M1EZ8 Installation and Programming

Page 8

1.4 Control Wiring

Zone Inputs (1 thru 8 on main board, 17 thru 208 via expanders)

Zones Z1 thru Z8 are on the main board, others are in groups of 16, starting with Z17.  Each 2 zones share a common
negative terminal.  A zone may be programming for EOL resistor supervision (Default), or normally closed/normally open
without a resistor.  In addition, Burglar and Keyswitch zones may be programmed for EOL with Security Alert on Short, or EOL
with Security Alert on Open/Short, also referred to as a 

Four (4) State Zone 

(firmware 4.3.5 or later).  If EOL resistors are used,

they should be placed at the furthest most remote end of the detection device wiring.   EOL zones permit a combination of
N.C. (normally closed) or N.O. (normally open) devices.  

Using voltage meter probes across the zone and com terminals, a

non-violated EOL zone will measures approx. 7.0 VDC.  An open circuit will be approx. 13.8 VDC.  A shorted circuit will be
0 VDC.  The Keypad also provides the ability “Menu 8 “System Diagnostics” to view zone voltage.

ELK-M1KP

1

See Note about

Data Bus

Termination

6

BLACK

WHITE

GREEN

RED

Keypad

Wiring

Assembly

Data Bus Cable

CAT5 or CAT6 Recommended

Optional programmable Zone Input from Keypad

Hookup Diagram for Keypad

Splice 6 Pin Keypad Wiring Assembly to the Data Bus cable using ELK-900-2 "B" Connectors.

BROWN

Optional programmable Output from Keypad

Keypad 1

The optional Zone Input # or Output # is

determined by the Keypad Address.

Load (50mA max)

I.E. LED, Relay

-

+

To BLACK (Neg) Wire

To BROWN Wire

N.C. N.O.

2200

Ohm

EOL

To BLACK (Neg) Wire

BLUE

To BLUE Wire

NOTE: The first batch of M1KP Keypads provided a switched
negative (pull to ground) output.  Connect per diagram above.
These units have the letter "E" at the end of the ID number on the
lower back side of the board.  EG: PC096

E

  Boards with a letter

"F" or later provide the output as a switched positive.

Load (50mA max)

i.e. Relay, LED

-

+

To Red (Pos) Wire

To Brown Wire

 KP       Zone Output
Address    #        #
     1        193      193
     2        194      194
     3        195      195
     4        196      196
     5        197      197
     6        198      198
     7        199      199
     8        200      200

 KP       Zone Output
Address    #        #
     9        201      201
     10      202      202
     11      203      203
     12      204      204
     13      205      205
     14      206      206
     15      207      207
     16      208      208

Optional Four (4) State Zone Wiring  (2 series resistors w/ N.C. contacts)

Zone
Input

Neg.

N.C. Alarm

Contacts

2200 Ohm

Resistor

2200 Ohm

EOL Resistor

N.C. Tamper

Contacts

Pos.

Neg.

Fig 2: Powered PIR, Glassbreak, etc. with Tamper

N.C.

N.O.

Contact

2200
Ohm

EOL

Zone Input

Neg.

Tamper Contact

N.C.

Alarm

Contact

Diagnostic Table

Short ~

2.2k Ohms
4.4k Ohms

Open ~

0 - 3.9 Volts

4.0 - 7.3 Volts

7.4 - 11 Volts

11.1 - 13.8 Volts

Zone

Resistance

Approx. Zone

Voltage Reading

Alarm

-

Alarm
Alarm

Armed

Sec. Alert/Tamper

Ready

Not Ready

Sec. Alert/Tamper

Disarmed

Condition When:

0 - 72

73 - 159

160 - 220
221 - 255

A to D

Value

Fig 1: N.C. Alarm Contact
(Unpowered) with N.C. Tamper

Program Zone for EOL Wiring

Type 4 -  Supervisory on Open

This feature

requires Firmware

2.3.5 or later.

2200 Ohm

Resistor

Traditional Three (3) State Zone Wiring (1 series resistor)

Wire in Series with zone
input or use another zone.

Neg.

N.C. Alarm

Contacts

2200 Ohm

EOL Resistor

N.C. Tamper

Contacts

Pos.

Neg.

Powered Motion, PIR, Glassbreak, etc.

N.O.

Contact

2200
Ohm

EOL

Zone Input

Neg.

N.C.

Alarm

Contact

Diagostic Table

Short ~

2.2k Ohms

Open ~

0 - 3.9 Volts

4.0 - 8.8 Volts

8.9 - 13.8 Volts

Zone

Resistance

Approx. Range

of Zone Voltage

Alarm

-

Alarm

Armed

Not Ready

Ready

Not Ready

Disarmed

Condition When:

0 - 72

73 - 170

171 - 255

A to D

Value

Zone
Input

Alarm Contact

NOTE: Refer to the section ‘Data Bus E.O.L. Termination’ for information on multiple homerun cables.

 

 NEVER SPLICE OR

CONNECT WIRE WITH CONTROL POWER ON.

  Minimum cabling should be four conductor 22 or 24 gauge.  Maximum resistance per wire

is 25 Ohms. Device placement beyond 1000' is not recommended.

Содержание EZ8 ELK-M1EZ8

Страница 1: ...Cross Platform Control Part ELK M1EZ8 A member of the M1 Family Specifications Installation and Programming M1 includes the SIA CP 01 Standards for False Alarm Reduction TM L523 Rev I 08 06 08 Current...

Страница 2: ...or low temperatures as well as large swings in temperature may all reduce the actual battery life in a given installation This wireless system however can identify a true low battery situation thus a...

Страница 3: ...keover 19 3 4 Area Partitioning 19 3 5 Communicator Setup Checklist 20 3 6 Entering Installer Level Programming 20 Menu 01 Bus Module Enrollment 22 Menu 02 User Code Options 23 Menu 03 Area Definition...

Страница 4: ...ever event can have one or more ANDs and THENs conditions and commands Total number of Rules Supported 528 Rules utilize easy to understand text based references Control lighting using RS 232 serial o...

Страница 5: ...Green Red Black 1 1 8 Conductor Cat5 cable from EZ8MSI Main Serial Port Interface End view Brn Wht Wht Brn Grn Wht Wht Blue Blue Wht Wht Grn Org Wht Wht Org 1 Wht Org Org Wht Wht Grn Blue Wht Wht Blu...

Страница 6: ...M1EZ8InstallationandProgramming Page 6 Intentionally Left Blank...

Страница 7: ...h those in the figure above to familiarize yourself with the part names Mount the control using the upper center slotted hole to level Install and connect all necessary wiring for the power transforme...

Страница 8: ...lower back side of the board EG PC096E Boards with a letter F or later provide the output as a switched positive Load 50mA max i e Relay LED To Red Pos Wire To Brown Wire KP Zone Output Address 1 193...

Страница 9: ...ower unplug the outputs for approx 20 seconds after a short to allow the PTC to reset Even if the short is no longer present the remaining residual current draw may be so high that the PTC cannot dete...

Страница 10: ...Rules Programming and can be triggered by multiple conditions events Do not exceed the current limits on voltage only outputs Output 2 Connect a UL Listed Bell or Siren self contained Current limited...

Страница 11: ...ch device directly to the M1 s VKP and Neg terminals DO NOT SERIES THE POWER WIRES as this will cause unnecessary voltage loss The ELK M1DBH Data Bus Hub accepts CAT5 or CAT6 cable with RJ45 plugs on...

Страница 12: ...ming 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 123456...

Страница 13: ...e User s Guide contains a description of operations accessible to the user codes Control operations accessed by the installer passcode are slightly different Factory Default for User Code 1 is 3 4 5 6...

Страница 14: ...rogrammed for Force arm Keypad Models and Feature Comparison PART NUMBER ELKM1KP ELKM1KP2 ELKM1KPAS PHYSICAL DIMENSIONS 6 87 W x 5 25 H x 1 32 D 4 65 W x 5 5 H x 95 D 1 3 W x 2 62 H x 3 D actual keypa...

Страница 15: ...789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 12345678901234567890...

Страница 16: ...123456789012345678901 1234567890123456789012345678901 1234567890123456789012345678901 1234567890123456789012345678901 1234567890123456789012345678901 8 System r Settings 123456789012345678901234567890...

Страница 17: ...3456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 1234567890123456...

Страница 18: ...012345678 1234567890123456789012345678 1234567890123456789012345678 0 Select Keypad Alternate Area r 1234567890123456789012345678 1234567890123456789012345678 1234567890123456789012345678 123456789012...

Страница 19: ...d log on serial number and dealer assigned RP access code The serial identifies the control to RP while the RP access code identifies the computer to the control prior to a programming session RP load...

Страница 20: ...omatic SIA or Contact ID codes program a 1 01 5 Under Menu 12 Sys Report Code Options Codes select and program each desired option such as AC Fail Low Battery Automatic Test and other system wide opti...

Страница 21: ...als 1 Receiver Size Menu 03 Menu 05 4 Celcius Disp 45 Default Control Options 18 Name 2 ZnBank Start Zn Area Defs Zone Defs 5 DST Observe 81 Default User Codes 3 Reg Supv Hrs Area 1 Zone 1 6 Fast Loop...

Страница 22: ...89012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 1234567890123456789012...

Страница 23: ...n the same area Default value for both these options is No code not required for bypass A Yes allows this code to activate the Access Keypad Events 1313 1328 for the keypad where code is entered Use t...

Страница 24: ...entry delay time in seconds for zones programmed as Entry Delay 1 Range is 030 to 255 seconds Default value is 030 The amount of exit delay time in seconds for zones programmed as Exit Delay 2 Range i...

Страница 25: ...press the right or left arrow keys While programming the text pressing the Chime key inserts a space and the Bypass key erases 1 digit The up and down arrow keys toggle between upper and lower case P...

Страница 26: ...ogram or press the up or down arrow keys to select another keypad To jump to any keypad enter the number 1 16 The keypad name displays on the bottom A keypad can only be assigned as primary for a sing...

Страница 27: ...ich will cause the key to light up See Event Codes in Appendix A Press the RIGHT arrow key and enter 4 digits The bottom line displays the description of the event Press the RIGHT arrow key to move to...

Страница 28: ...STAY INSTANT arm modes 07 Burglar Interior Nite Delay For motion detectors interior doors etc that are not close to sleeping areas Same as an Interior Nite zone except that Interior Nite Delay zones...

Страница 29: ...mentary Away Mode Intended for a spring loaded momentary key switch Arms the area in the AWAY mode with each trip 28 Keyswitch Momentary Stay Mode Intended for a spring loaded momentary key switch Arm...

Страница 30: ...the right or left arrow keys While programming the text pressing the Chime key inserts a space and the Bypass key erases 1 digit The up and down arrow keys move between upper and lower case Press the...

Страница 31: ...1234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 123456789012345678901234567890...

Страница 32: ...this option Default is No 4 digits NOTE The Installer code is ALWAYS 6 digits To prevent a would be thief or hacker from being able to hunt for a valid user code the system can automatically lock out...

Страница 33: ...rted from a siren driver into a voltage only output If set to No the control produces alarm sounds for use with 8 Ohm speakers If set to Yes the control will produce 12 Volts for use with self contain...

Страница 34: ...123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 G28 No Out2 r SingleAlmLockout 123456789012345678901234567890121234 123456789012345678901...

Страница 35: ...7890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123...

Страница 36: ...7890121234 T1 01 Format 0 r 0 Disabled 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 1234567890123...

Страница 37: ...While programming the text pressing the Chime key inserts a space and the Bypass key erases 1 digit The up and down arrow keys toggles between upper and lower case Press the ELK key when complete 1234...

Страница 38: ...567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 12...

Страница 39: ...23 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 AR1 15 Code 00r O...

Страница 40: ...g with the SIA and Contact ID formats is to set the programmed code to a non zero 0 value See below Press RIGHT arrow key to select this menu Press UP or DOWN arrow keys to select another menu The ELK...

Страница 41: ...012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 1234567890123...

Страница 42: ...789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901...

Страница 43: ...ssion as a verification that the control was accessed Range is 00 to FF Default is 00 no report Phone Line Fault T Trouble will be reported if the Voltage and Current is lost on the telephone line Pho...

Страница 44: ...1234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 1234567890...

Страница 45: ...4 123456789012345678901234567890121234 123456789012345678901234567890121234 RO2 00 ZnBank r StartingZone xxx 1234567890123456789012345678901212345 1234567890123456789012345678901212345 123456789012345...

Страница 46: ...890123456789012345678901212345 1234567890123456789012345678901212345 1234567890123456789012345678901212345 1234567890123456789012345678901212345 1234567890123456789012345678901212345 12345678901234567...

Страница 47: ...omatic RP dials the control phone number and listens for the control to answer on it s rings until answer setting If an answering machine answers RP will transmit codes to override it automatically Pr...

Страница 48: ...word restricted M1 Dealers ONLY location NOTE Firmware updating can only be done from a Direct to PC Com port connection or an optional Ethernet Network connection Due to the amount of data that has t...

Страница 49: ...to happen at a given time or in response to a set of circumstances The following information is intended to provide an overview of the vast automation features in the control TASKS A Task is similar t...

Страница 50: ...ew Z Wave wireless devices Even if a lighting product is not directly supported it is always possible to use RS 232 ASCII strings for communicating lighting control OUTPUTS These can be in the form of...

Страница 51: ...23 59 COUNTERS These memory locations often called flags can be set incremented decremented or compared by an automation rule to track an event or keep up with how many times an event has occurred The...

Страница 52: ...ut a serial port might be a series of ASCII characters formatted to a certain manufacturers protocol Special options built into this menu include automatic display of temperature readings from Zone Te...

Страница 53: ...iggering event in order to be started A triggering event can be a time of day occurrence a zone opening or closing the security system going from armed to disarmed a light changing from on to off or l...

Страница 54: ...OF THE WEEK IS ARE M W F Example 5 AND IT IS DARK OUTSIDE Example 6 AND John s House Area 1 IS ARMED AWAY THEN The third and final element of a rule is the action that you wish to occur as a result o...

Страница 55: ...nal AND element could be added to prevent the fan from operating on certain days or at certain times Rule 4 is another energy savings example It adjusts the cooling setpoint of the Main Floor Thermost...

Страница 56: ...2 Keypad 01 Code Lockout N 1113 Keypad 02 Code Lockout N 1114 Keypad 03 Code Lockout N 1115 Keypad 04 Code Lockout N 1116 Keypad 05 Code Lockout N 1117 Keypad 06 Code Lockout N 1118 Keypad 07 Code Loc...

Страница 57: ...Back B 1310 Area 6 Closing Ring Back B 1311 Area 7 Closing Ring Back B 1312 Area 8 Closing Ring Back B 1313 Access Keypad 1 TM 1314 Access Keypad 2 TM 1315 Access Keypad 3 TM 1316 Access Keypad 4 TM 1...

Страница 58: ...M1EZ8InstallationandProgramming Page 58 Appendix B C Unused Intentionally left blank...

Страница 59: ...M1EZ8InstallationandProgramming Page 59 Intentionally left blank...

Страница 60: ...1st ring and allow the Operator to press 55 to initiate a two way session 2 Once a two way session has begun it will continue for 3 minutes before automatically disconnecting To extend the two way ses...

Страница 61: ...y another zone Programmable from 1 to 255 seconds For all non fire zones shut down at 1 trip Depends on Panel and Sensors Call waiting cancel prefix code may be dialed on initial attempt ONLY Enabled...

Страница 62: ...M1EZ8InstallationandProgramming Page 62 Appendix F Unused Intentionally left blank...

Страница 63: ...M1EZ8InstallationandProgramming Page 63 Appendix F Unused Intentionally left blank...

Страница 64: ...M1EZ8InstallationandProgramming Page 64 Not evaluated by UL Intentionally left blank Appendix F Unused...

Страница 65: ...ey and the LCD will display Temperature Degrees F XX X This is the current temperature 3 Use the UP or DOWN arrow keys to adjust the temp display until it approximates the desired setting Each press c...

Страница 66: ...s warranty period contact ELK or one of its authorized distributors for a Return Authorization RMA number Returned Products must include a complete description of the problem along with the RA number...

Страница 67: ...Definitions 25 Menu 04 Keypad Definitions 26 Menu 05 Zone Definitions 28 Menu 06 Alarm Cutoff Timers 31 Menu 07 Global System Definitions 32 Menu 08 Telephone Account Setup 36 Menu 09 Area Reporting...

Страница 68: ...www elkproducts com Printed in USA...

Отзывы: