PROGRAMMING OF THE DIGITAL OUTPUT (

SET   DO1         SET   DO2

)

 

The DO1 and DO2 digital outputs have three modality of functioning: PULSE, alarm (ALR)  and REMOTE  command. 
The DO1 modality setting is independent from DO2. For example it’s possible to set DO1 on PULSE (pulse emission) 
and DO2 on alarm mode (ALR). 

 

In the menu SET   DO1  and SET   DO2  it’s possible to program the function of all digital outputs. In these menus are 
available the following modality: PULSE, ALR  and REMOTE. 
In  PULSE  mode the digital output DO1 will emit pulses proportional to the active energy counted while the digital 
output DO2 will emit pulses proportional to the reactive energy counted. The proportionality will depend from the 
PULSE set in the SETUP and the duration of the impulse is set in the TPL  voice of the SETUP. 
The ALR  modality is divided in two parts: ALR   SYS   3PH and ALR   SYS   123. With ALR   SYS   3PH the digital 
output will function as alarm verifying that the three phase value doesn’t exceed the threshold set (ALR   HI  and ALR 
LO).  With  ALR   SYS   123 the digital output will function as alarm verifying that the maximum value of the single 
phases doesn’t exceed the maximum threshold set (ALR   HI)  and that the minimum value of the single phases 
doesn’t come down the minimum threshold set (ALR   LO).  The activation of the alarm output will come after some 
seconds of delay set(ALR   DL). 
In the REMOTE  mode, the output status will be decided from the status of the correspondent MODBUS register (see 
protocol modbus manual for ELM). 
Enter to menu: 

ELM-4D1P 

instruction manual

IM443-U v0.7 

pag. 9

 

seT  UP  

Æ

 

seT  Up 

RESET 
SET   DO1 
SET   DO2 
SET   AN   OUT 
SET   HR_ 
--- OFF   OFF  

(the visualization depends on the settings and the I/O status) 

 

Pul se 

To choose the output modality

 

ALR   SYS   3PH  (selecting 

PULSE or 

ALR   PH_ 123  

BY_ REMOTE 

BY_  REMOTE  

the setting finish) 

 

ALR   SEl VLN 
ALR   SEl AMP 
ALR   SEl AN  (only for ALR   SYS   3PH) 
ALR   SEl P.f  

To chose the parameter

 

ALR   SEl ACT  

to control

 

ALR   SEl REA  

(see variable list) 

ALR   SEl APP 
ALR   SEl VLL 
ALR   SEL   FRE  (only for ALR   SYS   3PH) 
Alr sel T

°

c (only for ALR   SYS   3PH) 

 

Set maximum alarm threshold 

Increase

 

 

ALR   HI  

Decrease 

(after 0 there is OFF) 

 

Set minimum alarm threshold 

Increase

 

 

ALR   LO  

Decrease 

(after 0 there is OFF) 

 

Set delay 

Increase 

ALR   Dl  

Decrease 

Confirm and end of digital output settings.

 

Содержание ELM-4D1P

Страница 1: ...485 and with analog output OPTIONS Power Supply 20 60 Vac 24 72 Vcc C1 Power Supply 85 230 Vac 90 250 Vcc C2 Insulated current inputs T MEASURED PARAMETERS parameters unit of measurement initial ident...

Страница 2: ...Vac dc version Terminals Power Supply Terminals Power Supply Terminals Power Supply 19 20 0 110V 100 125Vac 50 60Hz 19 21 0 230V 220 240Vac 50 60Hz 19 23 0 400V 380 415Vac 50 60Hz 19 21 20 60Vac 24 7...

Страница 3: ...WIRING DIAGRAMS W ELM 4D1P instruction manual IM443 U v0 7 pag 3...

Страница 4: ...internalCT S1 I1 S2 auxiliary power supply S1 I2 S2 S1 ELM I3 S2 VL1 VL2 VL3 N with Ineutral option In VL1 VL2 VL3 N L1 S1 L2 P1 L3 S1 S2 L1 L2 L3 S1 S2 N P1 P2 P1 P2 CT connection to Voltage insertio...

Страница 5: ...lay indicates also the values of the active and reactive energy counters Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical m...

Страница 6: ...ynchronism 50 type 60 version with digital output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase f...

Страница 7: ...of the CT rate will be possible to set this value example with CT 1000 5the value will be 200 Pressing the A key confirm and go away with the next setting Programming of the average time seT AVG T Aft...

Страница 8: ...e password is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instrument at the enter of the set...

Страница 9: ...tput will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the...

Страница 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Страница 11: ...ing the C key the message SET AN OUT will appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will...

Страница 12: ...key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO P...

Страница 13: ...the measures appear on the L1 display Visualization section 2 At the same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltage va...

Страница 14: ...er maximum three phase powers max maxD avg I L1 max avg I L2 max avg I L3 max avg I N max avg phase and neutral currents maximum of average phase and neutral currents max demand max maxD avg W max avg...

Страница 15: ...electrically disturbed it is suggested to use 100 120ohm 1 2W resistors placed between the common of the RS485 outlet and the shielded cable For other information on the serial line it s better to se...

Страница 16: ...auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse P...

Отзывы: