3.2 Wire Gauge Selection
The following guidelines assist in determining the optimum cable specification for
your power applications. These guidelines are equally applicable to both DC and low
frequency AC (up to 450 Hz) power cabling. The same engineering rules apply whether
going into or out of an electrical device. Thus, this guide applies equally to the input
cable and output cable for this Elgar instrument and application loads.
Power cables must be able to safely carry maximum load current without overheating or
causing insulation destruction. It is important to everyday performance to minimize IR
(voltage drop) loss within the cable. These losses have a direct effect on the quality of
power delivered to and from instruments and corresponding loads.
When specifying wire gauge, the operating temperature needs to be considered. Wire
gauge current capability and insulation performance drops with the increased
temperature developed within a cable bundle and with increased environmental
temperature. Thus, short cables with generously derated gauge and insulation
properties are recommended for power source applications.
Avoid using published commercial utility wiring codes, which are designed for the
internal wiring of homes and buildings. Although these codes accommodate the safety
factors of wiring loss, heat, breakdown insulation, aging, etc., they consider that up to
5% voltage drop is acceptable. Such a loss directly detracts from the quality
performance specifications of this Elgar instrument. Frequently, these codes do not
consider bundles of wire within a cable arrangement.
In high performance applications, as in motor start-up and associated inrush/ transient
currents, additional consideration is required. The cable wire gauge must consider peak
voltages and currents that may be up to ten times the average values. An underrated
wire gauge adds losses that alter the inrush characteristics of the application and thus
the expected performance.
Table 3–1 identifies popular ratings for DC and AC power source cable wire gauges.
Column 1
Size (AWG)
Column 2
Amperes (Max)
Column 3
Ohms/100 ft (1 way)
Column 4
IR Drop/100 ft (Col 2 x Col 3)
14 15
0.257
3.85
12 20
0.162
3.24
10 30
0.102
3.06
8 40 0.064
2.56
6 55 0.043
2.36
4 70 0.025
1.75
2 95 0.015
1.42
1/0 125
0.010
1.25
3/0 165
0.006
1.04
Table 3–1 Recommended Wire Gauge Selection Guide
10
Содержание CW 1251M
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ...ii This page intentionally left blank...
Страница 12: ...Elgar CW M Series This page intentionally left blank 2...
Страница 24: ...Elgar CW M Series Figure 3 2 Mounting Dimensions Front and Rear Views CW 801M CW 1251M 14...
Страница 25: ...Elgar CW M Series Figure 3 3 Mounting Dimensions Front and Rear Views CW 2501M 15...
Страница 26: ...Elgar CW M Series Figure 3 4 Mounting Dimensions Top and Side Views CW 801M CW 1251M 16...
Страница 27: ...Elgar CW M Series Figure 3 5 Mounting Dimensions Top and Side Views CW 2501M 17...
Страница 34: ...Elgar CW M Series This page intentionally left blank 24...
Страница 38: ...Elgar CW M Series 4 3 2 Setup for Six in Parallel Configuration 28...
Страница 39: ...Elgar CW M Series 4 3 3 Setup for Six Phase Configuration 29...
Страница 40: ...Elgar CW M Series 4 3 4 Setup for Two Phase Configuration 30...
Страница 42: ...Elgar CW M Series This page intentionally left blank 32...
Страница 48: ...Elgar CW M Series This page intentionally left blank 38...