10/2010 - Art. Nr. 4200 1030 6900A

5

Operation

Fuel-air compound control
Gas valves and instruments group

en

Fuel-air compound control

This compound control system with 
precision-adjustment capability has 
been designed to allow the fuel and air 
flow rates to be steadily varied in sliding 
mode for an adjustment of the fuel-air 
ratio over the whole control range.
In the two-stage sliding control concept 
the partial-load and full-load positions 
are within the control range. Depending 
on the heat demand these two load 
points will be selected in sliding mode. A 
larger fuel feed will not be suddenly 
turned on or off. In the stepless control 
mode the load will be controlled at any 
point within the control range depending 
on the heat demand. The two-stage 
sliding and the stepless control concepts 
are different only in the control systems 
used with the burners. The same mode 
of operation is used for both versions.

Mechanical compound control:

The compound control system will be 
operated by the steplessly reversible 
electric drive unit in dependence of the 
heat requirement. The air damper and 
the gas damper will be controlled by the 
same system.

To ensure an optimum air-to-fuel 
adjustment over the full control range, it 
will be possible to vary the position of the 
air damper by means of stud bolts 
incorporated in the compound controller.

Gas valves and instruments group

The gas valves and instruments group 
used with the furnace will be selected 
according to the specific requirements to 
be met by a burner system.

The following factors must be taken into 
account:
•  burner output
•  furnace back pressure 
•  gas pressure loss of the burner head
•  gas pressure losses of the gas valves 

and instruments group

The total gas pressure loss must always 
be smaller than the available gas flow 
pressure.

NOTE:

 Use should only be made of gas 

valves and instruments that have been 
approved in accordance with the burner 
test specifications.

100 Burner
120 Air damper
141 Ball valve
142 Gas filter

143

Pressure gauge with stop valve

147 Test burner with stop valve 

(optional)

150 Gas damper
153 Main gas solenoid valve
154 Safety solenoid valve
310 Blower
311 Minimum air pressure switch
313 Minimum gas pressure switch
314 Leak test
349 Actuator

Содержание N6.2400 G-R

Страница 1: ...Art Nr 4200 1030 6900A N6 2400 G R N6 2900 G R N7 3600 G R N7 4500 G R Operating instructions For specialist installation engineers Gas burners 2 25 en de fr 4200 1030 7000 it nl 4200 1031 9200 4200 1...

Страница 2: ...achinery directive 2004 108 EC EMC directive 2006 95 EC Low voltage directive 2009 142 EC Gas appliances Directive 97 23 EC Pressure Equipment Directive Pirna 26th May 2010 D HOFFMANN Important inform...

Страница 3: ...wer controller option 5 Housing 6 Gas inlet flange 8 Burner flame tube 10 Integrated electrical cabinet 11 Burner fixing flange 13 Air intake box 14 Mechanical compound 19 Hoisting eyes F6 Air pressur...

Страница 4: ...is provided a stepless control concept The stepless control will allow the burner to be operated at any desired stage between its partial load and full load positions The burner will always be turned...

Страница 5: ...e electric drive unit in dependence of the heat requirement The air damper and the gas damper will be controlled by the same system To ensure an optimum air to fuel adjustment over the full control ra...

Страница 6: ...in the annex and in the documents LFL 1 7451 LGK Functional diagram LFL 1 LGK A Starting type interval A B Flame development interval B Burner has reached operating position B C Burner operation heat...

Страница 7: ...n 5 Actuator SKP 15 6 Actuator SKP 25 7 Gas main valve VGD 8 Gas manometer with push button downstream option 9 Gas tightness control unit en Technical data Input pressure 360 mbar max Ambient tempera...

Страница 8: ...s not allowed to be lined with brickwork Note for reverse flow boilers For reverse flow boilers the dimension T1 is only a recommended value Depending on type of boiler the burner head must stand at l...

Страница 9: ...valves and instruments group care should be taken to observe the flue resistance of the boiler and the gas pressure loss of the burner and valves and instruments group Caution The absence of impuritie...

Страница 10: ...sation probe and of the ignition electrode as per the diagrams Insert the combustion components into the head tighten the mounting screws S3 Connect the ionisation cable IK and the ignition cable ZK o...

Страница 11: ...f the gas line should be of a size designed to guarantee that the gas flow pressure does not drop below the specified level A manual shut off valve not supplied must be fitted upstream of the gas trai...

Страница 12: ...ressure Adjust the max power switch again Burner power should never exceed the max heat generator allowed flame power see chapter entitled Exhaust gas test Decrease power gradually down to min power u...

Страница 13: ...ate the selection of the switching points The cam plates are provided with a small pointer for indicating the switching point of a scale between the setting ranges An additional scale fitted to the en...

Страница 14: ...ke sure the polarity of the device is observed see connection examples for the control box LFL 1 LGK During ionisation monitoring it is important that the signal is transmitted without wastage The con...

Страница 15: ...e of the combustion air fan The pressure switch Dungs LGW has been designed for switching on off or over an electric circuit in the case of changes of the actual pressure levels from the setpoint sett...

Страница 16: ...re proper conditions for start up the distance between the burner and the gas shut off valve must be as low as possible On completion of installation the gas valves and instruments group must be subje...

Страница 17: ...list There follows a general description of the gas train Gas trains with a double valve are intended for the supply main shut off gas filtration gas pressure regulation and monitoring of the gas supp...

Страница 18: ...ptions in accordance with country specific requirements 143 Pressure gauge with pushbutton valve 147 Test burner with pushbutton valve 148 Compensator 154 Gas safety valve additional 313a Max gas pres...

Страница 19: ...re reinstallation NOTE For the installation of the filter mat take care to observe the marking or sticker en Test burner Depending on the country specific requirements when installing steam boilers it...

Страница 20: ...urner s control and safety unit which then starts its cycle If leakage test is NOK red light comes on and no power is fed to the control and safety unit Control cycles have to be restarted manually Ch...

Страница 21: ...ctive parts if necessary Clean the fan wheel and the blower Clean the gas filter replace it if necessary Visual inspection of the burner s electrical components eliminate malfunctions if necessary Che...

Страница 22: ...lts in the relevant documents Important Once the pressure switches have been set they must be protected to prevent settings from being altered For example this can be done by placing a spot of varnish...

Страница 23: ...lace cable search for cause and eliminate Pilot burner failure Adjust ignition gas pressure Ignition gas valve does not open Search for cause and eliminate Defective solenoid Replace 2 Motor running f...

Страница 24: ...ten to the motor bearing noise to identify possible irregularities 4 Mixing unit gives poor combustion data Cause Remedy Incorrect settings Correct settings Incorrect mixture ignition unit Replace uni...

Страница 25: ...ir Damper CLOSED limit switch is missing or a contact is not closed between terminals 12 and 4 or 4 and 5 or the contacts of all control and safety units in the controlled system are not closed e g ga...

Страница 26: ...10 2010 Art Nr 4200 1030 6900A 26...

Страница 27: ...10 2010 Art Nr 4200 1030 6900A 27...