background image

ID 985/E LX

11/13

PAR.

DESCRIPTION

RANGE

DEFAULT

VALUE*

LEVEL**

U.M.

Configuration- CnF label

H24

Digital output 4 configurability Same as H21
(default alarm)

0...10

4

2

num

H25  (7)

BUZZER output configurability 
0= disabled

1...7= not used 

8=enabled (default) if buzzer is present

0...10

8

2

num

H31   

UP button configurability 
0=disabled    1=defrost      2=auxiliary
3=reduced set point       4=HACCP alarm reset
5=disables alarm HACCP  6=light

7=stand-by 

8= maintenance request

H32

DOWN button configurability Same as 
H31(0=disabled default)

0...8

0

2

num

H33

ESC button configurability Same as 
H31(0=disabled default)

0...8

0

2

num

0...8

1

2

num

H40

Enabling inversion of probe 1 and probe 2 
0=Pb1 on channel 1, Pb2 on channel 2 
1=Pb1 on channel 2, Pb2 on channel 1

0...1

0

2

Flag

H41

Presence of control probe: 
n= not present
y= present

n/y

y

2

flag

H42

Presence of evaporator probe: 
n= not present; 
y= present

n/y

y

2

flag

H43

Presence of display probe: 
n= not present

y= present (display probe) 

2EP= probe on 2nd evaporator

n/y/2EP

n

2

flag

H45

Start of defrosting for dual evaporator: 
0= defrost activated if temperature of 1st 
evaporator<dSt 
1= defrosting activated if at least one of the condi-
tions is met:

-temperature 1st evaporator<dSt
-temperature 2nd evaporator<dS2 

2= defrosting activated if both conditions are met:

-temperature 1st evaporator<dSt
-temperature 2nd evaporator<dS2

0/1/2

1

2

num

H48

Presence of RTC 
n= not present;
y= present (Real Time Clock)

n/y

y

2

flag

PA2

in the CnF folder you can access level 2 parameters from label PA2 when you enter the correct password by pressing the
“set” button

reL

Device version. Read only parameter

tAb

Parameter table; Reserved; Read only parameter

/

/

1-2

/

/

/

1-2

/

Copy Card

Fpr label

UL

Transfer of parameter map from instrument to 
Copy Card

dL

Transfer of parameter map from Copy Card to
instrument

/

/

1

/

/

/

1

/

Fr  (8)

Formatting. Cancels all data in the Copy Card

/

/

1

/

NOTES:
(1) See Duty Cycle diagram

(3) If relative values are present (par. Att=1) parameter HAL is set to positive values and the parameter LAL is set to negative values (-LAL)
(4) Refers exclusively to high and low temperature alarms
(5) when changing from °C to °F or vice versa the set points, differentials, etc. are NOT converted (for example, “set=10 °C becomes set=10°F”)
(6) CAUTION: positive or negative values change polarity, Positive values: active input when contact is closed; Negative values: active input when contact is open.
(7) Parameter visible if buzzer is present.
(8) If the Fpr parameter is used, the data previously stored on the Copy Card will be permanently lost. This operation cannot be undone
(9) Only for Modbus models
* Value: to be compiled manually by user with any custom settings (if different from default settings)
** Level: indicates the visibility level of parameters accessed using a password (see relevant paragraph)

(2) In the deF folder there are two folders: “dd” (daily defrost) and “Fd” (festive defrost); the first folder includes the parameters dE1...dE8 (start of daily defrost) and the

second folder includes the parameters F1...F8 (start of festive defrost). The two folders can only be seen if parameter dit=3 and RTC is declared present.

NOTE: Do not confuse the days d0...d6 related to the nAd folder with dE1...dE8 daily defrost.

FUNCTIONS (folder with “FnC” label)The FnC folder (last folder visible from the Programming Menu) contains several functions that are activated using the
“set” button
SEE FUNCTIONS paragraph

PEn

Number of errors allowed per maximum/minimum
pressure switch input

0...15

10

2

num

PEI

Minimum/maximum pressure switch error count
time

1...99

60

2

min

Содержание ID 985 E

Страница 1: ...k folder Pb1 probe 1 value folder Pb2 probe 2 value folder Pb3 probe 3 value folder if present Set setting Access the Machine Status menu press the set button and quickly release it The Set folder lab...

Страница 2: ...ing menu in the diS folder If passwords are enabled they will be requested PA1 when entering the Programming menu see the Programming Menu sec tion PA2 in the Cnf folder containing the level 1 paramet...

Страница 3: ...elect dif ferent types of defrosting with the para meter dty defrost type defrost execution mode The dty parameter can have these values 0 electrical defrosting the compressor is turned off 1 cycle re...

Страница 4: ...or dis play probe probe 3 The temperature limits are defined by the HAL maximum alarm LAL minimum alarm and PbA alarm configuration on probe 1 3 or both parameters MAXIMUM AND MINIMUM TEMPERA TURE AL...

Страница 5: ...nputs Serial TTL for Televis or Copy Card con nection Digital outputs 4 outputs on relays first output A SPDT 8 3 A 250Va second and third output B C SPST 8 3 A 250Va fourth output D SPST 5 2 A 250Va...

Страница 6: ...sequent switch ons 0 250 0 1 2 min OdO Delay in enabling outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Type of defrost 0 electrical defrosting 1 cy...

Страница 7: ...e level 1 parameters At level 2 the folders will only display all the level 2 parameters The level marked 1 2 allows the parameter to be displayed at both levels FAd Fan activation intervention differ...

Страница 8: ...ling delay dLt is active n y n 2 flag dAd Delay in enabling digital input 0 255 0 2 min dOd Digital input switches off loads n y n 2 flag Att Determines if LAL and HAL are expressed as absolute values...

Страница 9: ...display n y y 2 Flag L05 Activation of Master network functions n does not ask Slaves for activation of remote functions y asks Slaves for activation of remote functions Slave n ignores activation of...

Страница 10: ...ed set point 3 auxiliary 4 door switch 5 external alarm 6 disables storage of HACCP alarms 7 stand by On Off 8 maintenance request 9 HACCP alarm reset 9 9 0 2 num H08 Stand by operating mode 0 only di...

Страница 11: ...1 2 Copy Card Fpr label UL Transfer of parameter map from instrument to Copy Card dL Transfer of parameter map from Copy Card to instrument 1 1 Fr 8 Formatting Cancels all data in the Copy Card 1 NOT...

Страница 12: ...r Lin set set set set set set set set set set set set set set set set set set set set set set Programming Menu Diagram PARAMETERS level 1 folders CP dEF FAn AL Lit Lin nad Add diS CnF level 2 folders...

Страница 13: ...when the probe temperature is 1 higher than or equal to HAL if Att Ab solute 2 higher than or equal to Set HAL if Att rEl ative if Att Abs olute HAL must be with a sign if Att rEL ative HAL must be on...

Отзывы: