background image

Art.-Nr./Art. No./Réf./N° art/N° art.: 9010017B01M

 

Version

1.0

Date: 

25.05.2016        

5/15

165ESK...

13.1 Accessories

Suitable components for sensor variants with M12 pigtail connector: 

M12 cable sets with plastic nut under item number K18G00.K.
An assembly wrench with preset torque is available under item number MS03

for ensuring an optimal connection between sensor and cable set.
For easy wiring in series connection of several safety sensors we recommend

our T-distributors:
- 350ATC6K serial
- 350ATD7K diagnostics / EDM
- 350ATD8K feed supply voltage
- 350AGA2K01 terminator
and connecting lines:
- K54G00.K male / female straight 4-pole
- K55G00.K male / female angled 4-pole
- K58G00.K male / female straight 8-pole
and cable sets:
- K14G00.K female straight 4-pole
- K18G00.K female straight 8-pole

14 Troubleshooting

If the errors described can not be resolved, the device must be replaced to

ensure the safety function.

15 Dismantling

Dismantle the safety sensor in a powered down state.

16 Disposal

Dispose of packaging and used parts according to the regulations of the coun-

try in which the device is installed.

17 Information about production date

Safety output faults
Flash code

Cause

Short  circuit  between  safety  outputs  to  ground  or  to

+24 V DC.
Wire breakage

Remedy

- Switch off supply voltage.
- Eliminate short/wire break at the output.
- Re-apply supply voltage.

Safety input faults
Flash code

Cause

Short  circuit  between  safety  inputs,  to  ground  or  to

+24 V DC.
Wire breakage.

Remedy

- Switch off supply voltage.
- Eliminate short/wire break at the output.
- Re-apply supply voltage.

Safety input faults
Flash code

Cause

- EDM automatic:

Error on connected safety relay.

- EDM manual:

Start pulse does not take place in the defined area.

- All variants: Wire breakage.

Remedy

- Switch off supply voltage.
- Check safety relay or set start pulse correctly, check

for broken wire.

- Re-apply supply voltage.

Error overvoltage or undervoltage
Flash code

Cause

The supply voltage has not been applied in the defined

region.

Remedy

- Switch off supply voltage.
- Ensure correct supply voltage and reconnect it.

Temperature outside the acceptable range
Flash code

Cause

The defined temperature range has been exceeded or

undershot.

Remedy

- Switch off supply voltage.
- Ensuring proper ambient temperature.
- Re-apply supply voltage.

Incorrect actuator
Flash code
Cause

Incorrect actuator in the detection range of the sensor.

Remedy

- Use correct actuator.

Internal device error
Flash code
Cause

Internal device error.

Remedy

- Switch off power supply and re-connect.

The date of manufacture can be seen on the safety sensor hous-

ing in the format "calendar week/year":
E.g. "37/14" = week 37/year 2014

Содержание eloProtect E 165ESK Series

Страница 1: ...25 05 2016 Translation of the original operating instructions eloProtect E Safety sensor series 165ESK ENG...

Страница 2: ...they differ from the operating instructions The operating instructions are to be made available to the person who is in stalling the safety sensor The operating instructions are to be kept in a legib...

Страница 3: ...70EFR eloFlex 471EFR eloProg 485EPB 485EPE08A02 485EPE08 4854EPE12 485EPE16 7 1 Coding variants The various versions of the safety sensors arise from the different encodings designated as type keys un...

Страница 4: ...sensor actuated safety inputs not set low level LED green flashes1 LED red off LED yellow off Diagnostic output 24 V DC Safety outputs 0 V Note Set safety inputs Actuator in the detection area sensor...

Страница 5: ...p to 300 s Depending on the inertia of the connected device control relay etc this can lead to short switching processes The inputs of a connected evaluation unit must be positive switching as the two...

Страница 6: ...or to 24 V DC Wire breakage Remedy Switch off supply voltage Eliminate short wire break at the output Re apply supply voltage Safety input faults Flash code Cause Short circuit between safety inputs...

Страница 7: ...ycles 3 Hz Utilization category DIN EN 60947 5 1 2014 04 DC 12 DC 13 Switching current per safety output max 400 mA Switching current diagnostic output max 50 mA Off state current Ir DIN EN 60947 5 2...

Страница 8: ...ut max 2 75 mA Power consumption at full load max 23 75 W Short circuit detection Short circuit recognition Technology RFID Possible actuator 165EBK001 Assured operating distance Sao DIN EN 60947 5 3...

Страница 9: ...25 70 C 60 C 45 C Storage temperature 25 70 C Cable temperature range moved 5 80 C Cable temperature range fixed installation 30 80 C Shock resistance DIN EN 60947 5 2 2014 01 30 g 11 ms Vibration vi...

Страница 10: ...n Free zone DIN EN 60947 5 2 2014 01 50 mm Minimum mounting distance 150 mm Flush mountable Dimensions 25 x 88 x 13 mm Installation any Mounting type Fitting with M4 screws recessed ISO 4762 2004 06 T...

Страница 11: ...ed high individual and unique types DIN EN ISO 14119 2014 03 165ESK00 1 165ESK00 3 165ESK00 2 Hardware fault tolerance HFT 1 Service life in years 20 1 Assumptions for the calculation according to IEC...

Страница 12: ...ns 165EBK 25 88 78 18 5 5 1 13 4 5 7 6 165ESK 9 5 18 5 25 4 5 7 6 88 78 5 1 13 LIYY 8x0 25mm 1000 35 150 25 5 For further information on actuators please contact elobau for appropriate dataheets contr...

Страница 13: ...165ESK Art Nr Art No R f N art 9010017B01M Version 1 0 Date 25 05 2016 12 15 Connection examples Stand Alone function Series connection 3 cascade...

Страница 14: ...Directive 2014 30 EC Bezeichnung und Beschreibung der Produktkomponenten des Sicherheitsbauteils Designation and description of the product components of the safety relevant component Sicherheitssens...

Страница 15: ...5 D 80339 M nchen Kennnummer 0123 Nummerierung der Bescheinigung Certification number M6A 16 01 20166 036 nderungsindex Modification Index D Leutkirch den 27 06 2016 Sandrina Fehrs CE Beauftragte EC a...

Отзывы: