Elgar CW-M Series
To utilize remote sensing at the user's load, follow these steps:
1. Remove the protective cover from the terminal block.
2. Route the cables through the strain relief device located above the terminal block.
Twisted shielded leads for power and sense leads are recommended for the lowest
noise operation. If used, shields should be connected to a CW output terminal block
GND ground connector, as shown in Figure 3–9.
3. Disconnect local–sense shorting jumpers. See Figure 3–9.
4. Connect the sense leads as shown in Figure 3–9.
5. Reinstall the protective cover on the terminal block.
Figure 3–9 Sense Connections
22
Содержание CW 1251M
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ...ii This page intentionally left blank...
Страница 12: ...Elgar CW M Series This page intentionally left blank 2...
Страница 24: ...Elgar CW M Series Figure 3 2 Mounting Dimensions Front and Rear Views CW 801M CW 1251M 14...
Страница 25: ...Elgar CW M Series Figure 3 3 Mounting Dimensions Front and Rear Views CW 2501M 15...
Страница 26: ...Elgar CW M Series Figure 3 4 Mounting Dimensions Top and Side Views CW 801M CW 1251M 16...
Страница 27: ...Elgar CW M Series Figure 3 5 Mounting Dimensions Top and Side Views CW 2501M 17...
Страница 34: ...Elgar CW M Series This page intentionally left blank 24...
Страница 38: ...Elgar CW M Series 4 3 2 Setup for Six in Parallel Configuration 28...
Страница 39: ...Elgar CW M Series 4 3 3 Setup for Six Phase Configuration 29...
Страница 40: ...Elgar CW M Series 4 3 4 Setup for Two Phase Configuration 30...
Страница 42: ...Elgar CW M Series This page intentionally left blank 32...
Страница 48: ...Elgar CW M Series This page intentionally left blank 38...