ELEKTROGAS – TECHNICAL MANUAL 

 3-12 

 

 

 

Functioning and 

  

application

 

The EVRM-NA /6NA type valve is a manual reset safety valve that is normally open. A manual 
operation  is  therefore  necessary  to  open  the  valve  and  to  reset  the  mechanism  consenting  to 
maintain this state. The powering by means of line current and/or condenser discharge, induced 
by  the  leakage  detector,  safety  thermostat  or  alarm  system  causes  driving  of  the  mechanism 
and  consequent  closing  of  the  gas  orifice.  If  energizing  of  the  sensor  persists  because  of  the 
presence of gas, the valve remains under power and does not allow reset. When the causes for 
locking have been eliminated, valve must be opened manually. 

 

              

Fig.1 

 

The /6NA versions are provided with a dual-shutter system for pressure compensation. To open 
the valve pull the knob for the first step, wait for pressure compensation, and then pull the knob 
completely up to full resetting (from 3/4" to 6”). 
 

This  kind  of  device  is  normally  installed  downstream  a manual  shut-off  valve  and  upstream  of 
the gas regulating train. Figure 2 shows a example of installation. 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig.2 

WARNING 

Location and mode of installation must be in compliance with local rules in force. 
 

Gas 
detector 

Solenoid valve 

manual reset 

Gas 

network 

Consumer 

Содержание EVRM-6NA

Страница 1: ...elektrogas com EVRM NA EVRM 6NA Safety solenoid valves for gas Manual reset Normally open DN10 DN200 EE167 0510...

Страница 2: ...ed in the 1 2 and 3 families EN 437 Two range of operating pressure low pressure 0 600 mbar and medium pressure 0 6 bar The valves are normally not powered allowing a remarkable energy saving An incor...

Страница 3: ...f the presence of gas the valve remains under power and does not allow reset When the causes for locking have been eliminated valve must be opened manually Fig 1 The 6NA versions are provided with a d...

Страница 4: ...th Ex proof marking for use in Zone 2 according to 94 9 EC Directive ATEX Technical specifications Tab 1 Connections Gas threaded ISO 7 1 from Rp3 8 to Rp2 Flanged PN16 ISO 7005 from DN40 to DN200 Vol...

Страница 5: ...6 9 5 85 96 138 165 0 8 Rp 1 16 12 0 85 96 138 165 0 8 Rp 11 4 16 20 0 120 153 170 203 1 6 Rp 11 2 16 26 0 120 153 170 203 1 6 Rp 2 16 40 0 106 156 175 213 1 9 DN 40 1 16 26 0 150 193 170 245 110 4x18...

Страница 6: ...AIR GAS V k V Gas flow chart Pressure drop Fig 4 Formula of conversion from air to other gases Tab 3 15 C 1013 mbar dry Gas type Specific gravity Kg m GAS k 25 1 Air 1 25 1 00 Natural gas 0 80 1 25 T...

Страница 7: ...ce with the characteristic Kvs value which is shown in table 2 The selection of the valve requires the calculation of the Kv under the operating conditions Considering only subcritical pressure drops...

Страница 8: ...6F DN 50 1 B C GW H HW 110 VAC 24 VDC 12 VDC EVRMNA7 EVRM6NA7 DN 65 EVRMNA8 EVRM6NA8 DN 80 EVRMNA9 EVRM6NA9 DN 100 EVRMNA93 EVRM6NA93 DN 125 EVRMNA95 EVRM6NA95 DN 150 EVRMNA98 DN 200 B _ G H _ 1 Optio...

Страница 9: ...EC and the certification has been issued by the notified body C S I Spa Viale Lombardia 20 I 20021 Bollate MI The following standards technical specifications have been fulfilled Electromagnetic Compa...

Страница 10: ...move the end caps and make sure no foreign body is entered into the valve during handling THREADED MODELS Put sealing agent onto the pipe thread Avoid excessive quantities which could enter in the val...

Страница 11: ...cording to printed designation Pull back the cable and insert the terminal block into the housing Screw back the gland nut make sure that the grommet is locked on the cable Insert the screw and gasket...

Страница 12: ...ing If necessary replace them Remove the spring and blow it with compressed air Check the spring is corrosion free Clean the disc assembly with a clean cloth and compressed air Grease the rod O ring C...

Отзывы: