02/2016 - Art. Nr. 4200 1046 8202A
10
Operation
Pump
This is a gear pump. It must be
connected as a two-line pump via a
bleed filter. For the connection of the fuel
oil tank and the bleed filter, it is better to
use the single line option. An intake filter
and two oil pressure regulators are
integrated in the pump. Pressure
gauges for pressure measurements
4
and negative pressure measurements
5
must be connected before the
equipment is commissioned.
1
Return connection
G1/4
2
Vacuum connection
G1/4
3
Nozzle supply line connection G1/8
4
Pressure gauge connector
5
Vacuum gauge connector
8
1st stage pressure setting
9
2nd stage pressure setting
Y1
Solenoid valve, 1st stage
Y5
Solenoid valve, 2nd stage