ELEKTROGAS – TECHNICAL MANUAL 

 12-12 

 

 

INTERNAL INSPECTION 

If the valve does not work properly, do not dismount the resetting mechanism, but replace it with 
a new one. 

THREADED MODELS 

Shut ball valve upstream the system and make sure no pressure is inside the valve. 

Reset the valve (valve open). 

Unscrew  the  knob,  but  do  not  remove  the  nut  below.    This  is  to  avoid  the  accidental 
dismounting of the resetting mechanism.  

Remove the locking nut and the coil. 

Using an Allen key, remove the screws on the upper flange, in cross way. The gas in the 
valve will come out during this step. 

Check the main O-ring. If necessary, replace it. 

Blow the spring with compressed air and check it is corrosion free. 

Check the conditions of the sealing gasket. If gasket is deteriorated, replace it with a new 
one. 

Clean  the  sealing  lip  with  a  clean  cloth.  Do  not  use  tools,  because  a  lip  damage  could 
result. 

Remove the filter and blow it with compressed air. 

Reassemble the valve following the inverse sequence. 

 
FLANGED MODELS 

Shut ball valve upstream the system and make sure no pressure is inside the valve. 

Unscrew the knob. 

Using an Allen key, remove the screws on the upper flange, in cross way. The gas in the 
valve will come out during this step. 

Check the main O-ring and the rod O-ring. If necessary, replace them. 

Remove the spring and blow it with compressed air. Check the spring is corrosion free. 

Clean the disc assembly with a clean cloth and compressed air. Grease the rod O-ring. 

Check the conditions of the sealing gasket. If gasket is deteriorated, replace it with a new 
one. 

Clean  the  sealing  lip  with  a  clean  cloth.  Do  not  use  tools,  because  a  lip  damage  could 
result. 

Remove the filter and blow it with compressed air. 

Reassemble the valve following the inverse sequence. 

To insert the rod inside the flange assembly, power the coil and, using a screw driver, move the 
pin to allow the rod inserting. 

 

When the reassembly is completed, check the proper sealing between the upper flange and the 
valve body: 

Open ball valve to restore pressure into the valve. 

Apply  a  soap  solution  between  the  upper  flange  and  the  valve  body  and  check  for 
leakages. 

Remove the soap solution with a clean cloth and compressed air. 

 

WARNING 

To prevent product damage and dangerous situations, read the Installation and Service 
Instructions carefully. 

Turn off all power before servicing any part of the system. 

Make sure that the resetting rod is always free to move and no impediment hinders the 
valve closing. 

Perform leak and functional tests after mounting (max. testing pressure 1,5 Pmax). 

Use all gaskets properly (void warranty). 

All wiring must be in compliance with local and national codes. 

Make sure all works are performed by qualified technicians only. 
 

 

Содержание EVRM-6NA

Страница 1: ...elektrogas com EVRM NA EVRM 6NA Safety solenoid valves for gas Manual reset Normally open DN10 DN200 EE167 0510...

Страница 2: ...ed in the 1 2 and 3 families EN 437 Two range of operating pressure low pressure 0 600 mbar and medium pressure 0 6 bar The valves are normally not powered allowing a remarkable energy saving An incor...

Страница 3: ...f the presence of gas the valve remains under power and does not allow reset When the causes for locking have been eliminated valve must be opened manually Fig 1 The 6NA versions are provided with a d...

Страница 4: ...th Ex proof marking for use in Zone 2 according to 94 9 EC Directive ATEX Technical specifications Tab 1 Connections Gas threaded ISO 7 1 from Rp3 8 to Rp2 Flanged PN16 ISO 7005 from DN40 to DN200 Vol...

Страница 5: ...6 9 5 85 96 138 165 0 8 Rp 1 16 12 0 85 96 138 165 0 8 Rp 11 4 16 20 0 120 153 170 203 1 6 Rp 11 2 16 26 0 120 153 170 203 1 6 Rp 2 16 40 0 106 156 175 213 1 9 DN 40 1 16 26 0 150 193 170 245 110 4x18...

Страница 6: ...AIR GAS V k V Gas flow chart Pressure drop Fig 4 Formula of conversion from air to other gases Tab 3 15 C 1013 mbar dry Gas type Specific gravity Kg m GAS k 25 1 Air 1 25 1 00 Natural gas 0 80 1 25 T...

Страница 7: ...ce with the characteristic Kvs value which is shown in table 2 The selection of the valve requires the calculation of the Kv under the operating conditions Considering only subcritical pressure drops...

Страница 8: ...6F DN 50 1 B C GW H HW 110 VAC 24 VDC 12 VDC EVRMNA7 EVRM6NA7 DN 65 EVRMNA8 EVRM6NA8 DN 80 EVRMNA9 EVRM6NA9 DN 100 EVRMNA93 EVRM6NA93 DN 125 EVRMNA95 EVRM6NA95 DN 150 EVRMNA98 DN 200 B _ G H _ 1 Optio...

Страница 9: ...EC and the certification has been issued by the notified body C S I Spa Viale Lombardia 20 I 20021 Bollate MI The following standards technical specifications have been fulfilled Electromagnetic Compa...

Страница 10: ...move the end caps and make sure no foreign body is entered into the valve during handling THREADED MODELS Put sealing agent onto the pipe thread Avoid excessive quantities which could enter in the val...

Страница 11: ...cording to printed designation Pull back the cable and insert the terminal block into the housing Screw back the gland nut make sure that the grommet is locked on the cable Insert the screw and gasket...

Страница 12: ...ing If necessary replace them Remove the spring and blow it with compressed air Check the spring is corrosion free Clean the disc assembly with a clean cloth and compressed air Grease the rod O ring C...

Отзывы: