ID 985/E LX

8/13

PAR.

DESCRIPTION

RANGE

DEFAULT

VALUE*

LEVEL**

U.M.

OAO

High and low temperature alarm delay after dis-
abling digital input (door closed)

0...10

0

2

hours

Alarms-AL label

tdO

Time out after alarm signal when disabling digital
input (door open)

0...250

0

2

min

tAO  (5)

Temperature alarm delay time

0...250

0

1-2

min

dAT

Alarm for defrosting ended due to time out.
n=alarm not active
y=alarm active

n/y

n

2

flag

rLO

Controllers disabled by external alarm 
0=no resources are disabled 
1=disables compressor and defrosting 
2=disables compressor, defrosting and fans

0/1/2

0

2

num

AOP

Polarity of alarm output: 
0 = alarm active and output disabled; 
1 = alarm active and output enabled

0/1

1

2

flag

PbA

Configuration of temperature alarm on probe 1
and/or 3: 
0=on probe 1 (thermostat control) 
1=on probe 3 (display) 
2=on probe 1 and 3 (thermostat control and display) 
3=on probe 1 and 3 (thermostat control and display)
on external threshold 

0/1/2/3

0

2

num

SA3

Probe 3 alarm set point

-50.0...150.0

50

2

°C/°F

dA3

Probe 3 alarm differential

-30.0...30.0

2.0

2

°C/°F

Light & digital inputs

Lit Label

dSd

Light relay enable from door switch. 
n = door open, light does not turn on; 
y = door open, light turns on (if it was off)

n/y

y

2

flag

dLt

Light relay disabling delay after closing door if
“dSd”=y

0...31

0

2

min

OFL

Light relay disabled even if disabling delay 
“dLt” is active

n/y

n

2

flag

dAd

Delay in enabling digital input

0...255

0

2

min

dOd

Digital input switches off loads

n/y

n

2

flag

Att

Determines if “LAL” and “HAL” are expressed as
absolute values or as a differential related to the
set point 
0=absolute value 
1=value related to set point

0/1

0

2

flag

Afd

Alarm differential

1.0...50.0

2.0

1-2

°C/°F

HAL   (4)

Maximum alarm. Temperature limit (whose
absolute or relative value status is regulated by
“Att”) above which the alarm is activated.

LAL...150.0

50.0

1-2

°C/°F

LAL   (4)

Minimum alarm. Temperature limit (whose
absolute or relative value status is regulated by
“Att”) below which the alarm is activated.

-50.0...HAL

-50.0

1-2

°C/°F

PAO  (5)

Alarm exclusion time after start-up of instrument
following a power failure

0...10

0

1-2

hours

dAO

Alarm exclusion time after defrosting

0...999

0

1-2

min

dOA

Forced behaviour from digital input: 
0=no enabling;

1=compressor enabled

2=fans enabled; 
3=compressor and fans enabled

0/1/2/3

0

2

num

PEA

Enables forced behaviour from door light and/or
from external alarm 
0=function disabled;

1=associated with door light

2=associated with external alarm; 
3=associated with door light and external alarm

0/1/2/3

0

2

num

dCO

Delay in enabling compressor with consensus

0...250

0

2

min

dFO

Delay in enabling fans with consensus

0...250

0

2

min

NOTE:   At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the 

level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.

Содержание ID 985 E

Страница 1: ...k folder Pb1 probe 1 value folder Pb2 probe 2 value folder Pb3 probe 3 value folder if present Set setting Access the Machine Status menu press the set button and quickly release it The Set folder lab...

Страница 2: ...ing menu in the diS folder If passwords are enabled they will be requested PA1 when entering the Programming menu see the Programming Menu sec tion PA2 in the Cnf folder containing the level 1 paramet...

Страница 3: ...elect dif ferent types of defrosting with the para meter dty defrost type defrost execution mode The dty parameter can have these values 0 electrical defrosting the compressor is turned off 1 cycle re...

Страница 4: ...or dis play probe probe 3 The temperature limits are defined by the HAL maximum alarm LAL minimum alarm and PbA alarm configuration on probe 1 3 or both parameters MAXIMUM AND MINIMUM TEMPERA TURE AL...

Страница 5: ...nputs Serial TTL for Televis or Copy Card con nection Digital outputs 4 outputs on relays first output A SPDT 8 3 A 250Va second and third output B C SPST 8 3 A 250Va fourth output D SPST 5 2 A 250Va...

Страница 6: ...sequent switch ons 0 250 0 1 2 min OdO Delay in enabling outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Type of defrost 0 electrical defrosting 1 cy...

Страница 7: ...e level 1 parameters At level 2 the folders will only display all the level 2 parameters The level marked 1 2 allows the parameter to be displayed at both levels FAd Fan activation intervention differ...

Страница 8: ...ling delay dLt is active n y n 2 flag dAd Delay in enabling digital input 0 255 0 2 min dOd Digital input switches off loads n y n 2 flag Att Determines if LAL and HAL are expressed as absolute values...

Страница 9: ...display n y y 2 Flag L05 Activation of Master network functions n does not ask Slaves for activation of remote functions y asks Slaves for activation of remote functions Slave n ignores activation of...

Страница 10: ...ed set point 3 auxiliary 4 door switch 5 external alarm 6 disables storage of HACCP alarms 7 stand by On Off 8 maintenance request 9 HACCP alarm reset 9 9 0 2 num H08 Stand by operating mode 0 only di...

Страница 11: ...1 2 Copy Card Fpr label UL Transfer of parameter map from instrument to Copy Card dL Transfer of parameter map from Copy Card to instrument 1 1 Fr 8 Formatting Cancels all data in the Copy Card 1 NOT...

Страница 12: ...r Lin set set set set set set set set set set set set set set set set set set set set set set Programming Menu Diagram PARAMETERS level 1 folders CP dEF FAn AL Lit Lin nad Add diS CnF level 2 folders...

Страница 13: ...when the probe temperature is 1 higher than or equal to HAL if Att Ab solute 2 higher than or equal to Set HAL if Att rEl ative if Att Abs olute HAL must be with a sign if Att rEL ative HAL must be on...

Отзывы: