M1EZ8 Installation and Programming
Page 40
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
Z001: Sel
b
Prg
r
[Name of Zone]
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
123456789012345678901234567890121234
Z001:A=00 R=00
r
Byp=00 Tbl=00
Menu 10 - Zone Reporting Codes
12345678901234567890123456789012123
12345678901234567890123456789012123
12345678901234567890123456789012123
12345678901234567890123456789012123
12345678901234567890123456789012123
12345678901234567890123456789012123
12345678901234567890123456789012123
12345678901234567890123456789012123
12345678901234567890123456789012123
12345678901234567890123456789012123
12345678901234567890123456789012123
10-Zone Reportng
Codes
r
Zone Report Codes
Description of Option
Zones 1 thru 8 and zones 17 thru 208 have specific communicator reporting codes for
Alarm, Restore, Bypass, and Trouble. Using the up/down arrow keys, select the
appropriate zone, then press the right arrow key to begin programming of that zone.
NOTE: Zones 9 thru 16 do not exist in the M1EZ8.
The cursor starts at the 00 beside A (Alarm). Enter the desired two digit reporting code
and press the right arrow key to advance to the R (Restore). To jump the cursor to another
report without changing this one simply press the right arrow key. The next press of the
right arrow key after Tbl (Trouble) will advance the screen back to the beginning of that
zone. Range is 00 to FF. Default for all entries is 00 (no report).
NOTE: Each reporting code must be programmed according to the desired reporting
format. However, for SIA and Contact ID formats the actual reporting digits will be
produced by the control according to the type of alarm or event. The only programming
required to enable reporting with the SIA and Contact ID formats is to set the programmed
code to a non zero (0) value. See below:
Press RIGHT arrow key to select this menu. Press UP or DOWN arrow keys to select
another menu. The ELK key backs up one menu level. To exit press the * or Exit key.
NOTE: Enter a two digit value to enable a report code. To disable a report code enter 00. When SIA or Contact ID is the
reporting format, the two digit value can simply be 01 since the control automatically produces the correct code
according to the SIA or Contact ID protocol. For 4+2 pulse format, enter a value from 01 to FF. To enter the A thru F
HEX characters press the RIGHT arrow key to position the cursor under the desired digit, then press the UP arrow (shift)
key once. Each press of the 2 key will now produce the following: 2, A, B, C. Each press of the 3 key will now produce
the following: 3, D, E, F. Press the RIGHT arrow key to cancel shift and move to the next character. See Appendix for
a summary of the SIA and Contact ID codes.
Alarms
Restore
Bypass
Trouble
Zone Def.
CID SIA
CID SIA
CID SIA CID SIA
01 = Burglar Entry/Exit 1
134 BA
134 B R
573 BB
370 BT
02 = Burglar Entry/Exit 2
134 BA
134 B R
573 BB
370 BT
03 = Burglar Perim Inst
131 BA
131 B R
573 BB
370 BT
04 = Burglar Interior
132 BA
132 B R
573 BB
370 BT
05 = Burglar Int Follower
132 BA
132 B R
573 BB
370 BT
06 = Burglar Int Night
135 BA
135 B R
573 BB
370 BT
07 = Burglar Int Nt Fllwr
135 BA
135 B R
573 BB
370 BT
08 = Burglar 24 Hour
133 BA
133 B R
573 BB
370 BT
09 = Burglar Box Tamper
137 TA
137 T R
573 TB
370 BT
10 = Fire Alarm
110
FA
110
F R
571 FB
373 FT
11 = Fire Verified
110
FA
110
F R
571 FB
373 FT
12 = Fire Supervisory
200 FS
200 F R
571 FB
373 FT
13 = Aux Function 1
150 UA
150 U R
572 UB
----
----
14 = Aux Function 2
150 UA
150 U R
572 UB
----
----
15 = Keyfob
----
----
----
----
----
---- ----
----
16 = Non Alarm
----
----
----
----
----
---- ----
----
17 = Carbon Monoxide
162 GA
162 GR
572 GB ----
----
Based on the zone definition, the CID (Contact ID) or SIA formats for Zone Reporting Codes will be:
Alarms
Restore
Bypass
Trouble
Zone Def.
CID SIA
CID SIA
CID SIA CID SIA
18 = Emergency Alarm
101 QA
101 Q R 572 QB ----
----
19 = Freeze Alarm
159 Z A
159 Z R
572 ZB
----
----
20 = Gas Alarm
151 GA
151 G R 572 GB ----
----
21 = Heat Alarm
114
KA
114
K R
572 KB
----
----
22 = Medical Alarm
100 MA
100 M R 572 MB ----
----
23 = Police Alarm
120 P A
120 P H
572 PB
----
----
24 = Police No Indication
120 P A
120 H H
572 PB
----
----
25 = Water Alarm
154 WA 154 WR
572 WB ----
----
26 = Key Mom Arm/Disarm ---- ----
----
----
----
---- ----
----
27 = Key Mom Arm Away ---- ----
----
----
----
---- ----
----
28 = Key Mom Arm Stay
---- ----
----
----
----
---- ----
----
29 = Key Mom Disarm
---- ----
----
----
----
---- ----
----
30 = Key On/Off
---- ----
----
----
----
---- ----
----
31 = Mute Audibles
---- ----
----
----
----
---- ----
----
32 = Power Supervisory
338 YT
338 YR
572 UB
----
----
33 = Temperature
----
----
----
----
----
---- ----
----
34 = Analog Zone
---- ----
----
----
----
---- ----
----
NOTE: On CID reporting the 3 digit code is preceded by a “1” for new events or a “3” for restore (previous reported) events.
Содержание EZ8 ELK-M1EZ8
Страница 6: ...M1EZ8InstallationandProgramming Page 6 Intentionally Left Blank...
Страница 58: ...M1EZ8InstallationandProgramming Page 58 Appendix B C Unused Intentionally left blank...
Страница 59: ...M1EZ8InstallationandProgramming Page 59 Intentionally left blank...
Страница 62: ...M1EZ8InstallationandProgramming Page 62 Appendix F Unused Intentionally left blank...
Страница 63: ...M1EZ8InstallationandProgramming Page 63 Appendix F Unused Intentionally left blank...
Страница 64: ...M1EZ8InstallationandProgramming Page 64 Not evaluated by UL Intentionally left blank Appendix F Unused...
Страница 68: ...www elkproducts com Printed in USA...