To Load 

 

L    E    N 

   Mains 

 

Diagnostic LED 

Fault LED 

Mains ON LED 

Temperature Sensor 

connect 

 

C

OMMISSIONING

 

 

 

Mains Power Up 

1)

 

With no external connections made to the PSE, connect the mains input wires to the terminal block, 

ensuring that the mains isolator (disconnect device) is open

. Fasten wiring in place with cable tie to 

saddle. 

Note: Equipment must be earthed.

 

2)

 

Apply mains input. Confirm that all LED indicators flash on briefly proving integrity of indicating circuits. 
Ensure that the green Mains LED then stays illuminated and that the yellow Fault LED flashes after 
approximately 3 s (indicating a disconnected battery). 

3)

 

Disconnect the mains power. 
 

 

Load Output and Remote Signalling 

4)

 

Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault 
monitoring is required. 

5)

 

Connect the load (output) wiring as shown in Figure. 3. Cable tie to saddle provided (adjacent to exit hole).  

 
Figure 3 

 Connections 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 

6)

 

Re-apply mains. Verify that the green Mains LED illuminates and the yellow Fault LED flashes after 
approximately 3 s (disconnected battery). 

7)

 

If connected, verify that the EPS Fault monitor shows a 

closed

 contact and the GEN PSU Fault monitor 

shows an 

open

 contact. 

8)

 

Perform a full functional test of connected system (load) including full alarm condition

 

Figure 4 

 Terminal labels

 

 
 
 
 
 

 
 

 
 
 
 

   +    -  | +    -  |Temp| GEN    EPS  

   Load |  Batt |sense|     Fault       

BATT FUSE 

    1.6 Amp 

LOAD FUSE 

    1.6 Amp 

 

 

 + 

 

 

 

Содержание STX2401-C

Страница 1: ...elay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an optional plug in serial interface that can provide diagnostic and fault reporting...

Страница 2: ...ttery Capacity e g PowerSonic model Yuasa model 2 x 1 2 Ah 12 V PS12021 NP1 2 12 2 x 7 Ah 12 V PS12070 NP7 12 Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charg...

Страница 3: ...ault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fa...

Страница 4: ...systems If the PSE is used as a power supply for Control and Indicating Equipment CIE the PSE shall be installed no further than 10cm from the CIE and close coupled by conduit This unit must be fed f...

Страница 5: ...wall fixings are appropriate to support this weight 7 The product should be mounted no further than 10 cm from the control and indicating equipment close coupled by conduit if it is being used to pow...

Страница 6: ...ault LED flashes after approximately 3 s indicating a disconnected battery 3 Disconnect the mains power Load Output and Remote Signalling 4 Connect the EPS and PSU Fault outputs to the appropriate inp...

Страница 7: ...ull alarm condition Note ensure batteries have sufficient charge to support the system under full load Final 18 Reconnect the mains Verify that the green Mains LED illuminates and the yellow Fault LED...

Страница 8: ...of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries saf...

Отзывы: