9
ENGLISH
5.
SPECIFICATIONS
NOTE:
The installation must be
performed in accordance with the
requirement of local and national
When installing multiple indoor units
with a single outdoor unit, ensure that
the length of the refrigerant pipe and
Table 5.2
Unit: m/ft.
1 drive 2 1 drive 3 1 drive 4 1 drive 5
Max. length for all rooms
40/131
60/197
80/262
80/262
Max. length for one indoor unit
25/82
30/98
35/115
35/115
Max. height different between indoor
and outdoor unit
15/49
15/49
15/49
15/49
Max. height different between indoor units 10/33
10/33
10/33
10/33
Table 5.1
Number of units that can
be used together
Connected units
1-5 units
Compressor stop/start
frequency
Stop time
3 min or more
Power source voltage
voltage fluctuation
within ±10% of rated voltage
voltage drop during start within ±15% of rated voltage
interval unbalance
within ±3% of rated voltage
PIW
,QGRRUXQLW
,QGRRUXQLW
,QGRRUXQLW
0D[+HLJKWGLIIHUHQFH
2XWGRRUXQLW
PIW
PIW
standards. The installation may be
slightly different in different areas.
the drop height between the indoor and
outdoor units meet the requirements
illustrated in the following diagram: