background image

If activation state forcing is enabled (dOA
is not 0), the compressor and/or fan out-
puts can be activated when the time set in
parameters dCO and dFO expires.

Parameter H11 is used to configure the
digital input with values between -9 and
+9. Positive and negative values are used
to select the polarity assigned to the input
and:
NOTE: 
the sign “-” indicates that the input is
activated when the contact is closed
The ‘+’ sign indicates that the input is
activated when the contact is open

DEVICE STAND-BY CONTROLLER
This controls the operating mode of the
device when it is on stand by according to
the following parameters: 

The Stand-by controller can be digital input
or button enabled if suitably configured. 
The status of the instrument when on
stand-by is determined by the value of
parameter H08. Three possible operating
modes are defined:
EXAMPLE 1: the display is off and the con-
trollers active, the instrument signals any
alarms by reactivating the display - OFF DIS-
PLAY
EXAMPLE 2: the display is off and all the
controllers, including the alarms, are also
disabled  - STAND-BY
EXAMPLE 3: the display shows the “OFF”
label and all the controllers, including the
alarms, are also disabled- STAND-BY

LINK
The Link function is used to connect up to
8 instruments (1 Master device and 7 slave
devices). The distance between one device
and another must be 7 metres maximum
whereas the maximum distance between
the first and last instrument in the network
must be approximately 50m.
NOTE: the serial link between the devices is
powered.

Master
Instrument that controls the networks and
sends commands to the Slaves. The Master
is selected using parameter L00 (the value 0
defines the Master)
Slave
Instrument(s) with own controllers that also
perform(s) commands issued by the Master
(with parameters L03..L06).

Echo
This only displays the values of the instru-
ment that it is associated with (it does not
therefore have its own I/O resources but
only serves as a repeater). 
NOTE: only one Echo can be connected to
anyone instrument. 

Defrosting
The Link network controls defrosting. The
Master sends the defrost command which
can be performed synchronously (at the
same time) or sequentially (one defrost
after another) without affecting the normal
protections or delays for each instrument
(see parameter L03).

Other Functions
The Master can also activate the functions
associated with buttons or the Digital Input
for all the Slaves: switching lights on/off,
alarm silencing, auxiliary set point, auxiliary
relay, stand-by (on/off) and functions relat-
ed to Night & Day controller (see parame-
ter L05). 
The Master can also synchronize the Slave
(or Echo device) displays with the Master
device display (see parameter L04). 
NOTE: synchronized defrosting refers to
actual defrosting and not to dripping and
subsequent defrosting. The defrost LED on
the Slave units blinks when synchronized
defrosting has terminated and the Slaves
are awaiting for the thermostat control to
be enabled by the Master. 
The functions are associated with the
instruments by correctly setting the para-
meters (see the parameter table for the
“Lin” label folder)

DEFROST CONTROL
The instrument can be used to select dif-
ferent types of defrosting with the para-
meter dty, defrost type
(defrost execution mode). 
The dty parameter can have these values:
0 = electrical defrosting; the compressor is

turned off. 

1 = cycle reversing defrosting (hot gas); 

the compressor continues operating. 

2 = Free mode defrosting (compressor dis

abled).

Configuration of 3

rd

probe as 2nd evap-

orator probe
The 3

a

probe can be used to control the

defrosting of a second evaporator by con-
figuring a relay output as a 2nd evaporator
defrost relay (see par. H21…H26). 
To implement this function: 

a) configure the 3

rd

probe in 2nd evapora-

tor defrost control mode (par. H43=2EP). 
b) configure a relay output as 2nd evapo-
rator defrost relay (configuration parame-
ters H21…H26). 
c) define the defrost mode by setting
parameter H45.

Start of defrosting
If two evaporators are used, defrosting
starts in three different ways that are
determined by parameter H45.
• H45=0:  Defrosting is enabled by con-
trolling the temperature of the 1st evapo-
rator so it is lower than parameter dSt,
•H45=1: Defrosting is enabled by control-
ling so that at least one of the two probes
is below its end of defrosting temperature
(dSt for the 1st evaporator and dS2 for
the 2nd evaporator)
• H45=2: Defrosting is enabled by control-
ling so that both the probes are below
their respective end of defrosting set
points (dSt for the 1st evaporator and dS2
for the 2nd evaporator) 
The probe error condition is considered
the defrost calling probe. 
When defrosting is terminated by a probe
or is timed out (see par. dEt), dripping fol-
lows (see par. dt).

End of defrosting
If two evaporators are used, defrosting
ends when both the probes have reached
or exceeded their respective end of
defrosting set points (dSt for the 1st evap-
orator and dS2 for the 2nd evaporator) 
If one or both the probes are faulty,
defrosting is ended by a time-out.
NOTE:
• If there are no conditions for defrosting,
the request is ignored. 
Defrosting of a single evaporator ends
when the value read by the respective
probe is equal to or higher than the end
of defrosting temperature or a time-out
occurs. Dripping starts when both defrosts
have been completed.
• If one or both the probes are faulty,
defrosting in the corresponding evaporator
is ended by a time-out. 
The start of defrosting is permitted when
the corresponding temperature is lower
than the corresponding set point (dSt or
dS2).
• If probe 3 is not configured as a probe
on the second evaporator (H43 2),
defrosting on the second evaporator
occurs if a digital output is configured to
control defrosting on the second evapora-
tor (see par. H21..H25). If this is the case,
defrosting is confirmed (as if ST3<dS2)
and ends with a time-out. The fan con-
troller remains unchanged.

ID 985/E LX

3/13

Par

Description

PAO

alarm exclusion at start-up 

OdO

Output delay from power-on 

H08

Operating mode in stand-by.

Par

Description

dOd          Digital input switches off loads 
dAd

D.I. activation delay 

OAO

Alarm signal delay after disabling the digi-
tal input (door closed)

tdO

Time out door open. Time out signalled
when D.I is activated. 
(door open)

dOA

Forced behaviour from 
digital input

PEA

Enables forced behaviour from door
switch and/or external alarm 

dCO

Delay in enabling compressor with 
consensus 

dFO

Delay in enabling fans with 
consensus 

H11

Digital output configurability/polarity 1 

H21...H25

Digital output configurability 1...5

Содержание ID 985 E

Страница 1: ...k folder Pb1 probe 1 value folder Pb2 probe 2 value folder Pb3 probe 3 value folder if present Set setting Access the Machine Status menu press the set button and quickly release it The Set folder lab...

Страница 2: ...ing menu in the diS folder If passwords are enabled they will be requested PA1 when entering the Programming menu see the Programming Menu sec tion PA2 in the Cnf folder containing the level 1 paramet...

Страница 3: ...elect dif ferent types of defrosting with the para meter dty defrost type defrost execution mode The dty parameter can have these values 0 electrical defrosting the compressor is turned off 1 cycle re...

Страница 4: ...or dis play probe probe 3 The temperature limits are defined by the HAL maximum alarm LAL minimum alarm and PbA alarm configuration on probe 1 3 or both parameters MAXIMUM AND MINIMUM TEMPERA TURE AL...

Страница 5: ...nputs Serial TTL for Televis or Copy Card con nection Digital outputs 4 outputs on relays first output A SPDT 8 3 A 250Va second and third output B C SPST 8 3 A 250Va fourth output D SPST 5 2 A 250Va...

Страница 6: ...sequent switch ons 0 250 0 1 2 min OdO Delay in enabling outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Type of defrost 0 electrical defrosting 1 cy...

Страница 7: ...e level 1 parameters At level 2 the folders will only display all the level 2 parameters The level marked 1 2 allows the parameter to be displayed at both levels FAd Fan activation intervention differ...

Страница 8: ...ling delay dLt is active n y n 2 flag dAd Delay in enabling digital input 0 255 0 2 min dOd Digital input switches off loads n y n 2 flag Att Determines if LAL and HAL are expressed as absolute values...

Страница 9: ...display n y y 2 Flag L05 Activation of Master network functions n does not ask Slaves for activation of remote functions y asks Slaves for activation of remote functions Slave n ignores activation of...

Страница 10: ...ed set point 3 auxiliary 4 door switch 5 external alarm 6 disables storage of HACCP alarms 7 stand by On Off 8 maintenance request 9 HACCP alarm reset 9 9 0 2 num H08 Stand by operating mode 0 only di...

Страница 11: ...1 2 Copy Card Fpr label UL Transfer of parameter map from instrument to Copy Card dL Transfer of parameter map from Copy Card to instrument 1 1 Fr 8 Formatting Cancels all data in the Copy Card 1 NOT...

Страница 12: ...r Lin set set set set set set set set set set set set set set set set set set set set set set Programming Menu Diagram PARAMETERS level 1 folders CP dEF FAn AL Lit Lin nad Add diS CnF level 2 folders...

Страница 13: ...when the probe temperature is 1 higher than or equal to HAL if Att Ab solute 2 higher than or equal to Set HAL if Att rEl ative if Att Abs olute HAL must be with a sign if Att rEL ative HAL must be on...

Отзывы: