Mains Input 

Rated Voltage 
(Operational voltage) 

110 

 240 V ac  

(90 

 264 V ac) 

Frequency 

50 

  Hz 

Input current 

< 1.0 Amps at full load 

Inrush current 

5A Max at 25 °C 110 V ac for 10 ms 

Fuse 

T1.6 A 20mm, 250 V ac HRC 

 

Output 

Voltage at full load 

 

Mains power 

 

Battery standby 

 
 

27.0 

 28.3V dc  (range) (27.6V nominal) 

 

20.3 

 26.0V dc 

Ripple 

 

<100 mV pk 

 pk max @ Rated Voltage 

Fuse 
 

Load 

 

Battery 

 

F1.6 A 
F1.6 A 

Battery mode selected 

1.2 Ah (STX2401-T)

 

7 Ah (STX2401-C)

 

Continuous Output Current 

No charging (Imax B) 

With charging  (Imax A) 

 

1.5 A 
1.2 A 

 

1.5 A 
1.2 A 

Battery Capacity 
e.g. 

-

 

PowerSonic model 

-

 

Yuasa model 

2 x 1.2 Ah 12 V 

 

PS12021 

NP1.2-12 

2 x 7 Ah 12 V 

 

PS12070 

NP7-12 

Battery Charging 

Constant current bulk charging to 80% capacity within 24 hours 
Float charging to 100% within 48 hours 
Eco charging and check every 24 hours  

 (for up to  4 hours charge, level dependent on temperature) 

Constant current charge 

0.3 A 

0.3 A 

Low battery threshold voltage 

23 V 

Deep discharge protection 

Threshold voltage 

 21 V 

Quiescent current 

 no load 

< 30 mA @ 27.6 V 

Quiescent current 

 batt cut off 

< 1 mA @ 27.6 V 

 

 

Mechanical 

Product Reference 

STX2401-T 

STX2401-C 

Enclosure Dimensions 

 w x h x d (mm) 

300 x 240 x 60 

275 x 330 x 80 

Weight (kg)

 excluding battery 

2.4 Kg 

3.3 Kg 

Material  

1.2 mm steel white powder coated 

 

Environmental  

Temperature 

 Operating 

-10 to +40°C (operating) 75% RH non-condensing 

Temperature - Storage 

-20 to +80°C (storage) 

 

Содержание STX2401-C

Страница 1: ...elay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an optional plug in serial interface that can provide diagnostic and fault reporting...

Страница 2: ...ttery Capacity e g PowerSonic model Yuasa model 2 x 1 2 Ah 12 V PS12021 NP1 2 12 2 x 7 Ah 12 V PS12070 NP7 12 Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charg...

Страница 3: ...ault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fa...

Страница 4: ...systems If the PSE is used as a power supply for Control and Indicating Equipment CIE the PSE shall be installed no further than 10cm from the CIE and close coupled by conduit This unit must be fed f...

Страница 5: ...wall fixings are appropriate to support this weight 7 The product should be mounted no further than 10 cm from the control and indicating equipment close coupled by conduit if it is being used to pow...

Страница 6: ...ault LED flashes after approximately 3 s indicating a disconnected battery 3 Disconnect the mains power Load Output and Remote Signalling 4 Connect the EPS and PSU Fault outputs to the appropriate inp...

Страница 7: ...ull alarm condition Note ensure batteries have sufficient charge to support the system under full load Final 18 Reconnect the mains Verify that the green Mains LED illuminates and the yellow Fault LED...

Страница 8: ...of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries saf...

Отзывы: