background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200583_02C Jan 2021                        ©2019 ELMDENE INTERNATIONAL LTD  

 

Connections and Signalling outputs

 

Load / - 

Screw terminals Voltage output to load  

GEN PSU Fault  (normally 
closed contact) 

0.10 A @ 60V 

dc 16Ω solid state relay contact

s, volt free 

Open if Mains failed and battery voltage < 23 volts or fault PSU fault 
condition, (see below) 

EPS Fault  (normally closed 
contact) 

0.10 A @ 60V 

dc 16Ω solid state relay contacts, volt free

 

Open if loss of mains for > 10 seconds 

Temperature sensor 

Thermistor input from supplied battery terminal thermistor. 

BATT + / - 

Connection to back up battery using supplied battery lead 

Optional Serial interface  

5 pin header  (For details contact Elmdene Technical Support) 

 

S

IGNALLING AND 

D

IAGNOSTICS

 

 

 
Fault Outputs 

EPS Fault 

GEN Fault 

Condition 

Possible Cause 

Action 

C

LOSED

 

C

LOSED

 

Normal 

operation 

Mains present 
Battery healthy 

None 

O

PEN

 

C

LOSED

 

Standby 

Mode 

Mains lost 
Battery driving load 

Investigate loss of mains 

C

LOSED

 

O

PEN

 

Fault 

Present 

Blown fuses 
Battery fault 
 
Internal fault 

Investigate fault source 
using diagnostic LED 
Rectify fault where 
possible 

O

PEN

 

O

PEN

 

PSU 

Shutdown 

Mains lost 
Standby battery exhausted 

Restore mains as soon 
as possible 

 

LED Indication 

LED type

 

Function

 

Yellow LED  

Fault  Indicator (See ‘Fault Diagnostic table’ User and Engineer)

 

Green LED 

Mains supply On Indicator 

Orange LED 

Diagnostic  Indicator (Not visible through front panel) 

 
Fault Diagnostic table 

 Front panel - User 

Yellow LED 

Fault 

Green LED 

Mains 

Condition 

Possible Cause 

Action 

O

FF

 

O

N

 

Normal 

operation 

Mains present 
Battery healthy 

None 

F

LASH 

C

ONTINUOUS

 

O

or

 

O

FF

 

Fault 

Blown fuses 
Battery fault 
Internal fault 

Contact service 
engineer 

1

 

P

ULSE

/

S

 

O

FF

 

Standby Mode 

Mains lost 
Battery driving load 

Investigate loss of 
mains 

 

Содержание STX2401-C

Страница 1: ...elay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an optional plug in serial interface that can provide diagnostic and fault reporting...

Страница 2: ...ttery Capacity e g PowerSonic model Yuasa model 2 x 1 2 Ah 12 V PS12021 NP1 2 12 2 x 7 Ah 12 V PS12070 NP7 12 Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charg...

Страница 3: ...ault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fa...

Страница 4: ...systems If the PSE is used as a power supply for Control and Indicating Equipment CIE the PSE shall be installed no further than 10cm from the CIE and close coupled by conduit This unit must be fed f...

Страница 5: ...wall fixings are appropriate to support this weight 7 The product should be mounted no further than 10 cm from the control and indicating equipment close coupled by conduit if it is being used to pow...

Страница 6: ...ault LED flashes after approximately 3 s indicating a disconnected battery 3 Disconnect the mains power Load Output and Remote Signalling 4 Connect the EPS and PSU Fault outputs to the appropriate inp...

Страница 7: ...ull alarm condition Note ensure batteries have sufficient charge to support the system under full load Final 18 Reconnect the mains Verify that the green Mains LED illuminates and the yellow Fault LED...

Страница 8: ...of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries saf...

Отзывы: