Technical Data Sheet
Duoblock Dual Fuel Burner
Feld52:
RPD 60 / 70 / 80 GL-R / GS-R
14511
20470
30350
2232
3590
5500
0
5000
10000
15000
20000
25000
30000
35000
RPD 60 RPD 70 RPD 80
kW
Technical Data
Fuel flow rate (light oil)
Gas flow rate
Operating mode
Fuel type
Automatic burner controller
Flame sensor
Ignition burner
Ignition transformer
Pump output at 35 bar
MAT oil control block
Oil connection
Nozzle rod
Nozzle
Actuator
Gas connection
Weight
Pressure loss in mixing unit
Gas control organ
Burner output
Output range
2232 - 14511 kW
RPD 60
188 - 1223 kg/h
223 - 1451 m³/h
fully modulating
Light oil / heavy oil / natural gas / special fuels
LFL 1., LGK 16 or other approved models
QRA 2, QRA 53 or other approved models
MAT / Hegwein ZNVL (ZT0)
D-52 L5 KV
Z112 K5
3100 l/h
SRB 19000/60
R 3/4" / 22 mm
MAT
MAT - MK 50
WAN 4
R 5"
640 kg
30 mbar or according to diagram
according to gas pressure
(MAT ignition burner)
(Hegwein ignition burner)
3590 - 20470 kW
RPD 70
303 - 1726 kg/h
359 - 2047 m³/h
4000 l/h
SRB 19000/70
R 3/4" / 22 mm
MAT
MAT - MK 50
WAN 4 A
R 5"
900 kg
5500 - 30350 kW
RPD 80
465 - 2559 kg/h
550 - 3035 m³/h
6400 l/h
SRB 19000/80
R 1" / 28 mm
MAT
MAT - MK 50
WAN 4 A
R 8"
1200 kg
Technical Data Sheet
Duoblock Dual Fuel Burner
RPD 60, 70 & 80 GL-R / GS - R