22
ALARM
for operation as alarm contact output
REM
Remote
for operation as remote output device controlled via Modbus
5.1.2.4 Pulse characteristics configuration
If the PULSE selection is operated, the following page is shown allowing the configuration of the pulse
characteristics:
Where:
(1) Pulse output number being programmed.
(2) Pulse duration in mSec; programmable from 50 up to 900 in steps of 10
(3) Identifies the quantity proportional to the pulse output, selecting among:
Imported Active Power (import)
Inductive reactive Power with imported Active Power
Capacitive reactive Power with imported Active Power
Apparent Power with imported Active Power
Exported Active Power (export)
Inductive reactive Power with exported Active Power
Capacitive reactive Power with exported Active Power
Apparent Power with exported Active Power
(4)
the pulses take into account the CT and PT ratio and are referred to their primary readings
the pulses are referred to the CT (and PT) secondary reading without any multiplier .
(5) Pulse
weight
: programmable from 0,1 Wh up to 1 MWh through all the intermediate steps.
Example: 1.0 Wh = 1000 pulses/kWh.
(6) Identifies SETUP.
5.1.2.4.1 Pulse output set up with Modbus registers.
To set up the pulse output the Modbus Holding Registers from 120 to 127 have to be used.
Refer to chapter 9 for the details.