ID 985/E LX

9/13

Communication

Add label

dEA

Device address in family
(valid values from 0 to 14)

0...14

0 (Televis models)

1=(Modbus models)

1-2

num

FAA

Device family (valid values from 0 to 14)

0...14

0

1-2

num

Night & Day Control-

nAd label

E00

Functions enabled during events; 
0=control disabled

1=reduced set point 

2=reduced set point+light 3=reduced set point+light+aux
4=instrument off

0...4

0

2

num

E01

Hours/minutes of start of intervention. Starting
from this time, the “NIGHT” mode will be enabled.
The duration is determined by EO2

0...23/0...59

0

2

hours/min

E02

Duration of event. Sets the duration of the event
that begins at time E01 determined by value E00

0...99

0

2

hours

E03  (6)

Blocking/unblocking daily or holidays defrosting.
0= “work days” defrost sequence defined by para-
meters dE1...dE8; 
1= “festive/holidays” defrost sequence defined by
parameters F0...F8

0/1

0

2

flag

PAR.

DESCRIPTION

RANGE

DEFAULT

VALUE*

LEVEL**

U.M.

Link

-label Lin

L00

Selects the instrument as Master 
(0), Slave (from 1 to 7).

0...7

0

2

num

L01

Number of Slaves in the Network Refers to Master
only Number of Slaves in network (from 0 to 7).
Per Slaves/Echo leave value =0

0...7

0

2

num

L02

Enables ECHO control on slave: 
0=instrument does not control ECHO 
1=instrument controls ECHO

0/1

0

2

num

L03

Refers to Master and Slave  Defrosting
Simultaneous/sequential. Master: n = simul
taneous; y = sequential. Slave: y = accept; n = ignore.

n/y

n

2

Flag

L04

Refers to Slave only. Distributed display. 
n = Slave displays local values; 
y = Slave displays Master display

n/y

y

2

Flag

L05

Activation of Master network functions: n = does
not ask Slaves for activation of remote functions; 
y =asks Slaves for activation of remote functions.
Slave: n = ignores activation of remote functions
from Master; y = accepts activation of remote
functions from Master.

n/y

n

2

Flag

L06

Shuts down resources (compressors, fans, etc) at
end of defrosting. n=no; y=yes

n/y

y

2

Flag

Display - diS label

NOTE:   At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the 

level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.

LOC

Keyboard locked. Parameters can still be pro-
grammed. 
n= keyboard not locked 
y= keyboard locked

n/y

n

1-2

flag

PA1

Contains the password for level 1 parameters. 
Enabled if not 0

0...250

0

1-2

num

PA2

Contains the password for level 2 parameters. 
Enabled if not 0

0...250

0

2

num

ndt

Display with decimal point. 
n= without decimal point (only whole numbers) 
y= with decimal point

n/y

n

1-2

flag

CA1

Temperature value to be added to that read by
probe 1 as specified by parameter CA

-12.0...12.0

0

1-2

°C/°F

CA2

Temperature value to be added to that read by
probe 2 as specified by parameter CA

-12.0...12.0

0

1-2

°C/°F

CA3

Temperature value to be added to that read by
probe 3 as specified by parameter CA

-12.0...12.0

0

1-2

°C/°F

CA

Application of offset 
0 = modifies the temperature displayed 
1 = is added to the temperature used by con-
trollers not the temperature displayed that remains
unchanged. 
2= adds to temperature displayed that is 
also used by controllers.

0/1/2

2

2

num

PTY(9)

Parity bit Modbus
n=none

E=even

o=odd

n/E/o

0

1-2

num

StP(9)

Stop bit Modbus

1b/2b

1b

1-2

flag

Содержание ID 985 E

Страница 1: ...k folder Pb1 probe 1 value folder Pb2 probe 2 value folder Pb3 probe 3 value folder if present Set setting Access the Machine Status menu press the set button and quickly release it The Set folder lab...

Страница 2: ...ing menu in the diS folder If passwords are enabled they will be requested PA1 when entering the Programming menu see the Programming Menu sec tion PA2 in the Cnf folder containing the level 1 paramet...

Страница 3: ...elect dif ferent types of defrosting with the para meter dty defrost type defrost execution mode The dty parameter can have these values 0 electrical defrosting the compressor is turned off 1 cycle re...

Страница 4: ...or dis play probe probe 3 The temperature limits are defined by the HAL maximum alarm LAL minimum alarm and PbA alarm configuration on probe 1 3 or both parameters MAXIMUM AND MINIMUM TEMPERA TURE AL...

Страница 5: ...nputs Serial TTL for Televis or Copy Card con nection Digital outputs 4 outputs on relays first output A SPDT 8 3 A 250Va second and third output B C SPST 8 3 A 250Va fourth output D SPST 5 2 A 250Va...

Страница 6: ...sequent switch ons 0 250 0 1 2 min OdO Delay in enabling outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Type of defrost 0 electrical defrosting 1 cy...

Страница 7: ...e level 1 parameters At level 2 the folders will only display all the level 2 parameters The level marked 1 2 allows the parameter to be displayed at both levels FAd Fan activation intervention differ...

Страница 8: ...ling delay dLt is active n y n 2 flag dAd Delay in enabling digital input 0 255 0 2 min dOd Digital input switches off loads n y n 2 flag Att Determines if LAL and HAL are expressed as absolute values...

Страница 9: ...display n y y 2 Flag L05 Activation of Master network functions n does not ask Slaves for activation of remote functions y asks Slaves for activation of remote functions Slave n ignores activation of...

Страница 10: ...ed set point 3 auxiliary 4 door switch 5 external alarm 6 disables storage of HACCP alarms 7 stand by On Off 8 maintenance request 9 HACCP alarm reset 9 9 0 2 num H08 Stand by operating mode 0 only di...

Страница 11: ...1 2 Copy Card Fpr label UL Transfer of parameter map from instrument to Copy Card dL Transfer of parameter map from Copy Card to instrument 1 1 Fr 8 Formatting Cancels all data in the Copy Card 1 NOT...

Страница 12: ...r Lin set set set set set set set set set set set set set set set set set set set set set set Programming Menu Diagram PARAMETERS level 1 folders CP dEF FAn AL Lit Lin nad Add diS CnF level 2 folders...

Страница 13: ...when the probe temperature is 1 higher than or equal to HAL if Att Ab solute 2 higher than or equal to Set HAL if Att rEl ative if Att Abs olute HAL must be with a sign if Att rEL ative HAL must be on...

Отзывы: