EWHT800LX
10 - EN
English
EWHT800LX can be connected to:
• telecontrol system TelevisSystem (°)
• third-party systems via Modbus protocol (°°)
• Param
Manager fast parameter setting software
The connection can be made in 2 ways:
1) via TTL serial port. See Electrical Connections.
Use the BusAdapter150 TTL- RS 485 interface module
2) by direct RS-485 connection using the optional RS485/TTL plug-
in module (not included).
See figure opposite.
In both cases, use a RS485/RS232-USB PC interface
converter and
the required software licence.
(°) To configure the instrument for this purpose, open the file identified by the label "Add" and use
parameters "dEA" and "FAA*
(°°) To configure the instrument for this purpose, open the file identified by the label “Add” and use
parameters "dEA", "FAA", "PtY"*
*FOR MORE INFORMATION READ the manual, p/n 9MA10024
SUPERVISION
+
-
+12V
I
I (4...20mA)
Pb5
Pb5
51 52 53
GND
Analogue
Output - AO
Analogue
Output - AO
39 40 41
0...20mA
4..20mA
GND
39 40 41
0...10V PWM
10V 55mA
485+
GND
485-
RS-485
RS-485
Keyboard
Copy Card
EWHT800 LX
14 15 16
Pb3
Pb4
Pb2
Pb1
DI4
DI3
DI2
DI1
Power
Supply
100...240V
17 18 19 20 21 22 23 24
31 32
39 40 41 45 46 47 51 52 53
Analogue
Output - AO
Pb5
TTL
25 26
27
28
29
30
64 65
66
67 68 69
70
71
54 55 56 57 59 60 61 62
Removable
Terminals
OUT8
OUT7
OUT6
OUT5
OUT4
OUT3 OUT2 OUT1
H28
H27
H26
H25
H24
H23
H22
H21
Relais
Parameters
Default configuration
LINE
NEUTRAL
Faston
2 3 4 5
10
11
12
13
8 9
AUX 1
AUX 1
RS485 connection to
Televis
System
available
with optional plug-in
module only
Copy
Card
Bus
Adapter
RS 485
TTL
AUX 2
AUX 2
+
+
-
-
ALARMS AND TROUBLESHOOTING
How to display the alarms
1) Press and release the UP key. The upper display will always show the label ALr. The lower display
will show:
• nOnE if no alarms active
• SYS to indicate system alarms - see Alarms Table
• HACP to indicate HACCP alarms - see HACCP alarms
2) Using the UP & DOWN keys, find the type of alarm that you want to check
System alarms
The upper display will show the label ALr, the lower display will indicate the alarm code
- see Alarms Table
• Using the UP & DOWN key, scroll the other alarms
• Press the ESC key to return to the previous alarm code, press the ESC key several times (or keep it
pressed) to return to the normal display
HACCP ALARMS
The instrument logs high and low temperature alarms for the cold room probe, as well as any power
failures. The alarm types and the duration and start time of the alarm itself will be displayed in the
alarms folder ALr. It is possible to disable the recording of alarms and/or resetting of HACCP alarms.
See Functions Menu.
FOR MORE INFORMATION READ the manual, p/n 9MA10024