r01

“ (Setpoint Page)

2. external:  assign function „

SEt

“ to a digital  

   

input. If connected to mains phase,  

   

the 2nd layer is in use.

 Light Control

One of the relays is able to control room lightings 

(function  "

LIt

").  In  this  case,  the  relay  switches 

together with the night settings. 

While  'day'-operation  the  light  relay  keeps  ener-

gized.

 Emergency Operation

If  all  control  sensors  fail,  the  unit  turns  to  an 

emergency mode automatically. The cooling relay 

cycles with a %-part (

P04

, Mode Page) of a 30 

minutes period.

 Digital Inputs

 (Optocoupler Inputs)

Switching OFF the controller unit

Sometimes it is necessary to switch off cold storages 

completely including the controller.

If the controller works in a network, the bus-master 

so detects a malfunction and generates an alarm. 

To prevent this, the unit must be switched OFF via 

digital input.

Controller OFF

If a digital input is assigned to the functions "

oFL

or "

oFH

" and is activated by the matching signal, 

then all control functions will be disabled. All alarm 

functions are locked and the display shows "

oFF

".

Safety Chain Monitoring

When using the controller for single compressor 

applications, one of the digital inputs can be used 

to monitor the safety chain ("

chA

"). 

Normally the digital input is connected to phase via 

this chain of contacts. If the chain opens, cooling 

and fan will switch off, a running defrost cycle will be 

terminated and a new defrost cycle is impossible. 

Parameter "

r46

" defines the response time on the 

missing signal voltage.

Door Contact Input

If a digital input with the function "

dor

" is connected 

to phase, the evap fan stops immediately. The control 

range of the EEx-Valve will be changed automatically 

to avoid a further evaporation. 

If the door is open 

> 3 minutes

, cooling will be 

stopped. All other functions continue working.

If the door is open 

> 5 minutes

, the unit generates the 

error message "

rdo

". After the timer "

r62

" (Setpoint 

Page) has been run down, cooling restarts and an 

alarm message will be forwarded.

Door open monitoring

Every time a door is opened, the controller adds 

the time to the total opening time of the present day 

"

L22

" (Actual Values Page). If the total opening time 

exceeds the value set by "

r32

" (Setpoint Page), an 

alarm will be generated. 

The alarm message will be forwarded at the point in 

time determined by "

P42

" (Mode Page) and will be 

cancelled automatically 1 hour later. "

L31

" shows 

the remaining time up to the alarm message.

External Alarm

The digital inputs are able to process external alarm 

messages. For this, the function "

ALA

" must be 

assigned (Assignment Page). 

While normal operation, the input is connected to 

mains phase. When the voltage drops down, a delay 

time starts ("

r61

", Setpoint Page). After this timer has 

been run down, an alarm will be forwarded.

Exception:

If no alarm sensor is assigned or if  

the temperature is above the alarm 

limit, cooling continues without inter-

ruption. The cooling keeps switched 

ON and the fan starts again, so the 

door opening is ignored. 

 Real Time Clock

The built-in real time clock has a buffer for max. 10 

days without mains voltage. Date and time can be 

set by "

P82

"..."

P87

" (Mode Page). 

An automatic summer / winter switch ("

P81

", Mode 

Page) considers the current EU-rules from 1996 (EU 
96), but can also be switched off. 

30 minutes

emergency ON

in %

ON

OFF

cooling OFF

cooling ON

Содержание EVP 3150-1

Страница 1: ...ming Enter access code if necessary Change value If you hold the key the values change faster and faster P Confirm programming P 2 sec Page name will be displayed again If an older version must be replaced please note the modified terminals Technical Manual 5311092 00 26E Cold Storage Controller from SoftVers 1 61 Types EVP 3150 1 EVP 3150 2 ELEKTRONISCHE REGELUNGEN GMBH Please note safety instruc...

Страница 2: ...personal injury or damage to property caused by inadequate handling or non observance of the safety instructions The guarantee will lapse in such cases This manual contains additional safety instructions in the functional description Please note them If you notice any damage the product may not be connected to mains voltage Danger of Life A riskless operation is impossible if The device has visibl...

Страница 3: ...01 is the 1st parameter on the page and determines the function of relay 1 displaying the function of relay 1 P any new assignment of relay 1 P C00 Code expected only if no key key is hit for about 3 minutes enter access code C88 confirm P any select function ALA ALA alarm relay confirm P h01 parameter will be displayed again select new in output h02 determines the function of relay 2 displaying t...

Страница 4: ...s 02 0 48 0 h min 24 0 h d11 Defrost release time 1 in 10 minutes steps 00 0 23 5 off 05 0 d12 Defrost release time 2 in 10 minutes steps 00 0 23 5 off off d13 Defrost release time 3 in 10 minutes steps 00 0 23 5 off off d14 Defrost release time 4 in 10 minutes steps 00 0 23 5 off off d15 Defrost release time 5 in 10 minutes steps 00 0 23 5 off off d16 Defrost release time 6 in 10 minutes steps 00...

Страница 5: ...ve Control 1 999 sec 240 sec P65 Superheat maximum value 2 0 100 0K 8 0K P66 Limitation of EEx valve signal 0 100 100 P67 Actuating Variable Delay EEx valve step size 1 100 100 P68 Actuating Variable Delay EEx valve output delay 0 240 sec 0 P79 X Software version P81 Standard of summer winter switch oFF on EU since 96 on P82 P83 Year Month P84 P85 Day Hour P86 P87 Minute Second P90 Address of the ...

Страница 6: ...y digital input or via interface LED on defrost increase values decrease values this setpoint is active Connection EVP 3150 1 Older product production discontinued DI 1 relay K2 10 29 analog out EVP 3150 1 24V supply L DI 2 mains 2 1 N 3 L 4 N 7 6 5 8 9 relay K1 24 21 20 22 23 NDO DO RS 485 26 25 28 27 sensor 3 sensor 4 sensor 1 sensor 2 0 10V IN 15 SSR K4 230V AC 11 12 14 13 relay K3 18 L 230V AC...

Страница 7: ...eshold for the low temperature limitation function Low temperature alarm can be disabled by P41 Mode Page Supplementary alarm delay during defrost Afteradefrostcyclethetemperaturemaytakelonger to stabilize and the normal alarm delay turns out to be too short For this reason the value of parameter d33 defrost page will be added on to the normal alarm delay after defrosting cooling relay normal cool...

Страница 8: ...ller OFF If a digital input is assigned to the functions oFL or oFH and is activated by the matching signal then all control functions will be disabled All alarm functions are locked and the display shows oFF Safety Chain Monitoring When using the controller for single compressor appli ca tions one of the digital inputs can be used to monitor the safety chain chA Normally the digital input is conn...

Страница 9: ...he superheat value is determined by P60 only Function is disabled P65 Superheat maximum value exceeds P60 Function enabled P65 is below or equal to P60 Temperature control with Electronic Expansion Valves Sensor Positions Pressure Transmitter Temperatur Sensor method 2 Temperature Sensors method Parameterization Thefollowingrecommendationsrefertothepressure transmitter DG 1 9 2 10V L05 Display of ...

Страница 10: ...tion where by experience iceremainsthelongesttime Ifthetemperaturerises at that position the ice in the evaporator is probably melted completely Adefrost cycle is completed as soon as the defrost sensor has reached the defrost limitation tempera ture d31 Defrost Page If 2 defrost sensors are assigned both sensors must achieve the limitation temperature to termi nate defrost Defrost termination by ...

Страница 11: ...influence If you want to prevent that defrost starts at certain day times use all the defrost release times and set them to points in time where defrost is allowed If no icing is detected these times will be ignored On the other hand once icing detected the controller will wait for the next defrost release time before starting a defrost cycle External command Assign one of the digital inputs to de...

Страница 12: ...al input OK DI1 is configured at h61 to the value AnA r63 is set to 50 If the analogue output works as voltage output it delivers 5V DC If it works as current output it delivers 12 mA Electronic Expansion Valves with analogue input The analogue output is able to control expansion valves with analog input Therefore h52 must be set to EEP Also in this case h51 serves as a switch for a voltage or cur...

Страница 13: ...o 0 2 fan interval mode defrost by fan A relay is reserved for fan control P02 is set to Int d01 is set to on 3 fan interval mode defrost by electric heater hot gaz A relay is reserved for fan control P02 is set to Int d01 is set to oFF The fan runs while cooling is on will be disabled during defrost periods and comes on after defrost with a time delay set by parameter r22 4 fan in permanent mode ...

Страница 14: ...fthe ambient air market temperature The information about current market temperature and humidity the controller gets from a superior system VPR 5240 can also be disabled ther to calculate the absolute humidty Ifoneoftherelaysisassignedto FrA thiswillcontrol theframeheaterenergywithacertainfrequencyand pulse width For day and night operation you can choose different values to save energy The corre...

Страница 15: ...ry for selecting the right controller when a data package is transmitted on the network bus If the controller is used outside a network these parameters are of no importance Remote control at Frontend Systems EVP controllers can be operated remotely via interface when they are connected to Frontend Systems such as SMZ or VPR Inthiscase theFrontendSystemshowstheEVP s display contents and the keys o...

Страница 16: ...the minimum specifications of the used pressure transmitter In practise up to 10 controllers mostly work trouble free Sensor positions for EEx Valve control Temperature Sensors Method alternative positions for Outlet Sensor Please care for a good isolation by foamed material so that none of the sensors get contact with the airflow Pipe mounting Most expedient is it to use cable fixers some thermal...

Отзывы: