background image

EWHT800LX  

 

8 - EN

English

band, always positive) and switches off when the value is SEt+db-diF. 

SEt = 20.0°C Cooling SetPoint; db = 2.0°C temperature intervention half-band, always positive

diF = differential = 2.0

COMPRESSOR

Digital output OUT4  is configured as compressor relay. The compressor is active if the cold room 

temperature detected by Pb1 exceeds the value of SP1 + differential diF. The compressor stops if the 

cold room temperature detected by Pb1 falls below the SP1 value. The instrument includes compres-

sor on/off protection*

EVAPORATOR FANS

Digital output OUT5 is configured as evaporator fan relay and is activated in the required cases, ac

-

cording to delays and parameter settings*

Default fan settings

dt = 0 min. drip time; dFd = Y. Fans off during defrosting

LIGHT

Digital output OUT8 is configured as light relay. The light is activated by pressing and holding the 

LIGHT key (G).

Since digital input D.I. 1 is configured as door switch, relay OUT8 (light) is activated when the door is 

opened. The light also switches on with the instrument in standby*.

CONDENSER FANS

Probe Pb4 is configured as NTC condenser fan temperature probe. It is adjusted according to the 

temperature of the probe (see parameter F02=1) in cooling mode (see parameter F01=C). The con

-

denser fan functions independently from the compressor, e.g. the fan is on even if the compressor is 

off (see parameter F16=1)

Note: Analogue output AO is enabled as 0-10V output (F00=4) for piloting an external fan module.*

AUXILIARY (AUX1/2) - ventilation fans

Digital output OUT6 is configured as ventilation fans relay.

The auxiliary output is activated manually by pressing and releasing the AUX1-2 key (H)*

AUXILIARY (AUX1/2) - destratification fans

Digital output OUT7 is configured as destratification fans relay.

The auxiliary output is activated manually by pressing and releasing the AUX1-2 key (H). To prevent 

stratification, e.g. when hot air inside the room rises to the ceiling and cold air falls to the floor, use 

probe Pb3 as a stratification probe, positioning it in accordance with the room probe wiring (one 

near the ceiling, the other near the floor). The fans switch on if Pb1-Pb3 as an absolute value (posi

-

tive value) is greater than the SFd “difference” value and switch off after SFd-diS temperature differ

-

ential.

SFd = 4.0°C difference to be compared with |Pb1-Pb3|

diS = 1.0°C differential

MINIMUM / MAXIMUM PRESSURE SWITCH

Digital input D.I. 3 is configured to manage the minimum pressure switch (low pressure)

Digital input D.I. 4 is configured to manage the maximum pressure switch (high pressure)

Pressure switch setting (default)

PEn = 15. Maximum number of low/high pressure error messages

PEi=99 min. The time interval, in minutes, for counting errors indicated by PEn. If during this interval the 

number of responses from the pressure switch exceeds the indicated threshold, the instrument will report 

a pressure switch error and power to the compressor, defrost and fans will be cut off. See Alarms Table*

*FOR MORE INFORMATION READ the manual, p/n 9MA10024

Содержание Coldface EWHT800LX Series

Страница 1: ...EWHT800LX Controllers for cold rooms and curing rooms for on board installation...

Страница 2: ...downloaded free of charge from the www eliwell it website MECHANICAL INSTALLATION Manual defrost Display HACCP alarms if function active Display alarms if active Functions menu LOC keyboard lock rSE a...

Страница 3: ...3 Heating OUT4 Compressor OUT5 Evaporator fan OUT6 Auxiliary 1 ventilation fans OUT7 Auxiliary 2 destratification fans OUT8 Light Probe inputs default settings Pb1 NTC cold room probe Pb2 NTC defrost...

Страница 4: ...lation FansOFF 2 CONDENSERFANS yellow FansON FansOFF 3 VENTILATIONFANS AUXILIARY1 AUX yellow VENTILATIONFANS AUX1ON VENTILATIONFANS AUX1OFF 4 DESTRATIFICATIONFANS AUXILIARY2 AUX yellow DESTRATIFICATIO...

Страница 5: ...document in the section Parameters Table 1 Press and hold the SET key for 3 seconds until the display shows PAr Lite 2 Press and release the SET key once more The upper display will show the first pa...

Страница 6: ...meter FPt can be either the absolute temperature or the temperature relative to the set point 50 150 6 0 C F Fdt Fan activation delay after a defrosting cycle 0 250 0 min dt Drip time 0 250 0 min dFd...

Страница 7: ...tor probe Pb2 set H42 0 and set relay OUT5 parameter H25 6 STANDBY or 0 DISABLED to prevent con tinuous ventilation DEHUMIDIFICATION Digital output OUT1 is configured as dehumidification relay It swit...

Страница 8: ...is enabled as 0 10V output F00 4 for piloting an external fan module AUXILIARY AUX1 2 ventilation fans Digital output OUT6 is configured as ventilation fans relay The auxiliary output is activated ma...

Страница 9: ...gulation activation of relay AUX1 2 and procedures for completing one STEP and switching to the next By default regulation is disabled and the setpoints are all zero The auxiliary relay is enabled The...

Страница 10: ...54 55 56 57 OUT8 OUT7 OUT6 OUT5 H28 H27 H26 H25 2 3 4 5 10 11 12 13 8 9 AUX 1 AUX 1 RS485 connection to TelevisSystem available with optional plug in module only Copy Card Bus Adapter RS 485 TTL AUX...

Страница 11: ...nlowerdisplay Theupperdisplaywillshowthevalueread bytheroomprobeexceptinthecaseof probeerrors Checkprobetype H45 Checkwiring 2 3 4 5 wireprobe Replaceprobe AL1 Pb1LOWtemperaturealarm valuereadbyPb1 LA...

Страница 12: ...11 H14 DependsondelaysetbyparametertdO RecordingoflabelOPdinfolderALr Regulatorblocked seepara dOA PEA Closedoor Depends on delay set by parameter OAO L01 L15 H01 H15 PEn para meter value default 15 m...

Страница 13: ...0 10V 0 10 55mA minimum load resistance 180 Ohm Digital output Buzzer only on models where this is provided Serials 1TTL port for connection to Copy Card 1TTL port for connection toTelevisSystem 1RS...

Страница 14: ...e 1B controller in terms of software class and structure as a class A device In terms of connection as a device with flexible external and removable cable with Y connection device with pollution grade...

Страница 15: ...one 39 0437 986 111 Facsimile 39 0437 989 066 Sales 39 0437 986 100 Italy 39 0437 986 200 other countries saleseliwell invensyscontrols com Technical helpline 39 0437 986 300 E mail techsuppeliwell in...

Отзывы: