02/2016 - Art. Nr. 4200 1046 8202A
21
en
Start-up
Setting the air pressure switch
Menu 5: Configuration for domestic use
Setting the air pressure switch
• Start the burner in the 1
st
stage.
• Increase the air pressure switch
setting value until the burner cuts out.
• Set the switch-off point to approxi-
mately 20% below the switch-off
pressure read.
Menu 5: Configuration for domestic use
To be used by ELCO-qualified technicians only!
The menu lets you set the following parameters:
• Fuel oil burners: fuel oil heater on / off as well as max heating time.
• Adjustment release waiting time.
• Fan speed when the burner is off.
• Fan speed during the pre-ventilation phase.
• Activate the option
“Configuration for domestic use”
from the menu overview. Enter the
access code (only available to an ELCO-qualified technician). Access is possible only when the
burner is off.
Fuel oil heater
If no time indication is displayed next to the heater symbol, the heater is off.
• Activate the heater setting using the
key. The time starts to flash.
• Heater on/off switch using keys
• Changing max heating time with
,
(1 press = 10 s)
Note: for VB2..VD: 400 s