1.1 Planning the Installation

The first step in any multi-zone security system installation is planning the job.
1.

Read this entire manual to familiarize yourself with all system features and procedures before actually beginning the
installation. Read all the information regarding Underwriters Laboratories (UL) and NFPA requirements.

2.

Perform a physical survey of the installation site. Use the diagrams below as a guide in planning the installation.

3.

Discuss the installation requirements and applications with the customer.

4.

Compare the installation requirements and applications with the factory default settings to determine what customized
programming is needed to meet the specific installation requirements.

5.

Bench test the system prior to installation.

1.2 Parts Diagram & Descriptions

See Wiring & Hookup Diagram on pages 6 & 7.

1.3 Mounting and Wiring Preparation

Control Mounting

DO NOT MOUNT THE CONTROL OUTDOORS OR IN A DAMP LOCATION OR WHERE THE ENVIRONMENTAL CONDITIONS
ARE UNSUITABLE FOR ELECTRONIC BASED EQUIPMENT.  DO NOT MOUNT IN AN UNCONDITIONED ATTIC.  USE
COMMON SENSE AND GOOD INSTALLATION PRACTICES.  A suitable location would be inside a secure dry location where
the ambient temperature inside the control box can remain at 32‘ to 120

°

 Fahrenheit (0’ to +49' Celsius).  Choose a location

that allows easy wiring to an unswitched power outlet and to a grounding conductor for the control.  A central location makes
running system wiring easier. Remove control box knockouts that best suit your wiring needs.

After removing all packing materials, compare the system components with those in the figure above to familiarize yourself
with the part names. Mount the control using the upper center slotted hole to level. Install and connect all necessary wiring for
the power transformer, detection loops, keypads and siren outputs.

Keypad Mounting and Wiring

Ideal keypad height is 50-58 inches above the floor.  Select a location with an ambient temperature range between 32

°

 and

120

°

 F (0° to +49

°

 C).  Avoid direct sunlight if possible.  Fasten mounting plate to electrical box (or directly to wall) using flat

head screws to prevent shorts to the back of the circuit board.  Keypads have a removable wiring plug for connecting to the M1
4-wire data bus.   CAT5 or CAT6 eight (8) conductor cable is recommended for all Data Bus cables.  The extra wires provide
data return paths.  Splice the Black, Red, White, and Green wires from the removable wiring plug to the Data Bus cable.  Plug
the connector into the back of the keypad.  Tuck wires neatly into back plate and install Keypad on mounting plate. Each
keypad has connections for an optional programmable output and a programmable zone input.

Section 1 - Installation and Wiring

Legend
- Main Control
- Audible Alarm
- Smoke Detector
- Contact
- Keypad

M

A
S
C
K

Bedroom 1

Bedroom 2

Bedroom 3

Living Room

Kitchen / Dining

TYPICAL BURGLARY INSTALLATION LAYOUT

M

A

K

Bedroom 1

Bedroom 2

Bedroom 3

Living Room

Kitchen / Dining

TYPICAL FIRE INSTALLATION LAYOUT

M

A

K

C

C

C

C

C

C

S

S

S

S

Basement

First Floor

All perimeter openings below 18" should be provided with protection.

A Smoke Detector shall be located in each sleeping area and between
the sleeping areas and the main living area.

Early warning fire detection is best achieved by the installation of fire
detection equipment in the location shown above.

In homes basements or multiple levels at least one smoke detector
shall be on each level.

Содержание EZ8 ELK-M1EZ8

Страница 1: ...Cross Platform Control Part ELK M1EZ8 A member of the M1 Family Specifications Installation and Programming M1 includes the SIA CP 01 Standards for False Alarm Reduction TM L523 Rev I 08 06 08 Current...

Страница 2: ...or low temperatures as well as large swings in temperature may all reduce the actual battery life in a given installation This wireless system however can identify a true low battery situation thus a...

Страница 3: ...keover 19 3 4 Area Partitioning 19 3 5 Communicator Setup Checklist 20 3 6 Entering Installer Level Programming 20 Menu 01 Bus Module Enrollment 22 Menu 02 User Code Options 23 Menu 03 Area Definition...

Страница 4: ...ever event can have one or more ANDs and THENs conditions and commands Total number of Rules Supported 528 Rules utilize easy to understand text based references Control lighting using RS 232 serial o...

Страница 5: ...Green Red Black 1 1 8 Conductor Cat5 cable from EZ8MSI Main Serial Port Interface End view Brn Wht Wht Brn Grn Wht Wht Blue Blue Wht Wht Grn Org Wht Wht Org 1 Wht Org Org Wht Wht Grn Blue Wht Wht Blu...

Страница 6: ...M1EZ8InstallationandProgramming Page 6 Intentionally Left Blank...

Страница 7: ...h those in the figure above to familiarize yourself with the part names Mount the control using the upper center slotted hole to level Install and connect all necessary wiring for the power transforme...

Страница 8: ...lower back side of the board EG PC096E Boards with a letter F or later provide the output as a switched positive Load 50mA max i e Relay LED To Red Pos Wire To Brown Wire KP Zone Output Address 1 193...

Страница 9: ...ower unplug the outputs for approx 20 seconds after a short to allow the PTC to reset Even if the short is no longer present the remaining residual current draw may be so high that the PTC cannot dete...

Страница 10: ...Rules Programming and can be triggered by multiple conditions events Do not exceed the current limits on voltage only outputs Output 2 Connect a UL Listed Bell or Siren self contained Current limited...

Страница 11: ...ch device directly to the M1 s VKP and Neg terminals DO NOT SERIES THE POWER WIRES as this will cause unnecessary voltage loss The ELK M1DBH Data Bus Hub accepts CAT5 or CAT6 cable with RJ45 plugs on...

Страница 12: ...ming 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 12345678901234567890123456 123456...

Страница 13: ...e User s Guide contains a description of operations accessible to the user codes Control operations accessed by the installer passcode are slightly different Factory Default for User Code 1 is 3 4 5 6...

Страница 14: ...rogrammed for Force arm Keypad Models and Feature Comparison PART NUMBER ELKM1KP ELKM1KP2 ELKM1KPAS PHYSICAL DIMENSIONS 6 87 W x 5 25 H x 1 32 D 4 65 W x 5 5 H x 95 D 1 3 W x 2 62 H x 3 D actual keypa...

Страница 15: ...789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 12345678901234567890...

Страница 16: ...123456789012345678901 1234567890123456789012345678901 1234567890123456789012345678901 1234567890123456789012345678901 1234567890123456789012345678901 8 System r Settings 123456789012345678901234567890...

Страница 17: ...3456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 123456789012345678901234567890 1234567890123456...

Страница 18: ...012345678 1234567890123456789012345678 1234567890123456789012345678 0 Select Keypad Alternate Area r 1234567890123456789012345678 1234567890123456789012345678 1234567890123456789012345678 123456789012...

Страница 19: ...d log on serial number and dealer assigned RP access code The serial identifies the control to RP while the RP access code identifies the computer to the control prior to a programming session RP load...

Страница 20: ...omatic SIA or Contact ID codes program a 1 01 5 Under Menu 12 Sys Report Code Options Codes select and program each desired option such as AC Fail Low Battery Automatic Test and other system wide opti...

Страница 21: ...als 1 Receiver Size Menu 03 Menu 05 4 Celcius Disp 45 Default Control Options 18 Name 2 ZnBank Start Zn Area Defs Zone Defs 5 DST Observe 81 Default User Codes 3 Reg Supv Hrs Area 1 Zone 1 6 Fast Loop...

Страница 22: ...89012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 1234567890123456789012...

Страница 23: ...n the same area Default value for both these options is No code not required for bypass A Yes allows this code to activate the Access Keypad Events 1313 1328 for the keypad where code is entered Use t...

Страница 24: ...entry delay time in seconds for zones programmed as Entry Delay 1 Range is 030 to 255 seconds Default value is 030 The amount of exit delay time in seconds for zones programmed as Exit Delay 2 Range i...

Страница 25: ...press the right or left arrow keys While programming the text pressing the Chime key inserts a space and the Bypass key erases 1 digit The up and down arrow keys toggle between upper and lower case P...

Страница 26: ...ogram or press the up or down arrow keys to select another keypad To jump to any keypad enter the number 1 16 The keypad name displays on the bottom A keypad can only be assigned as primary for a sing...

Страница 27: ...ich will cause the key to light up See Event Codes in Appendix A Press the RIGHT arrow key and enter 4 digits The bottom line displays the description of the event Press the RIGHT arrow key to move to...

Страница 28: ...STAY INSTANT arm modes 07 Burglar Interior Nite Delay For motion detectors interior doors etc that are not close to sleeping areas Same as an Interior Nite zone except that Interior Nite Delay zones...

Страница 29: ...mentary Away Mode Intended for a spring loaded momentary key switch Arms the area in the AWAY mode with each trip 28 Keyswitch Momentary Stay Mode Intended for a spring loaded momentary key switch Arm...

Страница 30: ...the right or left arrow keys While programming the text pressing the Chime key inserts a space and the Bypass key erases 1 digit The up and down arrow keys move between upper and lower case Press the...

Страница 31: ...1234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 123456789012345678901234567890...

Страница 32: ...this option Default is No 4 digits NOTE The Installer code is ALWAYS 6 digits To prevent a would be thief or hacker from being able to hunt for a valid user code the system can automatically lock out...

Страница 33: ...rted from a siren driver into a voltage only output If set to No the control produces alarm sounds for use with 8 Ohm speakers If set to Yes the control will produce 12 Volts for use with self contain...

Страница 34: ...123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 G28 No Out2 r SingleAlmLockout 123456789012345678901234567890121234 123456789012345678901...

Страница 35: ...7890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123...

Страница 36: ...7890121234 T1 01 Format 0 r 0 Disabled 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 1234567890123...

Страница 37: ...While programming the text pressing the Chime key inserts a space and the Bypass key erases 1 digit The up and down arrow keys toggles between upper and lower case Press the ELK key when complete 1234...

Страница 38: ...567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 12...

Страница 39: ...23 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 AR1 15 Code 00r O...

Страница 40: ...g with the SIA and Contact ID formats is to set the programmed code to a non zero 0 value See below Press RIGHT arrow key to select this menu Press UP or DOWN arrow keys to select another menu The ELK...

Страница 41: ...012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 12345678901234567890123456789012123 1234567890123...

Страница 42: ...789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901...

Страница 43: ...ssion as a verification that the control was accessed Range is 00 to FF Default is 00 no report Phone Line Fault T Trouble will be reported if the Voltage and Current is lost on the telephone line Pho...

Страница 44: ...1234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 123456789012345678901234567890121234 1234567890...

Страница 45: ...4 123456789012345678901234567890121234 123456789012345678901234567890121234 RO2 00 ZnBank r StartingZone xxx 1234567890123456789012345678901212345 1234567890123456789012345678901212345 123456789012345...

Страница 46: ...890123456789012345678901212345 1234567890123456789012345678901212345 1234567890123456789012345678901212345 1234567890123456789012345678901212345 1234567890123456789012345678901212345 12345678901234567...

Страница 47: ...omatic RP dials the control phone number and listens for the control to answer on it s rings until answer setting If an answering machine answers RP will transmit codes to override it automatically Pr...

Страница 48: ...word restricted M1 Dealers ONLY location NOTE Firmware updating can only be done from a Direct to PC Com port connection or an optional Ethernet Network connection Due to the amount of data that has t...

Страница 49: ...to happen at a given time or in response to a set of circumstances The following information is intended to provide an overview of the vast automation features in the control TASKS A Task is similar t...

Страница 50: ...ew Z Wave wireless devices Even if a lighting product is not directly supported it is always possible to use RS 232 ASCII strings for communicating lighting control OUTPUTS These can be in the form of...

Страница 51: ...23 59 COUNTERS These memory locations often called flags can be set incremented decremented or compared by an automation rule to track an event or keep up with how many times an event has occurred The...

Страница 52: ...ut a serial port might be a series of ASCII characters formatted to a certain manufacturers protocol Special options built into this menu include automatic display of temperature readings from Zone Te...

Страница 53: ...iggering event in order to be started A triggering event can be a time of day occurrence a zone opening or closing the security system going from armed to disarmed a light changing from on to off or l...

Страница 54: ...OF THE WEEK IS ARE M W F Example 5 AND IT IS DARK OUTSIDE Example 6 AND John s House Area 1 IS ARMED AWAY THEN The third and final element of a rule is the action that you wish to occur as a result o...

Страница 55: ...nal AND element could be added to prevent the fan from operating on certain days or at certain times Rule 4 is another energy savings example It adjusts the cooling setpoint of the Main Floor Thermost...

Страница 56: ...2 Keypad 01 Code Lockout N 1113 Keypad 02 Code Lockout N 1114 Keypad 03 Code Lockout N 1115 Keypad 04 Code Lockout N 1116 Keypad 05 Code Lockout N 1117 Keypad 06 Code Lockout N 1118 Keypad 07 Code Loc...

Страница 57: ...Back B 1310 Area 6 Closing Ring Back B 1311 Area 7 Closing Ring Back B 1312 Area 8 Closing Ring Back B 1313 Access Keypad 1 TM 1314 Access Keypad 2 TM 1315 Access Keypad 3 TM 1316 Access Keypad 4 TM 1...

Страница 58: ...M1EZ8InstallationandProgramming Page 58 Appendix B C Unused Intentionally left blank...

Страница 59: ...M1EZ8InstallationandProgramming Page 59 Intentionally left blank...

Страница 60: ...1st ring and allow the Operator to press 55 to initiate a two way session 2 Once a two way session has begun it will continue for 3 minutes before automatically disconnecting To extend the two way ses...

Страница 61: ...y another zone Programmable from 1 to 255 seconds For all non fire zones shut down at 1 trip Depends on Panel and Sensors Call waiting cancel prefix code may be dialed on initial attempt ONLY Enabled...

Страница 62: ...M1EZ8InstallationandProgramming Page 62 Appendix F Unused Intentionally left blank...

Страница 63: ...M1EZ8InstallationandProgramming Page 63 Appendix F Unused Intentionally left blank...

Страница 64: ...M1EZ8InstallationandProgramming Page 64 Not evaluated by UL Intentionally left blank Appendix F Unused...

Страница 65: ...ey and the LCD will display Temperature Degrees F XX X This is the current temperature 3 Use the UP or DOWN arrow keys to adjust the temp display until it approximates the desired setting Each press c...

Страница 66: ...s warranty period contact ELK or one of its authorized distributors for a Return Authorization RMA number Returned Products must include a complete description of the problem along with the RA number...

Страница 67: ...Definitions 25 Menu 04 Keypad Definitions 26 Menu 05 Zone Definitions 28 Menu 06 Alarm Cutoff Timers 31 Menu 07 Global System Definitions 32 Menu 08 Telephone Account Setup 36 Menu 09 Area Reporting...

Страница 68: ...www elkproducts com Printed in USA...

Отзывы: