background image

7 - EN

EWHT800LX

English

THE INSTRUMENT ENABLES MODIFICATION OF OTHER PARAMETERS DIVIDED INTO USER 

LEVEL (USr) and INSTALLER LEVEL (InS) 

How to modify other parameters

Installer (InS) level access - User level access is similar:

Procedure applies only to more advanced applications. In this case the parameters are arranged in 

folders (Compressor / Defrost / Fans etc)

1)  Press and hold the SET key for 3 seconds until the display shows PAr / Lite

2)  Use the UP & DOWN keys to select the parameter level concerned (Usr or Ins)

3)  Press and release the SET key once more. The display will show the first folder

4)  Press and release the SET key once more. The upper display will show the first parameter in the 

folder, the lower display will indicate the current parameter value

5)  Using the UP & DOWN keys, find the parameter that you wish to modify

6)  Press and release the SET key once more. The upper display will show the name of the blinking 

parameter

7)  Use the UP & DOWN keys to adjust the parameter value

8)  Press and release SET to save the parameter value

9)  Return to step 5) or press ESC several times to return to the normal display

OPERATION IN DEFAULT CONFIGURATION

The instrument is configured for negative cold. For positive cold, disable the evaporator probe Pb2 

(set H42=0) and set relay OUT5 (parameter H25) = 6 (STANDBY) or 0 (DISABLED) to prevent con

-

tinuous ventilation.

DEHUMIDIFICATION

Digital output OUT1 is configured as dehumidification relay. It switches on if the relative humidity is 

greater than the Humidity Setpoint SPH + dbH (intervention half-band, always positive) and switches 

off when the value is SPH. Dehumidification is activated by relay (H09=0).

SPH = 20.0°C Humidity Setpoint

dbH = 5.0°C intervention half-band, always positive

dFH = differential = 0 => dFH = dbH

HUMIDIFICATION

Digital output OUT2 is configured as humidification relay. It switches on if the relative humidity is 

less than the Humidity Setpoint SPH - dbH (intervention half-band, always positive) and switches off 

when the value is SPH. Humidification is disabled during defrost (dEH=0).

NOTE:

• Humidification and dehumidification are in Neutral Zone mode (H05=nE)

• Humidification and dehumidification are disabled during defrost (dEH=0)

HEATING

Digital output OUT3 is configured as heating relay. It is activated in Neutral Zone mode (H07=1).

Heating mode:

It switches on if the temperature is less than the Heating Setpoint StH - db (intervention half-band, 

always positive) and switches off when the value is StH.

StH = 0.0°C Heating Setpoint

db = 2.0°C temperature intervention half-band, always positive

diH = differential = 0 diH = db

Cooling mode:

It switches on if the temperature is greater than the Cooling SetPoint SEt + db (intervention half-

Содержание Coldface EWHT800LX Series

Страница 1: ...EWHT800LX Controllers for cold rooms and curing rooms for on board installation...

Страница 2: ...downloaded free of charge from the www eliwell it website MECHANICAL INSTALLATION Manual defrost Display HACCP alarms if function active Display alarms if active Functions menu LOC keyboard lock rSE a...

Страница 3: ...3 Heating OUT4 Compressor OUT5 Evaporator fan OUT6 Auxiliary 1 ventilation fans OUT7 Auxiliary 2 destratification fans OUT8 Light Probe inputs default settings Pb1 NTC cold room probe Pb2 NTC defrost...

Страница 4: ...lation FansOFF 2 CONDENSERFANS yellow FansON FansOFF 3 VENTILATIONFANS AUXILIARY1 AUX yellow VENTILATIONFANS AUX1ON VENTILATIONFANS AUX1OFF 4 DESTRATIFICATIONFANS AUXILIARY2 AUX yellow DESTRATIFICATIO...

Страница 5: ...document in the section Parameters Table 1 Press and hold the SET key for 3 seconds until the display shows PAr Lite 2 Press and release the SET key once more The upper display will show the first pa...

Страница 6: ...meter FPt can be either the absolute temperature or the temperature relative to the set point 50 150 6 0 C F Fdt Fan activation delay after a defrosting cycle 0 250 0 min dt Drip time 0 250 0 min dFd...

Страница 7: ...tor probe Pb2 set H42 0 and set relay OUT5 parameter H25 6 STANDBY or 0 DISABLED to prevent con tinuous ventilation DEHUMIDIFICATION Digital output OUT1 is configured as dehumidification relay It swit...

Страница 8: ...is enabled as 0 10V output F00 4 for piloting an external fan module AUXILIARY AUX1 2 ventilation fans Digital output OUT6 is configured as ventilation fans relay The auxiliary output is activated ma...

Страница 9: ...gulation activation of relay AUX1 2 and procedures for completing one STEP and switching to the next By default regulation is disabled and the setpoints are all zero The auxiliary relay is enabled The...

Страница 10: ...54 55 56 57 OUT8 OUT7 OUT6 OUT5 H28 H27 H26 H25 2 3 4 5 10 11 12 13 8 9 AUX 1 AUX 1 RS485 connection to TelevisSystem available with optional plug in module only Copy Card Bus Adapter RS 485 TTL AUX...

Страница 11: ...nlowerdisplay Theupperdisplaywillshowthevalueread bytheroomprobeexceptinthecaseof probeerrors Checkprobetype H45 Checkwiring 2 3 4 5 wireprobe Replaceprobe AL1 Pb1LOWtemperaturealarm valuereadbyPb1 LA...

Страница 12: ...11 H14 DependsondelaysetbyparametertdO RecordingoflabelOPdinfolderALr Regulatorblocked seepara dOA PEA Closedoor Depends on delay set by parameter OAO L01 L15 H01 H15 PEn para meter value default 15 m...

Страница 13: ...0 10V 0 10 55mA minimum load resistance 180 Ohm Digital output Buzzer only on models where this is provided Serials 1TTL port for connection to Copy Card 1TTL port for connection toTelevisSystem 1RS...

Страница 14: ...e 1B controller in terms of software class and structure as a class A device In terms of connection as a device with flexible external and removable cable with Y connection device with pollution grade...

Страница 15: ...one 39 0437 986 111 Facsimile 39 0437 989 066 Sales 39 0437 986 100 Italy 39 0437 986 200 other countries saleseliwell invensyscontrols com Technical helpline 39 0437 986 300 E mail techsuppeliwell in...

Отзывы: