10/2010 - Art. Nr. 4200 1030 6900A

23

Servicing

Exhaust gas test
Trouble shooting instructions

Exhaust gas loss

Exhaust gas loss by way of free heat will 
occur as a result of the temperature 
difference between the fuel-air mixture 
entering the furnace chamber and the 
gases discharged. Any increase in the 
excess of air and the resultant higher 
exhaust gas volume will cause the 
exhaust gas loss to rise. The exhaust 
gas loss can be calculated as follows:

q

A

= exhaust gas loss in %

t

A

= exhaust gas temperature in °C

t

L

= combustion air temperature in °C

CO

2

= volumetric content of carbon

dioxide in %

O

2

= volumetric content of oxygen

in %

q

A

t

A

t

L

(

)

A

1

C O

2

-

-

-

-

-

-

-

-

-

-

-

-

B

+ 

=

In any case of trouble proceed with 
checking the basic conditions for a 
proper operation of the boiler 
system:

1. Is electric power available?
2. Is ther any gas pressure?
3. Are the shut-off valves opened?
4. Are all control and safety instruments 

such as boiler thermostat, water 
supply failure cut-out, limit switches, 
etc. properly set?

1.  Ignition failure

Cause

Remedy

Ignition
electrode short 
circuit.

Adjust
electrodes.

Wide ignition 
electrode
spacing.

Adjust
electrodes.

Dirty and wet 
electrodes.

Clean
electrodes.

Cracked
insulator.

Replace
insulator.

Defective
ignition
transformer.

Replace
transformer.

Defective
automatic
furnace
controller.

Replace
controller.

Burnt ignition 
cable.

Replace cable; 
search for cause 
and eliminate.

Pilot burner 
failure.

Adjust ignition 
gas pressure

Ignition gas 
valve does not 
open.

Search for cause 
and eliminate

Defective
solenoid.

Replace

2. Motor running failure

Cause

Remedy

Motor protection 
relay and fuses.

Check and 
replace if 
required.

Air pressure 
switch not 
changed over or 
defective.

Check and 
replace if 
required.

Defective motor.

Replace motor.

Defective power 
contactor.

Replace
contactor.

Air fan motor 
starts but stops 
after 20-25 secs.

Check for 
solenoid leaks

Air fan motor 
starts, but stops 
after about 10 
secs in pre-
ventilating mode.

Air pressure 
switch fails to 
change over; 
replace switch if 
defective; clean 
switch if dirt has 
accumulated;
check electrical 
connections.

3. No response to flame by 
    automatic furnace controller
    with flame sensor

Cause

Remedy

Dirty flame 
sensor.

Clean flame 
sensor.

Burner fails to 
start.

Check
connection of 
automatic
furnace
controller.

Trouble lamp 
lights; flame 
trouble.

Unlock and 
search for cause

Ionisation
current too 
weak.

Check
combustion
setting.

Burner starts 
without flame 
formation.
Solenoid valve 
fails to open.

Defective coil or 
rectifier.
Check
connection.

Lack of gas or 
gas pressure too 
low.

Check gas 
pressure
controller, gas 
valve, gas filter. 
Is the equipment 
gas cock open?

Example:
Data measured in natural gas mode:
CO

2

 content of exhaust gases 10,8%

Exhaust gas temperature

195°C

Air intake temperature

22°C

The exhaust gas loss can be calculated 
as follows:

Natural

gas

Town

gas

L.P.G.

A

1

 =

0,370

0,350

0,420

B =

0,009

0,011

0,008

en

Содержание N6.2400 G-R

Страница 1: ...Art Nr 4200 1030 6900A N6 2400 G R N6 2900 G R N7 3600 G R N7 4500 G R Operating instructions For specialist installation engineers Gas burners 2 25 en de fr 4200 1030 7000 it nl 4200 1031 9200 4200 1...

Страница 2: ...achinery directive 2004 108 EC EMC directive 2006 95 EC Low voltage directive 2009 142 EC Gas appliances Directive 97 23 EC Pressure Equipment Directive Pirna 26th May 2010 D HOFFMANN Important inform...

Страница 3: ...wer controller option 5 Housing 6 Gas inlet flange 8 Burner flame tube 10 Integrated electrical cabinet 11 Burner fixing flange 13 Air intake box 14 Mechanical compound 19 Hoisting eyes F6 Air pressur...

Страница 4: ...is provided a stepless control concept The stepless control will allow the burner to be operated at any desired stage between its partial load and full load positions The burner will always be turned...

Страница 5: ...e electric drive unit in dependence of the heat requirement The air damper and the gas damper will be controlled by the same system To ensure an optimum air to fuel adjustment over the full control ra...

Страница 6: ...in the annex and in the documents LFL 1 7451 LGK Functional diagram LFL 1 LGK A Starting type interval A B Flame development interval B Burner has reached operating position B C Burner operation heat...

Страница 7: ...n 5 Actuator SKP 15 6 Actuator SKP 25 7 Gas main valve VGD 8 Gas manometer with push button downstream option 9 Gas tightness control unit en Technical data Input pressure 360 mbar max Ambient tempera...

Страница 8: ...s not allowed to be lined with brickwork Note for reverse flow boilers For reverse flow boilers the dimension T1 is only a recommended value Depending on type of boiler the burner head must stand at l...

Страница 9: ...valves and instruments group care should be taken to observe the flue resistance of the boiler and the gas pressure loss of the burner and valves and instruments group Caution The absence of impuritie...

Страница 10: ...sation probe and of the ignition electrode as per the diagrams Insert the combustion components into the head tighten the mounting screws S3 Connect the ionisation cable IK and the ignition cable ZK o...

Страница 11: ...f the gas line should be of a size designed to guarantee that the gas flow pressure does not drop below the specified level A manual shut off valve not supplied must be fitted upstream of the gas trai...

Страница 12: ...ressure Adjust the max power switch again Burner power should never exceed the max heat generator allowed flame power see chapter entitled Exhaust gas test Decrease power gradually down to min power u...

Страница 13: ...ate the selection of the switching points The cam plates are provided with a small pointer for indicating the switching point of a scale between the setting ranges An additional scale fitted to the en...

Страница 14: ...ke sure the polarity of the device is observed see connection examples for the control box LFL 1 LGK During ionisation monitoring it is important that the signal is transmitted without wastage The con...

Страница 15: ...e of the combustion air fan The pressure switch Dungs LGW has been designed for switching on off or over an electric circuit in the case of changes of the actual pressure levels from the setpoint sett...

Страница 16: ...re proper conditions for start up the distance between the burner and the gas shut off valve must be as low as possible On completion of installation the gas valves and instruments group must be subje...

Страница 17: ...list There follows a general description of the gas train Gas trains with a double valve are intended for the supply main shut off gas filtration gas pressure regulation and monitoring of the gas supp...

Страница 18: ...ptions in accordance with country specific requirements 143 Pressure gauge with pushbutton valve 147 Test burner with pushbutton valve 148 Compensator 154 Gas safety valve additional 313a Max gas pres...

Страница 19: ...re reinstallation NOTE For the installation of the filter mat take care to observe the marking or sticker en Test burner Depending on the country specific requirements when installing steam boilers it...

Страница 20: ...urner s control and safety unit which then starts its cycle If leakage test is NOK red light comes on and no power is fed to the control and safety unit Control cycles have to be restarted manually Ch...

Страница 21: ...ctive parts if necessary Clean the fan wheel and the blower Clean the gas filter replace it if necessary Visual inspection of the burner s electrical components eliminate malfunctions if necessary Che...

Страница 22: ...lts in the relevant documents Important Once the pressure switches have been set they must be protected to prevent settings from being altered For example this can be done by placing a spot of varnish...

Страница 23: ...lace cable search for cause and eliminate Pilot burner failure Adjust ignition gas pressure Ignition gas valve does not open Search for cause and eliminate Defective solenoid Replace 2 Motor running f...

Страница 24: ...ten to the motor bearing noise to identify possible irregularities 4 Mixing unit gives poor combustion data Cause Remedy Incorrect settings Correct settings Incorrect mixture ignition unit Replace uni...

Страница 25: ...ir Damper CLOSED limit switch is missing or a contact is not closed between terminals 12 and 4 or 4 and 5 or the contacts of all control and safety units in the controlled system are not closed e g ga...

Страница 26: ...10 2010 Art Nr 4200 1030 6900A 26...

Страница 27: ...10 2010 Art Nr 4200 1030 6900A 27...

Страница 28: ...60 1731 Zellik 02 4631902 ELCOTHERM AG Sarganserstrasse 100 7324 Vilters 0848 808 808 ELCO GmbH Dreieichstr 10 64546 M rfelden Walldorf 0180 3526180 ELCO Italia S p A Via Roma 64 31023 Resana TV 800...

Отзывы: