background image

ELEKTROGAS – TECHNICAL MANUAL 

 4-12 

 

 

 

Special versions 
and optionals 

The sizes 1”¼, 1”½ and 2” can be provided with G1/4 gauges also in the outlet chamber. 

A closed position indicator micro-switch (CPI) can be installed. Models from DN65 to DN200 are 
provided with G1/8 connection on the bottom for these facilities -on request from 3/4" to 2" - (not 
available for 6 bar versions and brass models). To install the micro-switch the adapting kit must 
be required. 

The  threaded  models  Rp11/2  and  Rp2  can  be  provided  with  flanged  connections  using  an 
optional kit. 

Whole  range  can  be  provided  with  Ex-proof  marking  for  use  in  Zone  2,  according  to  94/9/EC 
Directive (ATEX). 

 

 

Technical 
specifications 

 

Tab. 1 

Connections 

Gas threaded ISO 7/1 from Rp3/8 to Rp2 
Flanged PN16 – ISO 7005 from DN40 to DN200 

 

 

Voltage rating 

230 VAC 50/60 Hz 
110 VAC 50/60 Hz 

24 VAC; 24 VDC 

12 VDC 

 

 

Voltage tolerance 

-15% / +10% 

 

 

Power consumption 

see charts 

 

 

Ambient temperature 

-15°C / +60°C 

 

 

Max. operating pressure 

600 mbar  (60 kPa) 
6 bar  (600 kPa) 

 

 

Flow capacity 

see charts 

 

 

Closing time 

< 1 second 

 

 

Filter (except brass models) 

600 µm, metal mesh 

 

 

Protection class 

IP54 (EN 60529) 

 

 

Cable gland 

PG 9 

 

 

Coil winding insulation 

Class H (200°C) 

 

 

Coil thermal resistance  

Class F (155°C) 

 

 

Materials in contact with gas 

Aluminium alloy 
Brass 
Stainless steel 
Plated steel 
Anaerobic adhesive 
Nitrile rubber (NBR) 
Polytetrafluoroethylene (PTFE) 

 
 
 
 
 
 
 
 
 
 
 

Содержание EVRM-6NA

Страница 1: ...elektrogas com EVRM NA EVRM 6NA Safety solenoid valves for gas Manual reset Normally open DN10 DN200 EE167 0510...

Страница 2: ...ed in the 1 2 and 3 families EN 437 Two range of operating pressure low pressure 0 600 mbar and medium pressure 0 6 bar The valves are normally not powered allowing a remarkable energy saving An incor...

Страница 3: ...f the presence of gas the valve remains under power and does not allow reset When the causes for locking have been eliminated valve must be opened manually Fig 1 The 6NA versions are provided with a d...

Страница 4: ...th Ex proof marking for use in Zone 2 according to 94 9 EC Directive ATEX Technical specifications Tab 1 Connections Gas threaded ISO 7 1 from Rp3 8 to Rp2 Flanged PN16 ISO 7005 from DN40 to DN200 Vol...

Страница 5: ...6 9 5 85 96 138 165 0 8 Rp 1 16 12 0 85 96 138 165 0 8 Rp 11 4 16 20 0 120 153 170 203 1 6 Rp 11 2 16 26 0 120 153 170 203 1 6 Rp 2 16 40 0 106 156 175 213 1 9 DN 40 1 16 26 0 150 193 170 245 110 4x18...

Страница 6: ...AIR GAS V k V Gas flow chart Pressure drop Fig 4 Formula of conversion from air to other gases Tab 3 15 C 1013 mbar dry Gas type Specific gravity Kg m GAS k 25 1 Air 1 25 1 00 Natural gas 0 80 1 25 T...

Страница 7: ...ce with the characteristic Kvs value which is shown in table 2 The selection of the valve requires the calculation of the Kv under the operating conditions Considering only subcritical pressure drops...

Страница 8: ...6F DN 50 1 B C GW H HW 110 VAC 24 VDC 12 VDC EVRMNA7 EVRM6NA7 DN 65 EVRMNA8 EVRM6NA8 DN 80 EVRMNA9 EVRM6NA9 DN 100 EVRMNA93 EVRM6NA93 DN 125 EVRMNA95 EVRM6NA95 DN 150 EVRMNA98 DN 200 B _ G H _ 1 Optio...

Страница 9: ...EC and the certification has been issued by the notified body C S I Spa Viale Lombardia 20 I 20021 Bollate MI The following standards technical specifications have been fulfilled Electromagnetic Compa...

Страница 10: ...move the end caps and make sure no foreign body is entered into the valve during handling THREADED MODELS Put sealing agent onto the pipe thread Avoid excessive quantities which could enter in the val...

Страница 11: ...cording to printed designation Pull back the cable and insert the terminal block into the housing Screw back the gland nut make sure that the grommet is locked on the cable Insert the screw and gasket...

Страница 12: ...ing If necessary replace them Remove the spring and blow it with compressed air Check the spring is corrosion free Clean the disc assembly with a clean cloth and compressed air Grease the rod O ring C...