HANDBOOK
9. Installation
The feeder cable sections mentioned in our literature are given only as a guide.
To obtain a value perfectly suited to your own application and which takes account of the differ-
ent correction factors in respect of your plant, refer to the tables below.
Table 1
(in accordance with EN Standard 60204-1)
Values given for :
- Cable with copper conductors
- Cable with PVC insulation (for other insulants see Table 3)
- Ambient temperature 40 °C max. (for others see Table 2)
- Three-phase cable under load without including starting currents
- BT / C/ E cable layout.
Maximum Admissible Current
Cable section
Seated in Cable Duct
Wall
Cable
or Cable Trough
Fixing
Tray
B2 C E
3 x 1.5 mm² ................. 12.2 A .....................15.2 A ..................... 16.1 A
3 x 2.5 mm² ................. 16.5 A ...................... 21 A .........................22 A
3 x 4 mm² ....................23 A ........................ 28 A .........................30 A
3 x 6 mm² ....................29 A ........................ 36 A .........................37 A
3 x 10 mm² ...................40 A ........................ 50 A .........................52 A
3 x 16 mm² ...................53 A ........................ 66 A .........................70 A
3 x 25 m² .....................67 A ........................ 84 A .........................88 A
3 x 35 mm² ...................83 A ....................... 104 A .......................114 A
3 x 50 mm² ......................- .......................... 123 A .......................123 A
3 x 70 mm² ......................- .......................... 155 A .......................155 A
Ambient Correction
Temperature
Factor
30°C
(86°F)
...................1.15
35°C
(95°F)
...................1.08
40°C
(104°F)
..................1.00
45°C
(113°F)
..................0.91
50°C
(122°F)
..................0.82
55°C
(131°F)
..................0.71
60°C
(140°F)
..................0.58
Table 2
(correction factors for different ambient
temperatures)
Table 3
(correction factors for different cable insulating materials)
Insulating Max.
Working
Correction
material
Temperature
range
factor
PVC
...............................70°C (158°F) ............................ 1.00
Natural or Synthetic Rubber
...........60°C (140°F) ............................ 0.92
Silicone Rubber
....................120°C (248°F) ........................... 1.60
Содержание Washer-extractors WS4250H
Страница 2: ... ...
Страница 41: ...1009 7 9 Notice Date Page 01201138 INSTRUCTION HANDBOOK 9 Installation This page ist left blank on purpose ...
Страница 67: ...0807 33 9 Notice Date Page 01201138 INSTRUCTION HANDBOOK 9 Installation This page ist left blank on purpose ...
Страница 145: ...0107 76 11 Notice Date Page 01201138 INSTRUCTION HANDBOOK This page ist left blank on purpose 11 Machine operation ...
Страница 167: ... ...
Страница 168: ...www electrolux com laundrysystems Share more of our thinking at www electrolux com ...