6
Technical Support: +44(0)23 9269 6638 (option 3)
PAK200583_02C Jan 2021 ©2019 ELMDENE INTERNATIONAL LTD
+
+
–
To Load
L E N
Mains
Diagnostic LED
Fault LED
Mains ON LED
Temperature Sensor
connect
C
OMMISSIONING
Mains Power Up
1)
With no external connections made to the PSE, connect the mains input wires to the terminal block,
ensuring that the mains isolator (disconnect device) is open
. Fasten wiring in place with cable tie to
saddle.
Note: Equipment must be earthed.
2)
Apply mains input. Confirm that all LED indicators flash on briefly proving integrity of indicating circuits.
Ensure that the green Mains LED then stays illuminated and that the yellow Fault LED flashes after
approximately 3 s (indicating a disconnected battery).
3)
Disconnect the mains power.
Load Output and Remote Signalling
4)
Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault
monitoring is required.
5)
Connect the load (output) wiring as shown in Figure. 3. Cable tie to saddle provided (adjacent to exit hole).
Figure 3
–
Connections
6)
Re-apply mains. Verify that the green Mains LED illuminates and the yellow Fault LED flashes after
approximately 3 s (disconnected battery).
7)
If connected, verify that the EPS Fault monitor shows a
closed
contact and the GEN PSU Fault monitor
shows an
open
contact.
8)
Perform a full functional test of connected system (load) including full alarm condition
.
Figure 4
–
Terminal labels
+ - | + - |Temp| GEN EPS
Load | Batt |sense| Fault
BATT FUSE
1.6 Amp
LOAD FUSE
1.6 Amp
+
–
+
–