elco N6.2400 G-R Скачать руководство пользователя страница 9

10/2010 - Art. Nr. 4200 1030 6900A

9

Assembly

Gas connection

Gas connection

The gas lines and valves and 
instruments group should be installed 
and taken into operation in accordance 
with the applicable engineering 
standards and regulations.

The connection between the gas 
distribution network and the gas ramp 
must be done by authorised persons.

The section of the pipings must be 
calculated so that the loss of load 
doesn’t exceed 5% of the distribution 
pressure.

A quarter turn manual valve (not 
supplied) must be provided for upstream 
of the gas ramp and the filter.

The filter must be installed on a 
horizontal nozzle with the cover in the 
vertical position to enable cleaning.

The threaded unions used must be in 
conformity with present standards 
(tapered male thread, straight female 
thread with sealing provided in the 
thread).

Provide for sufficient space to access 
the gas pressure switch adjustment.

Gas properties

Prior to any installation work make sure 
to obtain the following data from the gas 
supply company:
1. type of gas
2. calorific value H

un

=kW/m³ (kJ/m³)

3. maximum CO

2

 content of exhaust gas

4. gas connection pressure and rest 
pressure

Type of gas test

Prior to mounting the burner to the gas 
feed line check the available type of gas 
and burner type against the data given 
on the burner nameplate (attached to 
burner). Be sure the description of the 
burner and the type of gas are the same 
as indicated on the nameplate.

Gas connection pressure

A minimum connection pressure must 
be available upstream of the burner gas 
valve to ensure the proper functioning of 
the burner.
For the installation of the valves and 
instruments group take care to observe 
the mounting instructions supplied by 
their manufacturers (these are packed 
with the equipment).
The gas line installed to the burner must 
be dimensioned in accordance with the 
throughput rate and the available 
pressure.

For selecting the nominal bore „DN“ of 
the gas valves and instruments group 

care should be taken to observe the 
flue resistance of the boiler and the 
gas pressure loss of the burner and 
valves and instruments group

.

Caution!

The absence of impurities and foreign 
bodies must be checked before 
installation and commissioning of the 
gas ramp, the lever valves and unions.

Gas valves and instruments group

The gas valves and instruments group 
can be connected directly to the gas 
feed line. 

Take care to observe the 

correct order of installation and 
direction of flow (arrow on housing).

Check the valves and instruments and 
connection pieces for absence of dirt 
particles and foreign matter before 
installation and initial operation. 

To

provide effective conditions for start-
up make sure the distance between 
the burner and the gas stop valve is 
as short as possible.

Leak test

The gas line upstream of the burner gas 
valves and instruments group must be 
installed in accordance with the 
applicable regulations, checked for 
absence of leaks, vented and certified 
accordingly by the gas installation 
company. The screwed unions and 
flanged joints must be checked for 
proper tightness (by making a pressure 
test). The leak test must be made under 
pressure using approved foaming 
agents which do not cause corrosion. 
For steam boiler furnaces the result of 
the leak test must be duly certified.

Venting
Caution

! Prior to taking the burner into 

operation or after any repair work make 
sure to vent the complete gas feed line 
and the gas valves and instruments 
group into the open atmosphere (e.g. by 
means of a hose) taking care to avoid 
any hazards.

In no case should the gas line be 
vented into the heating or furnace 
chambers.

 Make use of a test burner to 

check the gas-carrying spaces are free 
from an inflammable gas mixture.

Support

The valves and instruments group must 
be supported with a telescopic jacking 
member or similar during and after 
installation (e.g. on filter and valve).

Joint

It is recommended to provide an easyto-
disconnect joint (with planar sealing 
faces) to facilitate repair work on the 
boiler (furnace) and allow the boiler door 
to be swivelled out if required.

en

Содержание N6.2400 G-R

Страница 1: ...Art Nr 4200 1030 6900A N6 2400 G R N6 2900 G R N7 3600 G R N7 4500 G R Operating instructions For specialist installation engineers Gas burners 2 25 en de fr 4200 1030 7000 it nl 4200 1031 9200 4200 1...

Страница 2: ...achinery directive 2004 108 EC EMC directive 2006 95 EC Low voltage directive 2009 142 EC Gas appliances Directive 97 23 EC Pressure Equipment Directive Pirna 26th May 2010 D HOFFMANN Important inform...

Страница 3: ...wer controller option 5 Housing 6 Gas inlet flange 8 Burner flame tube 10 Integrated electrical cabinet 11 Burner fixing flange 13 Air intake box 14 Mechanical compound 19 Hoisting eyes F6 Air pressur...

Страница 4: ...is provided a stepless control concept The stepless control will allow the burner to be operated at any desired stage between its partial load and full load positions The burner will always be turned...

Страница 5: ...e electric drive unit in dependence of the heat requirement The air damper and the gas damper will be controlled by the same system To ensure an optimum air to fuel adjustment over the full control ra...

Страница 6: ...in the annex and in the documents LFL 1 7451 LGK Functional diagram LFL 1 LGK A Starting type interval A B Flame development interval B Burner has reached operating position B C Burner operation heat...

Страница 7: ...n 5 Actuator SKP 15 6 Actuator SKP 25 7 Gas main valve VGD 8 Gas manometer with push button downstream option 9 Gas tightness control unit en Technical data Input pressure 360 mbar max Ambient tempera...

Страница 8: ...s not allowed to be lined with brickwork Note for reverse flow boilers For reverse flow boilers the dimension T1 is only a recommended value Depending on type of boiler the burner head must stand at l...

Страница 9: ...valves and instruments group care should be taken to observe the flue resistance of the boiler and the gas pressure loss of the burner and valves and instruments group Caution The absence of impuritie...

Страница 10: ...sation probe and of the ignition electrode as per the diagrams Insert the combustion components into the head tighten the mounting screws S3 Connect the ionisation cable IK and the ignition cable ZK o...

Страница 11: ...f the gas line should be of a size designed to guarantee that the gas flow pressure does not drop below the specified level A manual shut off valve not supplied must be fitted upstream of the gas trai...

Страница 12: ...ressure Adjust the max power switch again Burner power should never exceed the max heat generator allowed flame power see chapter entitled Exhaust gas test Decrease power gradually down to min power u...

Страница 13: ...ate the selection of the switching points The cam plates are provided with a small pointer for indicating the switching point of a scale between the setting ranges An additional scale fitted to the en...

Страница 14: ...ke sure the polarity of the device is observed see connection examples for the control box LFL 1 LGK During ionisation monitoring it is important that the signal is transmitted without wastage The con...

Страница 15: ...e of the combustion air fan The pressure switch Dungs LGW has been designed for switching on off or over an electric circuit in the case of changes of the actual pressure levels from the setpoint sett...

Страница 16: ...re proper conditions for start up the distance between the burner and the gas shut off valve must be as low as possible On completion of installation the gas valves and instruments group must be subje...

Страница 17: ...list There follows a general description of the gas train Gas trains with a double valve are intended for the supply main shut off gas filtration gas pressure regulation and monitoring of the gas supp...

Страница 18: ...ptions in accordance with country specific requirements 143 Pressure gauge with pushbutton valve 147 Test burner with pushbutton valve 148 Compensator 154 Gas safety valve additional 313a Max gas pres...

Страница 19: ...re reinstallation NOTE For the installation of the filter mat take care to observe the marking or sticker en Test burner Depending on the country specific requirements when installing steam boilers it...

Страница 20: ...urner s control and safety unit which then starts its cycle If leakage test is NOK red light comes on and no power is fed to the control and safety unit Control cycles have to be restarted manually Ch...

Страница 21: ...ctive parts if necessary Clean the fan wheel and the blower Clean the gas filter replace it if necessary Visual inspection of the burner s electrical components eliminate malfunctions if necessary Che...

Страница 22: ...lts in the relevant documents Important Once the pressure switches have been set they must be protected to prevent settings from being altered For example this can be done by placing a spot of varnish...

Страница 23: ...lace cable search for cause and eliminate Pilot burner failure Adjust ignition gas pressure Ignition gas valve does not open Search for cause and eliminate Defective solenoid Replace 2 Motor running f...

Страница 24: ...ten to the motor bearing noise to identify possible irregularities 4 Mixing unit gives poor combustion data Cause Remedy Incorrect settings Correct settings Incorrect mixture ignition unit Replace uni...

Страница 25: ...ir Damper CLOSED limit switch is missing or a contact is not closed between terminals 12 and 4 or 4 and 5 or the contacts of all control and safety units in the controlled system are not closed e g ga...

Страница 26: ...10 2010 Art Nr 4200 1030 6900A 26...

Страница 27: ...10 2010 Art Nr 4200 1030 6900A 27...

Страница 28: ...60 1731 Zellik 02 4631902 ELCOTHERM AG Sarganserstrasse 100 7324 Vilters 0848 808 808 ELCO GmbH Dreieichstr 10 64546 M rfelden Walldorf 0180 3526180 ELCO Italia S p A Via Roma 64 31023 Resana TV 800...

Отзывы: