77
EN
EWD2 Manual v.1.4
4. EWD2 ZONES AND TAMPERS
Upon successful EWD2 magnetic door contact binding process, the system adds 2 wireless Instant zones. The wireless zones can be set up
to operate under one of the following modes each:
• Zone 1:
• Magnetic door contact
– Designed for causing an alarm (by default) if doors/windows are opened when the system is armed.
• External sensor
– Designed for causing an alarm (by default) if the wired digital sensor, connected to Z and COM terminals, is
triggered when the system is armed. This mode does NOT operate with
Flood sensor
mode on Zone 2 simultaneously.
• Zone 2:
• Shock sensor
– Designed for causing an alarm (by default) if the built-in shock sensor is triggered.
• Flood sensor
– Designed for causing an alarm (by default) if a flood sensor EFS1, connected to Z and COM terminals, is triggered.
This mode does NOT operate with External sensor mode on Zone 1 simultaneously.
Possible zone mode combinations:
• Zone 1:
Magnetic door c
Zone 2:
Shock sensor
• Zone 1:
Magnetic door c
Zone 2:
Flood sensor
• Zone 1:
External
Zone 2:
Shock sensor
• Zone 1:
Magnetic door c
Zone2:
N/A
• Zone 1:
External
Zone2:
N/A
• Zone 1:
N/A +
Zone 2:
Shock sensor
• Zone 1:
N/A +
Zone 2:
Flood sensor
NOTE:
Flood sensor
mode is not supported when EWD2 is used with ESIM264 alarm system.
In case of tamper violation, the alarm is caused regardless of system being armed or disarmed. There are 2 ways to detect tamper violation
on EWD2:
• By tamper switch.
EWD2 comes equipped with 2 built-in tamper switches intended for enclosure supervision:
• one located on the front side of the PCB supervising the front cover in case it is illegally opened (see Fig. No. 1).
• the other one located on back of the PCB supervising the back side of the enclosure in case the EWD2 is illegally detached from
the wall (see Fig. No. 1).
Once the enclosure of EWD2 is tampered, the tamper switch will become triggered. This action will be followed by alarm, resulting in
sending an SMS text message and/or phone call to the user. The SMS text message contains the violated tamper number.
• By wireless connection loss.
The wireless connection loss between EWD2 and ELDES alarm system leads to alarm. The system
identifies this event as a tamper violation and sends alarm by SMS text message and phone call to the user (-s) by default. The SMS text
message contains the wireless device model, wireless ID code and tamper number
ATTENTION:
The tamper will not operate if both wireless zones are disabled.
For more details on EWD2 zone and tamper configuration, please refer to
ELDES Configuration Tool
software's HELP section.
5. BATTERY REPLACEMENT
1. Open EWD2 enclosure.
2. Remove both old batteries from the battery slots.
3. Insert the 2 new 1,5V Alkaline AAAA type batteries according to the appropriate battery slot positive/negative terminals indicated on
the PCB of EWD2.
4. Batteries replaced.
See
3. INSTALLATION
for more details.
ATTENTION:
Only 1,5V Alkaline AAAA type batteries can be used. Install only new, high quality and unexpired batteries. Do not mix the old
batteries with the new ones.
ATTENTION:
At least 1 battery must be removed if the device is not in use.
ATTENTION:
In order to avoid fire or explosion hazards, the system must be used only with approved battery. Special care must be taken
when connecting positive and negative battery terminals. Dispose old batteries only into special collection sites. Do not charge, disassemble,
heat or incinerate old batteries.
ATTENTION:
The system sends an SMS message to a preset user phone number as soon as the battery level runs below 5%.
ATTENTION:
The battery status can be monitored in real-time using
ELDES Configuration Tool
software.
Содержание EWD2
Страница 1: ...EWD2 WIRELESS MAGNETIC DOOR CONTACT SHOCK SENSOR FLOOD SENSOR ...
Страница 9: ......
Страница 10: ...MadeintheEuropeanUnion www eldes lt ...