Table 8.1:
Minimum Cross-Sectional Area
of Power and Signal Cables North America
Rated Current
of Appliance (A)
AWG
≤7
18
7 - 13
16
13 - 18
14
18 - 25
12
25 - 30
10
Table 8.2:
Other Regions
Rated Current of
Appliance (A)
Nominal
Cross-Sectional
Area (mm²)
≤6
0.75
6 - 10
1
10 - 16
1.5
16 - 25
2.5
25 - 32
4
32 - 45
6
b. Using wire strippers, strip the rubber
jacket from both ends of signal
cable to reveal about 15cm (5.9″)
of the wires inside.
c. Strip the insulation from the ends
of the wires.
d. Using a wire crimper, crimp u-lugs
on the ends of the wires.
NOTE:
While connecting the wires,
please strictly follow the wiring diagram
(found inside the electrical box cover).
2.
Remove the electric cover of the
outdoor unit. If there is no cover
on the outdoor unit, disassemble the
bolts from the maintenance board
and remove the protection board.
(See Fig. 8.1)
&RYHU
6FUHZ
Fig. 8.1
3.
Connect the u-lugs to the terminals
Match the wire colors/labels with
the labels on the terminal block, and
firmly screw the u-lug of each wire to
its corresponding terminal.
4.
Clamp down the cable with
designated cable clamp.
5.
Insulate unused wires with electrical
tape. Keep them away from any
electrical or metal parts.
6.
Reinstall the cover of the electric
control box.
Harmonic declaration
“The equipment M4OB-36HFN8-Q
complies with IEC 61000-3-12 provided
that the short-circuit power Ssc is
greater than or equal to 4787737.5 at
the interface point between the user’s
supply and the public system. It is the
responsibility of the installer or user of
the equipment to ensure, by consultation
with the distribution network operator
if necessary, that the equipment is
connected only to a supply with a short-
circuit power Ssc greater than or equal
to 4787737.5.” “The equipment M5OD-
42HFN8-Q complies with IEC 61000-3-
12 provided that the short-circuit power
Ssc is greater than or equal to 3190042.5
at the interface point between the user’s
supply and the public system. It is the
responsibility of the installer or user of
the equipment to ensure, by consultation
with the distribution network operator
if necessary, that the equipment is
connected only to a supply with a short-
circuit power Ssc greater than or equal
to 3190042.5.”