Using the water heater via a WiFi connection is possible only with provided by the producer WiFi
modem. For further information contact the manufacturer / supplier of your water heater.

4.6а Controller version

Once the arrow „down“ is pressed from the screen „WiFi connection“, proceed to the information
screen with the version of the controller and software in it.

4.7 Diagnostics

Next   pressing   of   the   Enter   button   shall   display   the   last
information screen 

„Diagnostics“

, which consists of a list of

information about every registered problem and the exact
time and date of its occurrence. If these are more than three
with the arrows „down“ and „up“ shall be displayed the next
page. By holding the Enter key for over two seconds the
accumulated  diagnostic   information   shall   be  cleared. The
symbol   „star“   marks   both   the   latest   and   the   newest
registered issue. The messages that you can see on this
screen are the same as reports of failures and errors listed
in Table 6.

5. UNIT MODES

5.1 Protection modes

The protection modes are designed to protect the installations of the boiler, the solar collector and
the water heater in case of extreme operative conditions. Whether the water heater is on or off and
notwithstanding in which mode it works, the thermostat shall continuously monitor the temperature
as the water in the water tank and the solar collector. If necessary, the protection mode shall be
switched on for:

Anti-freezing protection of the solar collector

 

(NHC-H52M-1S  / NHC-H52M-2)

. This

protection brings heat from the water heater to protect the solar collector from freezing. It
activates when the temperature measured in the collector falls below 

„Solar protection“

limit on row 

„Anti-frost temp.“

. This function may be switched off from the same menu

line 

„Solar anti-frost“

.

Protection   from   freezing   of   the   water   tank

  (

NHC-H52M-1S  /   NHC-H52M-2

).   The

electric heater is activated if the temperature in the water tank falls below 3 degrees.

Protection against overheating of the solar collector (NHC-H52M-1S / NHC-H52M-2).

If the temperature of the solar collector gets above 90 degrees, the circulation pump of
the solar shall switch on regardless of the temperature difference. The pump will switch off
if the water temperature in the tank gets above 85 degrees.

Protection against overheating of the water tank

  (

NHC-H52M-2)

. For available and

activated heating system. If the water temperature in the middle of the  water heater
(measured by t5) exceeds 80 degrees and the water temperature in the boiler is below 50
degrees will turn on the heating system pump for release of the accumulated heat. The
pump will operate until the temperature falls to 76 degrees on the same thermo-sensor or

19

Содержание NHC-H52M-1S

Страница 1: ...ation and operation instruction attached to your water heater unit All of the general instruction requirements concerning the water heater installation and connection to the water supply and electrici...

Страница 2: ...e listed in Table 2 Table 1 Models and features of the electronic units NHC H52M 1S NHC H52M 2 Thermostat control of the utility storage water electric heater heaters Control of the utility storage wa...

Страница 3: ...eater Each interval can be set in any day of the week to switch on and to what temperature water can be heated Control of the solar collector circulation pump power depending on the temperature differ...

Страница 4: ...tional protective conductor that never should be interrupted and or connected on the layout from the electric panel to the tank Otherwise the appliance shall not be correctly earthed and it shall redu...

Страница 5: ...unit will not work and it is very possible to damage it and increase the risk of electric shock It is necessary to secure the power cord to the power circuit of the water heater and the power cord fr...

Страница 6: ...wires in water heaters designed for wall mounting with one heat exchanger Fig 1 and with two heat exchangers Fig 2 The power cord phase conductor connects to the thermal cut out terminal labeled A1 or...

Страница 7: ...Fig 2 Single phase connection of water heaters with two heat exchangers NHC H52M 2 3 DISPLAYS SETTINGS MENUS 3 1 Main display graphics and indications Fig 3 7...

Страница 8: ...do not make any changes for a longer period between 20 seconds and 5 minutes depending on the settings menu you will automatically exit the selected menu without saving any changes made The only excep...

Страница 9: ...protection against overheating of the solar collector by automatically switching to Holiday mode to discharge the stored energy 3 5 2 On All authorized heat sources shall be switched on see menu Heati...

Страница 10: ...line but in column Off on the same line When this pump works the circulating pump on the image of the boiler on the display will rotate To protect the water tank from overheating the circulation pump...

Страница 11: ...h off There is one more operation mode for the boiler pump set from the menu Heating Installation row Boiler Pump Mode CH Priority When this mode is activated in the menu Pumps control shall be used t...

Страница 12: ...erature and it will switch on if the temperature of the lower thermo sensor t1 drops by 5 degrees less than the temperature set in Temp The timer allows exclusion of certain days of the week during wh...

Страница 13: ...temperature that can be used for any household needs but at the same time if there is a strong sun it can take as well its heat 3 10 Pumps control Temperature settings for switching on and off the pum...

Страница 14: ...accumulated heat in the water tank when you activate Holiday mode the temperature will be reduced to the value set in this field Use boiler pump NHC H52M 2 When this field is checked the discharge of...

Страница 15: ...rature settings ATTENTION When for long periods you do not use hot water and the sun is strong enough do not disconnect the water heater from the apartment electricity panel This can damage the standi...

Страница 16: ...y collected in the water heater during the day Holiday mode Solar anti frost Switched on mode for protecting the solar collector against freezing Freezing protection of the boiler Switched on mode for...

Страница 17: ...d date to when the thermostat is working before you interrupted power supply Power supply on Time and date when the power supply is restored These messages will be registered only if the system clock...

Страница 18: ...creen is the date concerning the information displayed while at the bottom is provided a summary for the day 4 5 Information By pressing the button Enter after the state Statistics by the hours shall...

Страница 19: ...thermostat shall continuously monitor the temperature as the water in the water tank and the solar collector If necessary the protection mode shall be switched on for Anti freezing protection of the...

Страница 20: ...late a new heat in order to discharge the solar collector The pump will operate until the temperature in the tank falls below the temperature set in Solar protection line Tank min temp This mode is in...

Отзывы: