heated is accounted by the lower thermo-sensor (t1). When the water temperature is lower than the
one set and the higher than the switch on temperature the water heater will maintain its last state,
i.e. if it has been switched off it will stay off if it was  switched on it will stay  on. This rule is not
observed only if you change the temperature set, then the heater will turn on and will work to reach
the temperature set.
Note that 

"El Setting temp."

 must be 5 degrees higher than 

"Heater On temp."

 It is not possible to

set the temperatures unless that condition is satisfied!

RECOMMENDATION!

 Even if you have good solar installation and the season is suitable for using

solar energy for hot water, we recommend the following options: 

"Heater On temp."

 can be set to a

lower value such as 20 degrees and be measured by 

"Middle sensor t5"

. So even if there is no

sun, the water in the tank will not be colder than the tolerable 20 degrees. The heat exchanger for
the solar collector (bottom) shall heat the water in the measurement of the middle thermo-sensor t5
and if the day is with sufficient sun radiation the temperature measured by this sensor is unlikely to
drop more than 20 degrees and the electric heater will not switch on. We recommend that you set

"El Setting temp."

 at 40-45 degrees, because if there is no sun the water heater will be heated by

the electric heater to such a temperature that can be used for any household needs, but at the
same time if there is a strong sun it can take as well its heat.

3.10 Pumps control

Temperature settings for switching on and off the pumps of
the solar collector and / or boiler. The parameters are as
follows:

Solar ∆t1 (NHC-H52M-1S / NHC-H52M-2)

The differential temperature between the solar collector and
the  water heater  for switching on and off of the pump. In
case of temperature difference over the value in the column

"On"

  the pump will switch on and run until the difference

falls less than the value set in the column 

"Off"

Boiler DHW prior. ∆t2

 

(NHC-H52M-2)

The differential temperature between boiler and the water heater for switching on and off the pump
in mode with  priority  for  heating the  water   heater  for   domestic   hot water  (DHW).  In  case  of
temperature difference over the value in the column 

"On"

 the pump will switch on and run until the

difference falls less than the value set in the column 

"Off"

 

CH prior. t4 (NHC-H52M-2)

Adjust the temperature for switching on/off of the boiler circulating pump in heating priority mode for
the heating installation. When the temperature measured by
the probe panel in the boiler (t4) is higher than or equal to
the temperature set in the column  

"On"

  the boiler pump

shall switch on. When this temperature falls below the value
in the column 

"Off"

, the pump will turn off. 

3.11 Heating Installation

Check any heat source that works with the water heater. If
you still do not have systems for boiler or solar collector, you
can   disable   the   service   from   this   menu.   Furthermore,   in

13

Содержание NHC-H52M-1S

Страница 1: ...ation and operation instruction attached to your water heater unit All of the general instruction requirements concerning the water heater installation and connection to the water supply and electrici...

Страница 2: ...e listed in Table 2 Table 1 Models and features of the electronic units NHC H52M 1S NHC H52M 2 Thermostat control of the utility storage water electric heater heaters Control of the utility storage wa...

Страница 3: ...eater Each interval can be set in any day of the week to switch on and to what temperature water can be heated Control of the solar collector circulation pump power depending on the temperature differ...

Страница 4: ...tional protective conductor that never should be interrupted and or connected on the layout from the electric panel to the tank Otherwise the appliance shall not be correctly earthed and it shall redu...

Страница 5: ...unit will not work and it is very possible to damage it and increase the risk of electric shock It is necessary to secure the power cord to the power circuit of the water heater and the power cord fr...

Страница 6: ...wires in water heaters designed for wall mounting with one heat exchanger Fig 1 and with two heat exchangers Fig 2 The power cord phase conductor connects to the thermal cut out terminal labeled A1 or...

Страница 7: ...Fig 2 Single phase connection of water heaters with two heat exchangers NHC H52M 2 3 DISPLAYS SETTINGS MENUS 3 1 Main display graphics and indications Fig 3 7...

Страница 8: ...do not make any changes for a longer period between 20 seconds and 5 minutes depending on the settings menu you will automatically exit the selected menu without saving any changes made The only excep...

Страница 9: ...protection against overheating of the solar collector by automatically switching to Holiday mode to discharge the stored energy 3 5 2 On All authorized heat sources shall be switched on see menu Heati...

Страница 10: ...line but in column Off on the same line When this pump works the circulating pump on the image of the boiler on the display will rotate To protect the water tank from overheating the circulation pump...

Страница 11: ...h off There is one more operation mode for the boiler pump set from the menu Heating Installation row Boiler Pump Mode CH Priority When this mode is activated in the menu Pumps control shall be used t...

Страница 12: ...erature and it will switch on if the temperature of the lower thermo sensor t1 drops by 5 degrees less than the temperature set in Temp The timer allows exclusion of certain days of the week during wh...

Страница 13: ...temperature that can be used for any household needs but at the same time if there is a strong sun it can take as well its heat 3 10 Pumps control Temperature settings for switching on and off the pum...

Страница 14: ...accumulated heat in the water tank when you activate Holiday mode the temperature will be reduced to the value set in this field Use boiler pump NHC H52M 2 When this field is checked the discharge of...

Страница 15: ...rature settings ATTENTION When for long periods you do not use hot water and the sun is strong enough do not disconnect the water heater from the apartment electricity panel This can damage the standi...

Страница 16: ...y collected in the water heater during the day Holiday mode Solar anti frost Switched on mode for protecting the solar collector against freezing Freezing protection of the boiler Switched on mode for...

Страница 17: ...d date to when the thermostat is working before you interrupted power supply Power supply on Time and date when the power supply is restored These messages will be registered only if the system clock...

Страница 18: ...creen is the date concerning the information displayed while at the bottom is provided a summary for the day 4 5 Information By pressing the button Enter after the state Statistics by the hours shall...

Страница 19: ...thermostat shall continuously monitor the temperature as the water in the water tank and the solar collector If necessary the protection mode shall be switched on for Anti freezing protection of the...

Страница 20: ...late a new heat in order to discharge the solar collector The pump will operate until the temperature in the tank falls below the temperature set in Solar protection line Tank min temp This mode is in...

Отзывы: