background image

10/2010 - Art. Nr. 4200 1030 6900A

4

Gas start-up mode

As soon as the furnace system is 
required to supply heat, the burner 
control circuit will close and the program 
flow started. When the program has 
come to its end, the burner will be turned 
on.

An automatic test is made for the 
tightness of the gas valves prior to 
each burner start.

The air damper is in its closed 
position when the burner is out of 
operation.

The electric actuator will open the closed 
air damper to its full-load position so that 
the burner will ventilate the furnace and 
the exhaust hoods with the specified air 
rate. Shortly after the pre-ventilation 
process has been started the lack-of-air 
cut-out must change over to operating 
position within a certain time, i.e. the 
minimum air pressure setting must be 
reached and maintained until the burner 
is turned off. At the end of the specified 
pre-ventilation time the air damper will 
be moved into its partial-load position in 
a linked control concept with the gas 
damper.

The ignition transformer is activated.

After the pre-ignition time, the main gas 
valves are open and the gas comes out 
from injectors where it is mixed in the 
combustion head with air coming from 
the fan. The ignition of the gas air 
mixture is done directly by a high voltage 
spark on a gas injector. During the 
safety time, a stable flame is formed and 
is monitored by an ionisation sensor. 
The ignition is stopped before the end of 
the safety time and the burner operates 
at its minimum power. The start-up 
programme is completed.

Gas operating mode

After the flame has developed the load 
regulator will be enabled which brings 
the burner into its operating position. 
The load regulator will now control the 
burner automatically between its partial-
load and full-load stages. Depending on 
the heat demand, the electric actuator of 
the compound control system will be fed 
with the OPEN or CLOSE command via 
the regulator and thus increase or 
decrease the gas and air flow rates. This 
compound control system will vary the 
positions of the gas control valve and air 
damper and thus regulate the gas flow 
rate in a linked concept with the air flow 
rate. The burner can either be controlled 
by a 2-stage sliding or, if a respective 
controller is provided, a stepless control 
concept. The stepless control will allow 

the burner to be operated at any desired 
stage between its partial-load and full-
load positions. The burner will always be 
turned off out of its partial-load position. 
The air damper will be closed when the 
burner is out of operation and will thus 
prevent cold air flowing through the 
burner chamber, heat exchanger and 
chimney. The interior cooling losses will 
thus be greatly minimized.

Attention:

If there are shut-off dampers in the flue 
gas tract they must be complete open. 
Otherwise there will be a high danger of 
low-speed detonation or explosion!  The 
open-position of the shut-off damper can 
be assured by the integration of the 
opening contact of the shut-off damper 
in the safety chain of the heat generator.

General safety functions

In case a flame does not develop when 
starting the burner (fuel release), the 
burner controller will shut off at the end 
of the safety period (shut-off on trouble). 
A shut-off on trouble will also occur in 
the case of flame failure during 
operation, air flow failure during the pre-
ventilation phase and pressure failure 
during the whole period of burner 
operation. Any failure of the flame signal 
at the end of the safety period and a 
flame signal during the pre-ventilation 
phase (external light control) will result in 
a shut-off on trouble with the automatic 
furnace controller being locked.

The trouble is indicated by the trouble 
signal lamp lighting up. The automatic 
furnace controller can be unlocked 
immediately after a shut-off on trouble 
by pressing the unlocking key. The 
program unit will return to its starting 
position and proceed with the restart of 
the burner.

A voltage failure will result in a regular 
shut-off of the burner. After voltage 
recovery, the burner can be 
automatically restarted unless another 
interlock is active, e.g. one caused by 
the safety circuit. In any case, the fuel oil 
supply will be immediately stopped upon 
occurrence of a trouble.

The control unit will stop at the same 
time causing also the trouble location 
indicator to stop. The symbols will 
indicate the kind of trouble.

Operation

Gas start-up mode
Gas operating mode
General safety functions

Full load

Operating position

Load regulator

Release

Partial load

Ignition/Gas valves

Gas control:
2-stage sliding                                         Stepless

ON                    OFF

ON                      OFF

Full load

Operating position

Load regulator

Release

Start load

Partial load

Ignition/Gas valves

Содержание N6.2400 G-R

Страница 1: ...Art Nr 4200 1030 6900A N6 2400 G R N6 2900 G R N7 3600 G R N7 4500 G R Operating instructions For specialist installation engineers Gas burners 2 25 en de fr 4200 1030 7000 it nl 4200 1031 9200 4200 1...

Страница 2: ...achinery directive 2004 108 EC EMC directive 2006 95 EC Low voltage directive 2009 142 EC Gas appliances Directive 97 23 EC Pressure Equipment Directive Pirna 26th May 2010 D HOFFMANN Important inform...

Страница 3: ...wer controller option 5 Housing 6 Gas inlet flange 8 Burner flame tube 10 Integrated electrical cabinet 11 Burner fixing flange 13 Air intake box 14 Mechanical compound 19 Hoisting eyes F6 Air pressur...

Страница 4: ...is provided a stepless control concept The stepless control will allow the burner to be operated at any desired stage between its partial load and full load positions The burner will always be turned...

Страница 5: ...e electric drive unit in dependence of the heat requirement The air damper and the gas damper will be controlled by the same system To ensure an optimum air to fuel adjustment over the full control ra...

Страница 6: ...in the annex and in the documents LFL 1 7451 LGK Functional diagram LFL 1 LGK A Starting type interval A B Flame development interval B Burner has reached operating position B C Burner operation heat...

Страница 7: ...n 5 Actuator SKP 15 6 Actuator SKP 25 7 Gas main valve VGD 8 Gas manometer with push button downstream option 9 Gas tightness control unit en Technical data Input pressure 360 mbar max Ambient tempera...

Страница 8: ...s not allowed to be lined with brickwork Note for reverse flow boilers For reverse flow boilers the dimension T1 is only a recommended value Depending on type of boiler the burner head must stand at l...

Страница 9: ...valves and instruments group care should be taken to observe the flue resistance of the boiler and the gas pressure loss of the burner and valves and instruments group Caution The absence of impuritie...

Страница 10: ...sation probe and of the ignition electrode as per the diagrams Insert the combustion components into the head tighten the mounting screws S3 Connect the ionisation cable IK and the ignition cable ZK o...

Страница 11: ...f the gas line should be of a size designed to guarantee that the gas flow pressure does not drop below the specified level A manual shut off valve not supplied must be fitted upstream of the gas trai...

Страница 12: ...ressure Adjust the max power switch again Burner power should never exceed the max heat generator allowed flame power see chapter entitled Exhaust gas test Decrease power gradually down to min power u...

Страница 13: ...ate the selection of the switching points The cam plates are provided with a small pointer for indicating the switching point of a scale between the setting ranges An additional scale fitted to the en...

Страница 14: ...ke sure the polarity of the device is observed see connection examples for the control box LFL 1 LGK During ionisation monitoring it is important that the signal is transmitted without wastage The con...

Страница 15: ...e of the combustion air fan The pressure switch Dungs LGW has been designed for switching on off or over an electric circuit in the case of changes of the actual pressure levels from the setpoint sett...

Страница 16: ...re proper conditions for start up the distance between the burner and the gas shut off valve must be as low as possible On completion of installation the gas valves and instruments group must be subje...

Страница 17: ...list There follows a general description of the gas train Gas trains with a double valve are intended for the supply main shut off gas filtration gas pressure regulation and monitoring of the gas supp...

Страница 18: ...ptions in accordance with country specific requirements 143 Pressure gauge with pushbutton valve 147 Test burner with pushbutton valve 148 Compensator 154 Gas safety valve additional 313a Max gas pres...

Страница 19: ...re reinstallation NOTE For the installation of the filter mat take care to observe the marking or sticker en Test burner Depending on the country specific requirements when installing steam boilers it...

Страница 20: ...urner s control and safety unit which then starts its cycle If leakage test is NOK red light comes on and no power is fed to the control and safety unit Control cycles have to be restarted manually Ch...

Страница 21: ...ctive parts if necessary Clean the fan wheel and the blower Clean the gas filter replace it if necessary Visual inspection of the burner s electrical components eliminate malfunctions if necessary Che...

Страница 22: ...lts in the relevant documents Important Once the pressure switches have been set they must be protected to prevent settings from being altered For example this can be done by placing a spot of varnish...

Страница 23: ...lace cable search for cause and eliminate Pilot burner failure Adjust ignition gas pressure Ignition gas valve does not open Search for cause and eliminate Defective solenoid Replace 2 Motor running f...

Страница 24: ...ten to the motor bearing noise to identify possible irregularities 4 Mixing unit gives poor combustion data Cause Remedy Incorrect settings Correct settings Incorrect mixture ignition unit Replace uni...

Страница 25: ...ir Damper CLOSED limit switch is missing or a contact is not closed between terminals 12 and 4 or 4 and 5 or the contacts of all control and safety units in the controlled system are not closed e g ga...

Страница 26: ...10 2010 Art Nr 4200 1030 6900A 26...

Страница 27: ...10 2010 Art Nr 4200 1030 6900A 27...

Страница 28: ...60 1731 Zellik 02 4631902 ELCOTHERM AG Sarganserstrasse 100 7324 Vilters 0848 808 808 ELCO GmbH Dreieichstr 10 64546 M rfelden Walldorf 0180 3526180 ELCO Italia S p A Via Roma 64 31023 Resana TV 800...

Отзывы: