EWHT800LX  

 

6 - EN

English

LITE PARAMETER TABLE

This section describes the most useful parameters, which are contained in the 'Lite' folder. For a description of all User (USr) and Installer (Ins) 
parameters, see the user manual. Note: the 'Lite' folder parameters are NOT divided into subfolders and are always visible (no access password 
is required). The same parameters are also visible in the respective folders 'Compressor', 'Fans', etc. (also indicated here for easy reference) in the 
User (USr) and Installer (Ins) parameters menu.

PARA.

DESCRIPTION

RANGE

DEF. / U.o.M.

SP1

SETPOINT Control value within the range between the minimum set point LSE and the maximum set point HSE.  LSE...HSE

0.0  °C/°F

diF

Compressor relay activation differential; the compressor stops on reaching the set point value (as indicated by the 
regulation probe) and restarts at a temperature value equal to the set point plus the value of the differential. Note: 
the value 0 cannot be set.

0.1...30.0

2.0 °C/°F

HSE

Maximum value that can be assigned to the setpoint.

LSE...302 50.0 °C/°F

LSE

Minimum value that can be assigned to the setpoint. 

-55.0...HSE -50.0 °C/°F 

SPH

Humidity setpoint. Minimum LSH value that can be assigned to the setpoint. Maximum HSH value that can be 
assigned to the setpoint.

LSH...HSH 0.0 %RH

dbH Humidity intervention half-band. Always positive.

0.0...50.0

5.0 %RH

dtY

 Type of defrost.

0= electric defrosting - compressor off (OFF) during defrosting
1 = reverse cycle defrost (hot gas) - compressor ON during defrosting 
2= Free: defrosting independently of compressor 

0/1/2

0

dit

Interval between the start of two subsequent defrosting cycles. 
0= function disabled (defrosting NEVER performed)

0...250

6 h

dEt

Defrost time-out; determines the maximum duration of the defrost cycle. 

1...250

30 min

dSt

Defrost end temperature (determined by the evaporator probe Pb2). 

-50.0...150 6.0 °C/°F

FSt

Fan stop temperature; if the evaporator probe reads a higher value than the set value, the fans are stopped. The 
value is either positive or negative and, depending on parameter FPt, can be either the absolute temperature or 
the temperature relative to the set point.

-50...150

6.0 °C/°F

Fdt

Fan activation delay after a defrosting cycle.

0...250

0 min

dt

Drip time.

0...250

0 min

dFd

Allows exclusion of the evaporator fans to be selected or not selected during defrosting. y = yes; n = no.

n/y

y

F09

Minimum setpoint for condenser fan speed.

-50.0...99.9 30.0 °C/bar

SFd

Temperature difference for destratification fans. If the difference |Pb1-Pb3| as an absolute value (positive number) 
is greater than SFd, the destratification fans are started. They switch off when |Pb1-Pb3| is less than SFd -diS 

(destratification fans differential)

0...99.9

4.0 °C/°F

HAL

Maximum temperature alarm. Temperature value (intended either as distance from set point or as an absolute 
value based on Att) which, if exceeded in an upward direction, triggers the activation of the alarm signal.

LAL...150 50.0 °C/°F

LAL

Low temperature alarm. Temperature value (intended as distance from the set point or as an absolute value based 
on Att) which, when exceeded downwards, triggers the activation of the alarm signal. 

-50.0...HAL -50.0 °C/°F

dAO

Temperature alarm exclusion time after defrost.

0...999

60 min

tAO

Time delay for temperature alarm indication. Refers to high/low temperature alarms only.

0...250

0 min

CA1
CA2
CA3
CA4

Calibration 1/2/3/4.
Positive or negative temperature value added to the value read by probe Pb1/2/3/4, according to the setting of 
parameter “CA”.

-12.0...12.0 0 °C/°F

ddL

Display mode during defrost.
0 = displays the temperature read by the room probe Pb1;
1 = locks the reading at the temperature value read by room probe Pb1 when defrosting starts and until the next 

time the set point value is reached;

2 = displays the label “deF” during defrosting and until the next time the set point value is reached (or until Ldd 
has elapsed).

0/1/2

1

CONFIGURATION 

NOTE: the instrument must be switched off and restarted each time these parameters are modified.

H00

Probe type selection, PTC/NTC. 0 = PTC; 1 = NTC.

0/1

1

H09

Type of dehumidification. 0= with dehumidification relay; 1= with dehumidification relay + compressor; 2= 

without dehumidification relay; 

0/1/2

0

H42

Pb2 Evaporator probe presence. 0 = not present; 1 = present.

0/1

1

Содержание Coldface EWHT800LX Series

Страница 1: ...EWHT800LX Controllers for cold rooms and curing rooms for on board installation...

Страница 2: ...downloaded free of charge from the www eliwell it website MECHANICAL INSTALLATION Manual defrost Display HACCP alarms if function active Display alarms if active Functions menu LOC keyboard lock rSE a...

Страница 3: ...3 Heating OUT4 Compressor OUT5 Evaporator fan OUT6 Auxiliary 1 ventilation fans OUT7 Auxiliary 2 destratification fans OUT8 Light Probe inputs default settings Pb1 NTC cold room probe Pb2 NTC defrost...

Страница 4: ...lation FansOFF 2 CONDENSERFANS yellow FansON FansOFF 3 VENTILATIONFANS AUXILIARY1 AUX yellow VENTILATIONFANS AUX1ON VENTILATIONFANS AUX1OFF 4 DESTRATIFICATIONFANS AUXILIARY2 AUX yellow DESTRATIFICATIO...

Страница 5: ...document in the section Parameters Table 1 Press and hold the SET key for 3 seconds until the display shows PAr Lite 2 Press and release the SET key once more The upper display will show the first pa...

Страница 6: ...meter FPt can be either the absolute temperature or the temperature relative to the set point 50 150 6 0 C F Fdt Fan activation delay after a defrosting cycle 0 250 0 min dt Drip time 0 250 0 min dFd...

Страница 7: ...tor probe Pb2 set H42 0 and set relay OUT5 parameter H25 6 STANDBY or 0 DISABLED to prevent con tinuous ventilation DEHUMIDIFICATION Digital output OUT1 is configured as dehumidification relay It swit...

Страница 8: ...is enabled as 0 10V output F00 4 for piloting an external fan module AUXILIARY AUX1 2 ventilation fans Digital output OUT6 is configured as ventilation fans relay The auxiliary output is activated ma...

Страница 9: ...gulation activation of relay AUX1 2 and procedures for completing one STEP and switching to the next By default regulation is disabled and the setpoints are all zero The auxiliary relay is enabled The...

Страница 10: ...54 55 56 57 OUT8 OUT7 OUT6 OUT5 H28 H27 H26 H25 2 3 4 5 10 11 12 13 8 9 AUX 1 AUX 1 RS485 connection to TelevisSystem available with optional plug in module only Copy Card Bus Adapter RS 485 TTL AUX...

Страница 11: ...nlowerdisplay Theupperdisplaywillshowthevalueread bytheroomprobeexceptinthecaseof probeerrors Checkprobetype H45 Checkwiring 2 3 4 5 wireprobe Replaceprobe AL1 Pb1LOWtemperaturealarm valuereadbyPb1 LA...

Страница 12: ...11 H14 DependsondelaysetbyparametertdO RecordingoflabelOPdinfolderALr Regulatorblocked seepara dOA PEA Closedoor Depends on delay set by parameter OAO L01 L15 H01 H15 PEn para meter value default 15 m...

Страница 13: ...0 10V 0 10 55mA minimum load resistance 180 Ohm Digital output Buzzer only on models where this is provided Serials 1TTL port for connection to Copy Card 1TTL port for connection toTelevisSystem 1RS...

Страница 14: ...e 1B controller in terms of software class and structure as a class A device In terms of connection as a device with flexible external and removable cable with Y connection device with pollution grade...

Страница 15: ...one 39 0437 986 111 Facsimile 39 0437 989 066 Sales 39 0437 986 100 Italy 39 0437 986 200 other countries saleseliwell invensyscontrols com Technical helpline 39 0437 986 300 E mail techsuppeliwell in...

Отзывы: