Pag. 132 di 152
11.2.3
--del
Delete
It removes the file having the number that is specified. This command is executed directly with no request
of confirmation and maximum care should therefore be used.
The “Delete” command allows to remove a list of files too. The file numbers to be removed must be
specified on the same command line with comma separation.
Example: –fnum=0400,0100,FE02 deletes the 0400 file (i.e. the configuration file of Service 4), the 0100
file (i.e. configuration of the load profile service) and the FE02 file (i.e. a file configured and saved by the
user).
The “Delete” command may be applied for removal of a directory file too (example:
--fnum=01
) and this
will automatically remove all the files of the specified directory
WARNING: the “Delete” command with --fnum=0 will remove all the files in memory.
11.2.4
--create
Create
Command to be used together with the –write command when the file to be written does not exists.
11.2.5
--reboot
Instrument restart from zero
This command generates an instruction to the instrument that simulates a power off and a power on. It is
used in order to render operative a firmware up-grade.
11.3 Communication
port
The communication may be direct only via the following communication ports.
11.3.1 IP Address
It uses an Ethernet connexion and the IP address where the instrument is located must be specified.
The protocol used is Modbus over IP.
11.3.2 Com Port
It uses one of the physical ports of a PC that is programmed with the specified communication speed.
In the case of communication via a Modem, the connexion must be established separately.
11.4 Protocol
format
Modbus supports both the RTU 8 bit format and the ASCII format. The instrument may be configured to
both formats.
The program supports the RTU format as default setting but it may be set to support the ASCII format by
means of the “
--mascii
” command.
11.5 Address
It identifies the Modbus address that is assigned to the instrument.
The default factory-set address is 27.
11.6 File
number
It’s the number, in HEX format, of the file that needs to be downloaded.
The file number 0000H (a simple 0 is also accepted) represent the directory of the flash disk.