ID 985/E LX

7/13

PAR.

DESCRIPTION

RANGE

DEFAULT

VALUE*

LEVEL**

U.M.

dPO

Determines when instrument starts up if the
defrosting cycle must be activated (if the tempera-
ture on the evaporator allows this) 
y=defrosting activated at start-up 
n=defrosting not activated at start-up

n/y

n

1-2

flag

tcd

Minimum time for each compressor state before
defrosting “Ontime if >0; “Offtime if >0

-31...31

0

2

min

Cod

Compressor “Off” time before defrost cycle. The
compressor is not turned on if a defrost cycle is
expected in the time indicated by the parameter.
0=Function excluded

0...60

0

2

min

F

an controller

-F

An label

Defrosting controller

-deF label

FPt

Determines if “FSt” and “Fot” are expressed as
absolute values or in relation to set point
0=absolute value; 1=value related to set point

0/1

0

2

flag

FSt

Fan stop temperature. Temperature limit that, if
exceeded by the value read by the evaporator
probe, stops the fans.

-50.0...150.0

2.0

1-2

°C/°F

Fot

Fan start temperature. If the temperature read by
the evaporator probe is lower than the set value
the fans remain off.

-50.0...150.0

-50.0

2

°C/°F

NOTE:   At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the 

level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.

FAd

Fan activation intervention differential. 
(see “FSt”, “Fot”)

1.0...50.0

2.0

1-2

°C/°F

Fdt

Delay before fan activation after defrosting

0...250

0

1-2

min

dt

Dripping time

0...250

0

1-2

min

FCO

Disables fans with compressor off 
(Off) 
y = fans active (with thermostat; in response to
value read by defrost probe, see “FSt” parameter);
n = fans off; 
dc = duty cycle (using parameters “Fon” and “FoF”

n/y/dc

y

1-2

flag

dFd

Disables evaporator fans. 
y=fans disabled 
n=fans enabled

y/n

y

1-2

flag

Fod

Enables fan stop with door open and fan re-start
when door is closed (if fans were on). 
n=fans stop; 
y=fans unchanged

n/y

n

2

flag

FdC

Fan shut-down delay after compressor stop
0=function excluded

0...99

0

2

min

Fon

Fan start-up time in Duty mode 
Cycle; valid for FCO=dc 

0...99

0

2

min

FoF

Fan shut-down time in Duty
Cycle; valid for FCO=dc 

0...99

0

2

min

“dd (2)

dE1...dE8; daily defrost start time

0...23/0...59

24

1

hours/min

“Fd (2)

F1...F8 festive defrost start time

0...23/0...59

24

1

hours/min

(3)

SCF

Condenser fan set point

-50.0...150.0

10

2

°C/°F

dCF

Condenser fan differential

-30...30

2

2

°C/°F

tCF

Condenser fan start-up delay after defrost

0...59

0

2

min

dCd

exclusion of condenser fans in defrost mode

n/y

y

2

Flag

Содержание ID 985 E

Страница 1: ...k folder Pb1 probe 1 value folder Pb2 probe 2 value folder Pb3 probe 3 value folder if present Set setting Access the Machine Status menu press the set button and quickly release it The Set folder lab...

Страница 2: ...ing menu in the diS folder If passwords are enabled they will be requested PA1 when entering the Programming menu see the Programming Menu sec tion PA2 in the Cnf folder containing the level 1 paramet...

Страница 3: ...elect dif ferent types of defrosting with the para meter dty defrost type defrost execution mode The dty parameter can have these values 0 electrical defrosting the compressor is turned off 1 cycle re...

Страница 4: ...or dis play probe probe 3 The temperature limits are defined by the HAL maximum alarm LAL minimum alarm and PbA alarm configuration on probe 1 3 or both parameters MAXIMUM AND MINIMUM TEMPERA TURE AL...

Страница 5: ...nputs Serial TTL for Televis or Copy Card con nection Digital outputs 4 outputs on relays first output A SPDT 8 3 A 250Va second and third output B C SPST 8 3 A 250Va fourth output D SPST 5 2 A 250Va...

Страница 6: ...sequent switch ons 0 250 0 1 2 min OdO Delay in enabling outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Type of defrost 0 electrical defrosting 1 cy...

Страница 7: ...e level 1 parameters At level 2 the folders will only display all the level 2 parameters The level marked 1 2 allows the parameter to be displayed at both levels FAd Fan activation intervention differ...

Страница 8: ...ling delay dLt is active n y n 2 flag dAd Delay in enabling digital input 0 255 0 2 min dOd Digital input switches off loads n y n 2 flag Att Determines if LAL and HAL are expressed as absolute values...

Страница 9: ...display n y y 2 Flag L05 Activation of Master network functions n does not ask Slaves for activation of remote functions y asks Slaves for activation of remote functions Slave n ignores activation of...

Страница 10: ...ed set point 3 auxiliary 4 door switch 5 external alarm 6 disables storage of HACCP alarms 7 stand by On Off 8 maintenance request 9 HACCP alarm reset 9 9 0 2 num H08 Stand by operating mode 0 only di...

Страница 11: ...1 2 Copy Card Fpr label UL Transfer of parameter map from instrument to Copy Card dL Transfer of parameter map from Copy Card to instrument 1 1 Fr 8 Formatting Cancels all data in the Copy Card 1 NOT...

Страница 12: ...r Lin set set set set set set set set set set set set set set set set set set set set set set Programming Menu Diagram PARAMETERS level 1 folders CP dEF FAn AL Lit Lin nad Add diS CnF level 2 folders...

Страница 13: ...when the probe temperature is 1 higher than or equal to HAL if Att Ab solute 2 higher than or equal to Set HAL if Att rEl ative if Att Abs olute HAL must be with a sign if Att rEL ative HAL must be on...

Отзывы: