Page 55
EA Elektro-Automatik GmbH
Helmholtzstr. 31-37 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
www.elektroautomatik.de
PSB 9000 3U Series
IF Ebene 1
Level 2
Level 3
Description
CAN
Base ID
Setup of the CAN base ID (11 Bit or 29 Bit, hex format). Default:
0h
Baud Rate
Setup of the CAN bus speed or baud rate in typical value be-
tween 10 kbps and 1Mbps. Default:
500 kbps
Termination
Activates or deactivates CAN bus termination with a built-in resis-
tor. Default:
OFF
Broadcast ID
Setup of the CAN broadcast ID (11 Bit or 29 Bit, hex format). De-
fault:
7ffh
ID Format
Selection of the CAN ID format between
Base
(11 Bit ID, 0h...7ffh)
and
Extended
(29 Bit, 0h...1fffffffh)
Cyclic
Communication
Base ID
Cyclic
Read
Setup of the CAN base ID (11 Bit or 29 Bit, hex format) for cyclic read
of up to 5 object groups (see “
Cyclic Read Timing
”). The device
will automatically send specific object data to the IDs defined with
this setting. For more information refer to the programming guide.
Default:
100h
Base ID
Cyclic
Send
Setup of the CAN base ID (11 Bit or 29 Bit, hex format) for cyclic
send of the three set values for U, I and P along with status in one
single message. For more information refer to the programming
guide. Default:
200h
Cyclic
Read
Timing
Status
Activation/deactivation and time setting for the cyclic read of status
to the adjusted „
Base ID Cyclic Read + 1
“
Range: 20...5000 ms. Default: 0 (deactivated)
Actual
val.
Activation/deactivation and time setting for the cyclic read of actual
values to the adjusted „
Base ID Cyclic Read + 2
“
Range: 20...5000 ms. Default: 0 (deactivated)
Set val.
Activation/deactivation and time setting for the cyclic read of set
values of U & I to the adjusted „
Base ID Cyclic Read + 3
“
Range: 20...5000 ms. Default: 0 (deactivated)
Limits 1
Activation/deactivation and time setting for the cyclic read of adjust-
ment limits of P & R to the adjusted „
Base ID Cyclic Read + 4
“
Range: 20...5000 ms. Default: 0 (deactivated)
Limits 2
Activation/deactivation and time setting for the cyclic read of adjust-
ment limits of P & R to the adjusted „
Base ID Cyclic Read + 4
“
Data Length
Determines the DLC (data length) of all messages sent from the
device.
AUTO
= length varies between 3 and 8 bytes, depending on object
Always 8 Bytes
= length is always 8, filled up with zeros
IF Level 1
Level 2
Description
CANopen
Node Address
Selection of the CANopen node address in the range 1...127
Baud Rate
AUTO
Automatic detection of the bus baud rate.(speed)
LSS
Automatically sets baud rate and node address
Manual
Manual selection of the baud rate that is used by the CANopen interface.
Possible selections: 10 kbps, 20 kbps, 50 kbps, 100 kbps, 125 kbps, 250
kbps, 500 kbps, 800 kbps, 1Mbps (1Mbps = 1 Mbit/s, 10 kbps = 10 kbit/s)
IF Level 1
Description
RS232
-
The baud rate is selectable, other serial settings can’t be changed and are defined like
this: 8 data bits, 1 stop bit, parity = none
Baud rates: 2400, 4800, 9600, 19200, 38400, 57600, 115200