02/2016 - Art. Nr. 4200 1046 8202A
26
Servicing
Maintenance
Cleaning the pump filter
The filter is located in the pump housing.
It must be cleaned each time the
equipment is serviced. To do so:
• Close the oil shut-off valve.
• Place a container under the pump to
catch the fuel oil.
• Remove the screws
Z
and cover.
• Remove, clean or replace the filter.
• Refit the filter, close the cover again
and use a new gasket.
• Tighten securely.
• Reopen the oil shut-off valve.
• Check pressure and tightness.
Cleaning the cover
• Do not use abrasive products or
products containing chlorine.
• Clean the cover with water and a
suitable cleaning product.
• Refit the cover.
Important
After every operation: check the
combustion parameters and real
operating condition (doors closed,
cover fitted etc.). Record the results
in the relevant documents.
Checking the flue gas temperature
• Check the flue gas temperature at
regular intervals.
• Clean the boiler if the flue gas
temperature is more than 30 °C above
the value measured at the time of
commissioning.
• Use a flue gas temperature gauge to
make the check easier.
Resetting the maintenance indicator
The maintenance symbol
appears on the control unit display after
30,000 start-ups. This is why it is
necessary to reset the maintenance
counter after each service. To do this,
press the control unit unlocking button
for at least 9 seconds.